共 49 条
Bayesian assessments for acceptable airborne bacteria levels in air-conditioned spaces
被引:3
|作者:
Wong, L. T.
[1
]
Mui, K. W.
[1
]
Hui, P. S.
[1
]
Chan, W. Y.
[1
]
机构:
[1] Hong Kong Polytech Univ, Dept Bldg Serv Engn, Hong Kong, Hong Kong, Peoples R China
关键词:
air-conditioned space;
airborne bacteria level;
Bayesian assessment;
humidity;
temperature;
D O I:
10.1177/1420326X07086223
中图分类号:
TU [建筑科学];
学科分类号:
0813 ;
摘要:
The level of indoor airborne bacteria is usually selected as a reference to identify the cleanliness of a Heating, Ventilating and Air-Conditioning system. This study proposes an epistemic approach for assessing acceptance of air-conditioned spaces against certain acceptable airborne bacteria levels. From the thermal environmental conditions and a sample test of the airborne bacteria level, the assessment model can give a rapid estimation of the probability of an unsatisfactory indoor environment. An office having a higher risk of unsatisfactory Indoor Air Quality (IAQ) would require a lower sample test value to fulfill the IAQ acceptance at certain confidence level. The model parameters were determined from databases of 529 air-conditioned spaces in Hong Kong, with airborne bacteria levels ranging from 41 to 2304CFU . m(-3), air temperatures from 13.4 to 27.8 degrees C and relative humidities from 29 to 88%. This model would be useful to policymakers for making a fast response to the microbiological pollutant problem while avoiding an inappropriate level of reliance on the results.
引用
收藏
页码:80 / 86
页数:7
相关论文