Advanced control of condensing temperature for enhancing the operating efficiency of air-cooled chillers

被引:20
|
作者
Yu, FW [1 ]
Chan, KT [1 ]
机构
[1] Hong Kong Polytech Univ, Dept Bldg Serv Engn, Kowloon, Hong Kong, Peoples R China
关键词
air-cooled chiller; condenser fans; condensing temperature; efficiency;
D O I
10.1016/j.buildenv.2004.08.017
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Air-cooled chillers are commonly used to provide cooling energy in commercial buildings in the subtropical climate. These chillers have long been considered inefficient because they operate under head pressure control where the condensing temperature is kept high in the refrigeration cycle. This paper considers a novel method to strategically lower the condensing temperature to enhance chiller efficiency at any outdoor temperature. An experiment is carried out on an air-cooled reciprocating chiller to confirm that an electronic expansion valve enables refrigerant to be adequately fed into the evaporator in all operating conditions, even when the condensing temperature falls to around 20 degreesC. By enhancing the heat rejection airflow of the condenser, both the condensing temperature and chiller power can decrease considerably with less fluctuation. According to the algorithm of staging condenser fans, this enhancement corresponds to resetting the set point of the condensing temperature based on any outdoor temperature. The potential and benefits of implementing this reset strategy are discussed. (C) 2004 Elsevier Ltd. All rights reserved.
引用
下载
收藏
页码:727 / 737
页数:11
相关论文
共 50 条
  • [1] Reducing the condensing temperature to improve the efficiency of air-cooled chillers
    Fu, WY
    Kwok, TC
    PROCEEDINGS OF THE 3RD INTERNATIONAL SYMPOSIUM ON HEAT TRANSFER ENHANCEMENT AND ENERGY CONSERVATION, VOLS 1 AND 2, 2004, : 180 - 185
  • [2] Simulation of floating condensing temperature control for air-cooled chillers
    Yu, Fu Wing
    Chan, Kwok Tai
    PROCEEDINGS OF THE 3RD ASIAN CONFERENCE ON REFRIGERATION AND AIR-CONDITIONING VOLS I AND II, 2006, : 55 - +
  • [3] Optimum setpoint of condensing temperature for air-cooled chillers
    Chan, KT
    Yu, FW
    HVAC&R RESEARCH, 2004, 10 (02): : 113 - 127
  • [4] Applying condensing-temperature control in air-cooled reciprocating water chillers for energy efficiency
    Chan, KT
    Yu, FW
    APPLIED ENERGY, 2002, 72 (3-4) : 565 - 581
  • [5] Parameterization study on the operating efficiency of air-cooled chillers
    Chan, KT
    Yu, FW
    ADVANCES IN BUILDING TECHNOLOGY, VOLS I AND II, PROCEEDINGS, 2002, : 1157 - 1164
  • [6] Analysis of the component characteristics of air-cooled chillers for modelling floating condensing temperature control
    Chan, KT
    Yu, FW
    ENERGY CONVERSION AND MANAGEMENT, 2005, 46 (06) : 927 - 939
  • [7] Hybrid Artificial Neural Network-Genetic Algorithm Technique for Condensing Temperature Control of Air-Cooled Chillers
    Yang, Jia
    Chan, K. T.
    Dai, Tongyong
    Yu, F. W.
    Chen, Lei
    9TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATION AND AIR CONDITIONING (ISHVAC) JOINT WITH THE 3RD INTERNATIONAL CONFERENCE ON BUILDING ENERGY AND ENVIRONMENT (COBEE), 2015, 121 : 706 - 713
  • [8] Advanced control of heat rejection airflow for improving the coefficient of performance of air-cooled chillers
    Yu, FW
    Chan, KT
    APPLIED THERMAL ENGINEERING, 2006, 26 (01) : 97 - 110
  • [9] Thermodynamic-behaviour model for air-cooled screw chillers with a variable set-point condensing temperature
    Chan, KT
    Yu, FW
    APPLIED ENERGY, 2006, 83 (03) : 265 - 279
  • [10] Optimum placement for air-cooled chillers
    Khankari, Kishor, 1600, ASHRAE (58):