Diagnostics of thermal aging of transformer bushings with solid insulation

被引:0
|
作者
Subocz, Jan [1 ]
Zenker, Marek [1 ]
Mrozik, Andrzej [1 ]
机构
[1] Zachodniopomorski Uniwersytet Technol Szczecinie, Wydzial Elekt, Katedra Elektrotechnol & Diagnost, PL-70313 Szczecin, Poland
来源
PRZEGLAD ELEKTROTECHNICZNY | 2012年 / 88卷 / 5A期
关键词
relaxation; FDS; RVM; transformer bushing; thermovision;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The paper presents advanced diagnostic methods of transformer bushings. There are given results of temperature distribution modeling inside bushings' cores and the analysis of ageing influence on dielectric response of RIP type bushing model, based on the FDS and RVM characteristics. Thermal ageing of RIP bushing model causes the shift of FDS curves into higher frequencies, whereas deterioration products lead to appearance of additional relaxation in high frequency range. (Diagnostics of thermal aging of transformer bushings with solid insulation).
引用
收藏
页码:86 / 89
页数:4
相关论文
共 50 条
  • [21] Study on the influence of preload on the thermal aging of transformer oil-paper insulation
    Liu J.
    Wang F.-Y.
    Dianji yu Kongzhi Xuebao/Electric Machines and Control, 2020, 24 (06): : 127 - 134
  • [22] Thermal aging studies on cellulose insulation paper of power transformer using AFM
    Ruijin, Liao
    Chao, Tang
    Lijun, Yang
    Huanchao, Chen
    ICPASM 2005: PROCEEDINGS OF THE 8TH INTERNATIONAL CONFERENCE ON PROPERTIES AND APPLICATIONS OF DIELECTRIC MATERIALS, VOLS 1 AND 2, 2006, : 722 - +
  • [23] Electrical and chemical diagnostics of transformer insulation - Part A: Aged transformer samples
    Univ of Queensland, Queensland
    IEEE Trans Power Delivery, 4 (1547-1554):
  • [24] A solid insulation ageing model application to oil-filled power transformer for operation diagnostics
    Konogray, S. P.
    ELECTRICAL ENGINEERING & ELECTROMECHANICS, 2010, (01) : 43 - 45
  • [25] Insulation Condition Assessment of Power Transformer Bushings by Utilizing High Voltage Lightning Impulses
    Nikjoo, Roya
    Taylor, Nathaniel
    Edin, Hans
    2015 IEEE EINDHOVEN POWERTECH, 2015,
  • [26] Monitoring and diagnostic of transformer solid insulation
    van Bolhuis, JP
    Gulski, E
    Smit, JJ
    IEEE TRANSACTIONS ON POWER DELIVERY, 2002, 17 (02) : 528 - 536
  • [27] The Influence of Organic Acid on Thermal Aging of Power Transformer Oil-paper Insulation
    Cui Yunguang
    Wu Guangning
    Wang Xiaojian
    Peng Qian
    Chen Ling
    Gao Bo
    2013 IEEE CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA (CEIDP), 2013, : 116 - 119
  • [28] Terahertz Time Domain Spectroscopy of Transformer Insulation Paper after Thermal Aging Intervals
    Wang, Liang
    Tang, Chao
    Zhu, Shiping
    Zhou, Shengling
    MATERIALS, 2018, 11 (11):
  • [29] Effects of Impulse Loads on the Thermal Aging of Traction Transformer Oil-paper Insulation
    Liao W.
    Zhou L.
    Li H.
    Zhang C.
    Dai L.
    Li Z.
    Gaodianya Jishu/High Voltage Engineering, 2021, 47 (04): : 1403 - 1410
  • [30] Influence of Metal Transformer Materials on Oil-Paper Insulation after Thermal Aging
    Wang, Deng
    Zhu, Zhiping
    Zhang, Li
    Qian, Yihua
    Su, Wei
    Chen, Tiansheng
    Fan, Shengping
    Zhao, Yaohong
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2019, 26 (02) : 554 - 560