Partial discharge, dissipation factor, and corona aspects for high voltage electric generator stator bars and windings

被引:19
|
作者
Emery, FT [1 ]
机构
[1] Siemens Westinghouse Power Corp, Charlotte, NC 28273 USA
关键词
partial discharge; corona; high voltage generators; power factor; electrical insulation;
D O I
10.1109/TDEI.2005.1430403
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
High voltage stator windings in modern electric generators are subject to high electrical, mechanical, and thermal stress. Operation of these machines in both air and high pressure hydrogen results in different considerations. Operation in the air environment does not offer the dielectric advantages of operating in high-pressure hydrogen. The two major design factors that are significant for the design of high voltage stator bars to be operated in air, are corona activity and PD activity. These of course are closely related. With the movement to increasing the power density of generators, which means operation at higher voltages and higher insulation stress levels, it has become more critical to be sure the design constraints are met in the stator bar design to minimize both partial discharge activity and corona activity involving the stator bars. The stator bar insulation system must be designed for minimum partial discharge activity and ideally is corona free at the stator winding operating stress levels, and at the operating conditions (temperature and pressure) the generator is subject to. This paper will present the findings associated with the development work in designing, testing and implementing a PD reduced and corona free design.