Newly Developed and Cost-Effective Submersible Dry-Type Network Transformers

被引:0
|
作者
Tran, Nguyen N. [1 ]
Johnson, Charles W. [2 ]
Tedesco, Joseph L. [1 ]
机构
[1] ASEA Brown Boveri ABB Power T&D Co, Business Res & Dev Dept, 171 Ind Dr, Bland, VA 24315 USA
[2] ASEA Brown Boveri ABB Power T&D Co, Technol Dev Ctr, 171 Ind Dr, Bland, VA 24315 USA
关键词
Cast Coil; Dry-type; IEEE C37.20.07; C57.12.01; C57.12.52; C57.12.91; Submersible; Ground switch; Network transformers; Distribution; Underground transformer; transformer design optimization; OPTIMIZATION; DESIGN;
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
This paper describes the development of submersible dry-type network transformers. These transformers are safer for the public and are less potentially damaging to the environment. The dry-type transformers are installed in a sealed corrosive-resistant tank and are capable of operating in open air, partially submerged or completely submerged. The ratings are in the range of 100 kVA to about 1500 kVA and 25-kV voltage. A HV grounding switch is installed in the tank with electromechanical interlock to prevent closing when energized and with externally operated handle. Dimensions and losses are comparable to those of liquid-immersed transformers. Tank pressure and tank air temperature can be remotely monitored. These network transformers have been tested and verified to be compliant to IEEE C37.20.07, C57.12.01, C57.12.52, and C57.12.91.
引用
收藏
页数:5
相关论文
共 50 条
  • [21] Thermal modeling of disc-type winding for ventilated dry-type transformers
    Lee, Moonhee
    Abdullah, Hussein A.
    Jofriet, Jan C.
    Patel, Dhiru
    ELECTRIC POWER SYSTEMS RESEARCH, 2010, 80 (01) : 121 - 129
  • [22] Temperature rise analysis and calculation of cast resin dry-type transformers
    Xiong, L. (lxiong@cqu.edu.cn), 1600, Science Press (39):
  • [23] Analysis of temperature distribution in cast-resin dry-type transformers
    Rahimpour, Ebrahim
    Azizian, Davood
    ELECTRICAL ENGINEERING, 2007, 89 (04) : 301 - 309
  • [24] Enhanced thermal modeling of three-phase dry-type transformers
    Americo, Jonatas P.
    Leite, Jean V.
    Mazzola, Cristian F.
    CASE STUDIES IN THERMAL ENGINEERING, 2024, 58
  • [25] SPECIFYING DRY-TYPE DISTRIBUTION TRANSFORMERS FOR SOLID-STATE APPLICATIONS
    KERSZENBAUM, I
    MAZUR, A
    MISTRY, M
    FRANK, J
    IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1991, 27 (01) : 173 - 178
  • [26] Analysis of Temperature Distribution in Cast-resin Dry-type Transformers
    Ebrahim Rahimpour
    Davood Azizian
    Electrical Engineering, 2007, 89 : 301 - 309
  • [27] Dry-type transformers: Specification, installation, and operational impacts in a marine environment
    Equisales Associates Inc., Houston, TX 77047, United States
    不详
    不详
    IEEE Ind Appl Mag, 2013, 5 (68-75):
  • [28] Air temperature effect on thermal models for ventilated dry-type transformers
    Lee, Moonhee
    Abdullah, Hussein A.
    Jofriet, Jan C.
    Patel, Dhiru
    Fahrioglu, Murat
    ELECTRIC POWER SYSTEMS RESEARCH, 2011, 81 (03) : 783 - 789
  • [29] A Review of Thermal and Electrical Designs for Dry-type Transformers and Future Perspectives
    Xu, Hang
    Matharage, Shanika
    Wang, Zhongdong
    Squire, Darron
    Syzwala, Henry
    Fazakarley, Mark
    2024 IEEE ELECTRICAL INSULATION CONFERENCE, EIC 2024, 2024, : 380 - 383
  • [30] A comparison of liquid-filled and dry-type transformers for industrial applications
    Dooley, PK