Hydronic radiant floor for heating and cooling coupled with an underground heat exchanger: Modeling approach and results

被引:0
|
作者
Zmeureanu, Radu [1 ]
Brau, Jean [2 ]
机构
[1] Concordia Univ, Dept Bldg Civil & Environm Engn, Ctr Bldg Studies, Montreal, PQ H3G 1M8, Canada
[2] Inst Natl Sci Appl, Inst Natl Sci Appl, CETHIL, F-69621 Villeurbanne, France
关键词
simulation; radiant floor; heating; cooling; heat exchanger; underground;
D O I
暂无
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
This paper explores the Simulation of the thermal performance of a radiant floor for healing and Cooling that is connected with an underground heat exchanger installed under the concrete floor of a house. In the heating season, an electric boiler is used to maintain the operative temperature at the set point value by varying the supply water temperature to the radiant slab. In the cooling season, the water from the radiant floor is circulated through an underground heat exchanger installed under the concrete slab. This water is then mixed with the return water, and it is supplied to the radiant slab. The system does not use energy for mechanical cooling. The paper presents also the sensitivity analysis of the model to the efficiency of underground heat exchanger and the mixing ratio between the water flow rate circulated through the under-round heat exchanger and the water flow rate circulated through the radiant floor.
引用
收藏
页码:315 / +
页数:2
相关论文
共 50 条
  • [21] Corrosion on brazing parts of copper heat-exchanger for hydronic heating system
    Sakai M.
    Aoki T.
    Nakamura M.
    Itano Y.
    [J]. Zairyo to Kankyo/ Corrosion Engineering, 2011, 60 (03): : 129 - 131
  • [22] Heating and cooling systems with heat exchanger piles
    Fromentin, A
    Pahud, D
    Sarlos, G
    [J]. ENERGY AND ENVIRONMENT, 1998, : 230 - 234
  • [23] Study on heating capacity and heat loss of capillary radiant floor heating systems
    Ding, Pei
    Li, Yanru
    Long, Enshen
    Zhang, Yin
    Liu, Qinjian
    [J]. APPLIED THERMAL ENGINEERING, 2020, 165
  • [24] Hybrid ground coupled heat exchanger systems for space heating/cooling applications: A review
    Soni, Suresh Kumar
    Pandey, Mukesh
    Bartaria, Vishvendra Nath
    [J]. RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2016, 60 : 724 - 738
  • [25] Experimental evaluation of a radiant heated floor coupled to an air-to-water heat pump for the cooling of greenhouses
    Valino, V.
    Perdigones, A.
    Garcia, J. L.
    Luna, L.
    [J]. SPANISH JOURNAL OF AGRICULTURAL RESEARCH, 2010, 8 (03) : 580 - 591
  • [26] Radiant Floor Cooling Systems: A Critical Review of Modeling Methods
    Bizzarri, Marco
    Conti, Paolo
    Glicksman, Leon R.
    Schito, Eva
    Testi, Daniele
    [J]. ENERGIES, 2023, 16 (17)
  • [27] Modeling a radiant floor system with Phase Change Material (PCM) integrated into a building simulation tool: Analysis of a case study of a floor heating system coupled to a heat pump
    Mazo, Javier
    Delgado, Monica
    Marin, Jose Maria
    Zalba, Belen
    [J]. ENERGY AND BUILDINGS, 2012, 47 : 458 - 466
  • [28] Performance assessment of a ground-coupled heat pump for an office room heating using radiator or radiant floor heating systems
    Sebarchievici, Calin
    Dan, Daniel
    Sarbu, Ioan
    [J]. DEFINING THE FUTURE OF SUSTAINABILITY AND RESILIENCE IN DESIGN, ENGINEERING AND CONSTRUCTION, 2015, 118 : 88 - 100
  • [29] Dynamic heat transfer modeling and parametric study of thermoelectric radiant cooling and heating panel system
    Luo, Yongqiang
    Zhang, Ling
    Liu, Zhongbing
    Wang, Yingzi
    Wu, Jing
    Wang, Xiliang
    [J]. ENERGY CONVERSION AND MANAGEMENT, 2016, 124 : 504 - 516
  • [30] A micro photovoltaic-heat pump system for house heating by radiant floor: some experimental results
    Izquierdo, M.
    de Agustin, Pablo
    Martin, E.
    [J]. PROCEEDINGS OF THE 2ND INTERNATIONAL CONFERENCE ON SOLAR HEATING AND COOLING FOR BUILDINGS AND INDUSTRY (SHC 2013), 2014, 48 : 865 - 875