A Modified Aging Kinetics Model for Aging Condition Prediction of Transformer Polymer Insulation by Employing the Frequency Domain Spectroscopy

被引:13
|
作者
Liu, Jiefeng [1 ]
Fan, Xianhao [1 ]
Zhang, Yiyi [1 ]
Zheng, Hanbo [1 ]
Wang, Zixiao [1 ]
Zhao, Xixi [1 ]
机构
[1] Guangxi Univ, Coll Elect Engn, Nanning 530004, Guangxi, Peoples R China
基金
中国国家自然科学基金;
关键词
transformer polymer insulation; Frequency Domain Spectroscopy (FDS); aging kinetics model; aging condition prediction; degree of polymerization (DP); OIL-PAPER INSULATION; POWER TRANSFORMERS; OIL/PAPER SYSTEM; PART; DEGRADATION; MOISTURE;
D O I
10.3390/polym11122082
中图分类号
O63 [高分子化学(高聚物)];
学科分类号
070305 ; 080501 ; 081704 ;
摘要
The aging kinetics model is of great interest to scholars since it is capable of describing the variation law between the degree of polymerization (DP) and the aging duration of transformer polymer (cellulose) insulation. However, it is difficult to determine the moisture content inside the transformer polymer insulation without destroying it, so that the model parameters cannot be confirmed. Such limitation greatly restricts its application. It is interesting to note that as long as the moisture content of the transformer polymer insulation could be characterized (replaced) by a certain feature parameter, the above issue will be solved naturally. The existing researches indicate that the Frequency Domain Spectroscopy (FDS) is sensitive to moisture. Consequently, the feature parameter that could characterize the moisture inside transformer polymer insulation (extracted from the FDS curve) can be used to report a modified aging kinetics model, which could perform the aging condition prediction of transformer polymer insulation under various test conditions, including aging duration, aging temperature, and initial moisture. In that respect, the average relative error of prediction results of prepared samples is equal to 7.41%, which reveals that the reported model might be serviced as a potential tool for the aging condition prediction of transformer polymer insulation.
引用
收藏
页数:15
相关论文
共 50 条
  • [31] Assessment of Oil-Paper Insulation Aging Using Frequency Domain Spectroscopy and Moisture Equilibrium Curves
    Yang, Lijun
    Zou, Tiantian
    Deng, Bangfei
    Zhang, Haibing
    Mo, Yang
    Peng, Pan
    IEEE ACCESS, 2019, 7 : 45670 - 45678
  • [32] Influence of the Mechanical-Thermal Aging on the Frequency-Domain Dielectric Spectroscopy of Cellulose Insulation Paper
    Li C.
    Hao A.
    Diangong Jishu Xuebao/Transactions of China Electrotechnical Society, 2019, 34 (17): : 3705 - 3712
  • [33] Moisture Determination of the Main Insulation in a Transformer by Frequency-Domain Spectroscopy
    Yao, Renyun
    Zhou, Quan
    Yang, Lijun
    Gao, Jun
    IEEJ TRANSACTIONS ON ELECTRICAL AND ELECTRONIC ENGINEERING, 2017, 12 (06) : 809 - 816
  • [34] Broadband Frequency Domain Dielectric Spectroscopy of Cellulose Insulation Material in Transformer
    Wang, Shengkang
    Lin, Fuchang
    Li, Hua
    2023 IEEE ELECTRICAL INSULATION CONFERENCE, EIC, 2023,
  • [35] Understanding the Impact of Moisture and Ageing of Transformer Insulation on Frequency Domain Spectroscopy
    Jadav, Raj B.
    Ekanayake, Chandima
    Saha, Tapan K.
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2014, 21 (01) : 369 - 379
  • [36] Prediction of Dissolved Alcohol Concentrations in Transformer Oil and Aging Evaluation of Cellulose Insulation
    Zhang, Heng
    Zhang, Yuan
    Jiang, Zaijun
    Fan, Xianhao
    Li, Wen
    Liu, Chuying
    Zhang, Enze
    Wu, Thomas
    Liu, Jiefeng
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2025, 32 (02) : 1238 - 1245
  • [37] A MODIFIED COOPERATIVE MODEL OF RELAXATION AND AGING KINETICS
    KUBAT, DG
    BERTILSSON, H
    KUBAT, J
    UGGLA, S
    JOURNAL OF PHYSICS-CONDENSED MATTER, 1992, 4 (34) : 7041 - 7052
  • [38] Frequency domain dielectric properties of accelerated aging generator stator insulation
    Gao B.
    Hao C.-J.
    Yin X.-B.
    Chen Z.-X.
    Xu J.
    Wu G.-N.
    Dianji yu Kongzhi Xuebao/Electric Machines and Control, 2019, 23 (03): : 57 - 64
  • [39] Influence of organic acids on thermal aging and frequency domain dielectric spectroscopy characteristics of oil-paper insulation
    Wu, Guangning
    Wang, Xiaojian
    Li, Xianlang
    Gao, Bo
    Peng, Qian
    Li, Wei
    Gaodianya Jishu/High Voltage Engineering, 2014, 40 (05): : 1424 - 1432
  • [40] Feasibility Research of Aging Status Assessment of Steam Turbine Generator Insulation by Frequency-Domain Dielectric Spectroscopy
    Yu Xiaofeng
    Wu Guangning
    2016 IEEE ELECTRICAL INSULATION CONFERENCE (EIC), 2016, : 639 - 642