Analysis of influencing factors on buffer layer discharge for high-voltage XLPE cable

被引:11
|
作者
Wu, Zhiheng [1 ]
Lai, Qingbo [1 ,2 ]
Zhou, Wenqing [1 ]
Liu, Xiaodong [3 ]
Chen, Jie [4 ]
Hu, Libin [4 ]
Hao, Yanpeng [1 ]
Liu, Gang [1 ]
机构
[1] South China Univ Technol, Sch Elect Power Engn, Guangzhou 510641, Peoples R China
[2] Hunan Elect Power Design Inst Co Ltd, China Energy Engn Grp, Changsha, Hunan, Peoples R China
[3] Guangzhou Nanyang Cable Grp Holding Co Ltd, Guangzhou, Peoples R China
[4] State Grid Jiangsu Elect Power Co Ltd, Elect Power Res Inst, Nanjing, Peoples R China
关键词
32;
D O I
10.1049/gtd2.12585
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In the high-voltage (HV) cross-linked polyethylene (XLPE) cable, the buffer layer has the function of electrical connection and water-blocking. However, after water invades cables, the buffer layer discharge defect may occur, which can lead to the breakdown accident of cable line. It does serious harm to the safe and stable operation of the power system. At present, the buffer layer discharge defect has not been sufficiently investigated in existing research. This paper establishes a voltage distribution calculation model for analyzing the buffer layer discharge defect. The mechanism of how the presence of air gap and white marks (the corrosion products) between aluminium sheath and buffer layer influencing the voltage distribution inside cable is involved in this model. Based on the simulation software, a convenient method for solving the model is proposed. Using this model, the internal voltage distribution results of the cable under different forms of white marks are obtained. The influencing factors affecting the discharge of buffer layer are analyzed. The validity of the model is proved by the discharge test of the cable with controllable defects. The results show that the risk of buffer layer discharge can be quantitatively assessed by the white mark defect feature.
引用
收藏
页码:4142 / 4157
页数:16
相关论文
共 50 条
  • [1] Study on the ablation process and failure mechanism of the buffer layer in high-voltage XLPE cable
    Tian, Yi
    Zhu, Guixin
    Miao, Qingqing
    Huang, Jiasheng
    Huang, Xinbo
    Li, Shengtao
    Li, Licheng
    INTERNATIONAL JOURNAL OF ELECTROCHEMICAL SCIENCE, 2024, 19 (08):
  • [2] Partial Discharge Behaviors in High Voltage Cable Buffer Layer
    Du, Y.
    Du, B. X.
    Li, X.
    Li, Z. J.
    Xi, X. G.
    Song, P. X.
    Fang, J.
    Kong, X. X.
    Li, J.
    PROCEEDINGS OF THE 2020 3RD IEEE INTERNATIONAL CONFERENCE ON DIELECTRICS (ICD 2020), 2020, : 826 - 829
  • [3] Capacitive coupling detection and characteristic analysis of partial discharge in high-voltage XLPE power cable joints
    Jiang, Yun
    Min, Hong
    Xia, Rong
    Li, Wen-Jie
    Gaodianya Jishu/High Voltage Engineering, 2010, 36 (08): : 2005 - 2011
  • [4] Breakpoint and Moisture Detection Method Based on Distributed Brillouin Optical Fiber Built in Buffer Layer of High-Voltage XLPE Cable
    Cheng, Yanting
    Hao, Yanpeng
    Li, Qishun
    Hui, Baojun
    Tian, Wanxing
    Tan, Haotian
    Chen, Linhao
    Li, Licheng
    IEEE SENSORS JOURNAL, 2024, 24 (02) : 1443 - 1452
  • [5] Distributed Optical Fiber Detection Based on BOTDR for Buffer Layer Defects of High-Voltage XLPE Cable With Corrugated Aluminum Sheath
    Cheng, Yanting
    Hao, Yanpeng
    Tian, Wanxing
    Zhao, Peng
    Tan, Haotian
    Li, Qishun
    Li, Licheng
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2024, 31 (04) : 1778 - 1787
  • [6] DEVELOPMENT OF XLPE-MOULDED JOINT FOR HIGH-VOLTAGE XLPE INSULATED CABLE
    OHATA, K
    KOJIMA, H
    SHIMOMURA, T
    ASAHI, K
    IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1983, 102 (07): : 1935 - 1941
  • [7] Failure investigation of buffer layers in high-voltage XLPE cables
    Chen, Yun
    Hui, Baojun
    Cheng, Yanting
    Hao, Yanpeng
    Fu, Mingli
    Yang, Lin
    Hou, Shuai
    Li, Licheng
    ENGINEERING FAILURE ANALYSIS, 2020, 113
  • [8] Annealing Effects on XLPE Insulation of Retired High-Voltage Cable
    Xie, Yue
    Zhao, Yifeng
    Liu, Gang
    Huang, Jiasheng
    Li, Licheng
    IEEE ACCESS, 2019, 7 : 104344 - 104353
  • [9] An investigation on discharge fault in buffer layer of 220 kV XLPE AC cable
    Du, Boxue
    Du, Xiaoyu
    Kong, Xiaoxiao
    Li, Jin
    Li, Zhijian
    Li, Xu
    IET SCIENCE MEASUREMENT & TECHNOLOGY, 2021, 15 (06) : 508 - 516
  • [10] Study on Ablation between Metal Sheath and Buffer Layer of High Voltage XLPE Insulated Power Cable
    Jiang, Lei
    Xin, Yue
    Yan, Wenbo
    Zhao, Xiyuan
    Yao, Ruifeng
    Shen, Zhuoyuan
    Gao, Jinghui
    Zhong, Lisheng
    Wald, Detlef F.
    Ren, Zhigang
    2019 2ND INTERNATIONAL CONFERENCE ON ELECTRICAL MATERIALS AND POWER EQUIPMENT (ICEMPE 2019), 2019, : 372 - 375