Lightning Impulse Breakdown Voltage of Rice Bran Oil for Transformer Application

被引:1
|
作者
Hamid, Mardhiah Hayati Abdul [1 ]
Ishak, Mohd Taufiq [1 ]
Suhaimi, Nur Sabrina [1 ]
Adnan, Jaafar [1 ]
Makmor, Nazrul Fariq [1 ]
Katim, Nurul Izzatul Akma [2 ]
Abd Rahman, Rahisham [3 ]
机构
[1] Natl Def Univ Malaysia, Fac Engn, Dept Elect & Elect Engn, Kuala Lumpur 57000, Malaysia
[2] Malaysian Allied Hlth Sci Acad MAHSA Univ, Fac Engn & Built Environm, Jenjarom 42610, Selangor, Malaysia
[3] Univ Tun Hussein Onn Malaysia, Fac Elect & Elect Engn, Batu Pahat 86400, Johor, Malaysia
关键词
rice bran oi; transformer liquid insulation; vegetable oils; lightning impulse breakdown voltage; power transformer and dielectric material; NATURAL ESTER; PALM OIL; INSULATING LIQUID; NONUNIFORM FIELD; COCONUT OIL; PROPAGATION;
D O I
10.3390/en14165084
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Transformer oil does not only serve as an insulating liquid, but also in removing heat from the windings and cores. Mineral oil (MO) has been widely used in transformers for more than 150 years. Recently, researchers have attempted to search for alternative insulating oils due to the possibility that MO will run out in the future together with the concern on fire safety and environmental pollution. Among the potential oils is rice bran oil (RBO). This work presents the studies of the lightning impulse (LI) of RBO behavior under various electric fields, gap distances and testing methods. The electrical performances of LI tests show that RBO and Palm Oil (PO) have lower LI breakdown voltage than MO under both uniform and non-uniform electric fields. However, the difference in LI breakdown voltages between RBO, PO and MO are slightly small which is less than 20%. In addition, there is no significant effect in the various testing methods under both uniform field and non-uniform field where the percentages of difference are less than 12% and 8% respectively. The data of LI breakdown voltage were statistically analysed to predict the withstand voltage and 50% breakdown voltage of oil samples by using Weibull distribution. The Weibull distribution of MO, PO and RBO has well fit with the fitting line. Finally, the relationship between LI voltages under a non-uniform field with various parameters of PO and RBO was obtained and proposed. From this work, it can be concluded that RBO shows promising results to be considered as an alternative to MO in transformer applications.
引用
收藏
页数:22
相关论文
共 50 条
  • [1] Effect of magnetic nanoparticles on the lightning impulse breakdown voltage of transformer oil
    Ghasemi, J.
    Jafarmadar, S.
    Nazari, M.
    JOURNAL OF MAGNETISM AND MAGNETIC MATERIALS, 2015, 389 : 148 - 152
  • [2] Barrier effect on the time lag to breakdown of transformer oil gaps under lightning impulse voltage
    Zouaghi, A
    Beroual, A
    1998 ANNUAL REPORT CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA, VOLS 1 AND 2, 1998, : 444 - 447
  • [3] Pre-breakdown and Breakdown Mechanisms of an Inhibited Gas to Liquid Hydrocarbon Transformer Oil under Negative Lightning Impulse Voltage
    Lu, W.
    Liu, Q.
    Wang, Z. D.
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2017, 24 (05) : 2809 - 2818
  • [4] Effect of oscillation frequency on the breakdown characteristics of transformer oil in a highly nonuniform field under lightning impulse voltage
    Guo, Ruochen
    Hou, Zhiqiang
    Wang, Zhen
    He, Cong
    Zhang, Xuanrui
    Li, Junhao
    Jin, Yuhui
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2020, 27 (03) : 812 - 819
  • [5] Breakdown Characteristics of Transformer Oil with Cellulose Particles in a Non-uniform Field under Lightning Impulse Voltage
    Guo, Ruochen
    Wang, Zhen
    He, Cong
    Zhang, Xuanrui
    Meng, Xuan
    Li, Junhao
    Han, Xutao
    Yao, Xiu
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2020, 27 (05) : 1627 - 1635
  • [6] Prebreakdown and Breakdown Mechanisms of an Inhibited Gas to Liquid Hydrocarbon Transformer Oil under Positive Lightning Impulse Voltage
    Lu, W.
    Liu, Q.
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2016, 23 (04) : 2450 - 2461
  • [7] Influence of Electrode Geometry on the Lightning Impulse Breakdown Voltage of Palm Oil
    Thien, Y. V.
    Azis, N.
    Jasni, J.
    Yunus, R.
    Ab Kadir, M. Z. A.
    Yaakub, Z.
    2018 IEEE PES ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), 2018,
  • [8] Breakdown Behaviour of Oil-Barrier Insulation at Lightning Impulse Voltage
    Haller, R.
    Hornak, J.
    Trnka, P.
    Hamar, R.
    Hlavacek, J.
    2020 21ST INTERNATIONAL SCIENTIFIC CONFERENCE ON ELECTRIC POWER ENGINEERING (EPE), 2020, : 466 - 471
  • [9] Investigation on Transformer Oil Impedance during Breakdown under Impulse Voltage
    Abdi, S.
    Boubakeur, A.
    Haddad, A.
    Harid, N.
    2014 ELECTRICAL INSULATION CONFERENCE (EIC), 2014, : 5 - 9
  • [10] Breakdown Voltage of Transformer Oil Containing Cellulose Particle Contamination With and Without Bridge Formation Under Lightning Impulse Stress
    Bin Saaidon, Sarizan
    Talib, Mohd Aizam
    Rohani, Mohamad Nur Khairul Hafizi
    Muhamad, Nor Asiah
    Jamil, Mohamad Kamarol Mohd
    IEEE ACCESS, 2021, 9 : 147994 - 148003