Simulation and Experiment Analysis of 10 kV Flexible Grounding Device

被引:3
|
作者
Liu, Mengxuan [1 ]
Zhang, Chi [1 ]
Liu, Kangli [1 ]
机构
[1] Southeast Univ, Sch Elect Engn, Nanjing 210096, Peoples R China
关键词
flexible grounding; single-phase grounding fault; control system; current compensation; fault detection; line protection; FAULT ARC-SUPPRESSION; SINGLE-PHASE; PROTECTION; PRINCIPLE;
D O I
10.3390/info12090384
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
The traditional 10 kV distribution network grounding system has some disadvantages, such as small grounding current and poor arc extinguishing effect, thus, hindering the detection of high-resistance grounding fault. Therefore, this paper studied the flexible grounding system consisting of small-resistance and active inverter in parallel. The control system comprises the compensation current calculation module, the fault detection module, and line protection strategy. During a single-phase grounding fault, the device is designed to inject a current of a given amplitude and phase into the neutral point to effectively suppress fault-point voltage and current and, meanwhile, quickly identifying the fault line or the busbar fault and then systematically protecting the distribution line. In addition, a large number of simulations have performed based on three grounding faults (metal, low-resistance, and high-resistance) and two modes (ungrounded and small-resistance grounding). The device can all be functional. Finally, a 400 V-level experimental prototype was built, and the experimental results are consistent with the simulation results, which can verify the effectiveness and feasibility of the flexible grounding device.
引用
收藏
页数:12
相关论文
共 50 条
  • [1] Simulation calculation of impulse grounding resistance of 10 kV distribution line, Part 3: methods comparison and device development
    Weng, Ruo-fang
    Bian, Xiao-liang
    Long, Peng
    Cai, Qiu-ye
    Guo, Xiang
    Si, Wen-rong
    2021 13TH INTERNATIONAL CONFERENCE ON MEASURING TECHNOLOGY AND MECHATRONICS AUTOMATION (ICMTMA 2021), 2021, : 118 - 126
  • [2] Review of grounding fault testing and design of real experiment field for 10 kV distribution network
    Wang P.
    Feng G.
    Wei Y.
    Wang L.
    Chen M.
    Wang X.
    Zeng Z.
    Cheng F.
    Dianli Xitong Baohu yu Kongzhi/Power System Protection and Control, 2020, 48 (11): : 178 - 187
  • [3] Dynamic simulation analysis of the flexible swap device
    Cui, Yan-Bo
    Zhao, La-Sheng
    Zhang, Qiang
    Zhang, Jian-Xin
    Journal of Donghua University (English Edition), 2015, 32 (02) : 300 - 304
  • [4] Dynamic Simulation Analysis of the Flexible Swap Device
    崔艳波
    赵腊生
    张强
    张建新
    Journal of Donghua University(English Edition), 2015, 32 (02) : 300 - 304
  • [5] Transient Analysis and Simulation of a Single-Phase Grounding Fault in 20kV Small Resistance Grounding System
    Zhou, Yuan
    Zhao, Xiaofeng
    Cui, Xiaolong
    Yang, Ruixiong
    Lai, Jiayuan
    PROCEEDINGS OF 2019 IEEE 3RD INTERNATIONAL ELECTRICAL AND ENERGY CONFERENCE (CIEEC), 2019, : 1101 - 1105
  • [6] Dynamics Simulation of 10 kV Cable Tunnel Fire for Single-phase Arc Grounding Fault
    Liu S.
    Hu Y.
    Zheng J.
    Su X.
    Xu Y.
    Gaodianya Jishu/High Voltage Engineering, 2021, 47 (12): : 4341 - 4348
  • [7] Simulation calculation of impulse grounding resistance of 10 kV distribution line, Part 1: model construction
    Long, Peng
    Weng, Ruo-fang
    Cai, Qiu-ye
    Peng, Bo
    Zhao, Dan-dan
    Si, Wen-rong
    2021 13TH INTERNATIONAL CONFERENCE ON MEASURING TECHNOLOGY AND MECHATRONICS AUTOMATION (ICMTMA 2021), 2021, : 110 - 117
  • [8] Design of overvoltage monitoring device for 10 kV power grid and contrastive analysis of its measured and simulation waveforms
    Zhou, Kai
    Xiong, Qing
    He, Min
    Ran, Li
    Gaodianya Jishu/High Voltage Engineering, 2015, 41 (01): : 35 - 41
  • [9] Grounding Design and Fault Analysis of MMC Based Flexible Interconnection Device in Future Distribution Networks
    Zang, Jiajie
    Wang, Jiacheng
    Zhang, Jianwen
    Zhou, Jianqiao
    2018 IEEE INTERNATIONAL POWER ELECTRONICS AND APPLICATION CONFERENCE AND EXPOSITION (PEAC), 2018, : 2102 - 2107
  • [10] Analysis of 10kV Grid Arc Grounding Over-voltage Hazards and Countermeasures
    You Hongxia
    Li Yueyue
    Su Hainan
    Zhang Junyi
    Li Lijun
    Bai Xue
    Chen Runjing
    2016 CHINA INTERNATIONAL CONFERENCE ON ELECTRICITY DISTRIBUTION (CICED), 2016,