Retrofit of R-410A in Air to Water Heat Pumps: Test of Two Low GWP Candidates

被引:0
|
作者
Zoughaib, Assaad [1 ]
Besbes, Karim [2 ]
机构
[1] Mines ParisTech, Ctr Energy Efficiency Syst CES, Paris, France
[2] CES, Paris, France
关键词
D O I
暂无
中图分类号
O414.1 [热力学];
学科分类号
摘要
This paper presents an experimental evaluation of two low GWP refrigerants candidates for the replacement of R-410A in an "air to water" heat pump. The baseline is evaluated following the ANSI/AHRI Standard 551/591. For both low GWP candidates (ARM-70 alpha and DR-5), tests are performed following the same standard for three refrigerant charges. Both heat capacity and coefficient of performance are compared for the baseline and the tests with the low GWP refrigerants. The results show that for the best refrigerant charge, both heat capacity and COP are improved by 5 to 10%. The best refrigerant charge is found for both replacement candidates.
引用
收藏
页数:6
相关论文
共 50 条
  • [31] Condensation heat transfer and pressure drop of R-410A in a 7.0 mm O.D. microfin tube at low mass fluxes
    Nae-Hyun Kim
    [J]. Heat and Mass Transfer, 2016, 52 : 2833 - 2847
  • [32] Air to water heat pumps for heating system retrofit in urban areas: understanding the multi-faceted challenge
    Calame, Nicole
    Freyre, Alisa
    Rognon, Fabrice
    Callegari, Simon
    Ruetschi, Matthias
    [J]. CLIMATE RESILIENT CITIES - ENERGY EFFICIENCY & RENEWABLES IN THE DIGITAL ERA (CISBAT 2019), 2019, 1343
  • [33] CONDENSATION HEAT TRANSFER AND PRESSURE DROP OF R-410A IN 5.0-MM-OD SMOOTH OR MICROFIN TUBES AT LOW MASS FLUXES
    Kim, Nae-Hyun
    [J]. JOURNAL OF ENHANCED HEAT TRANSFER, 2016, 23 (05) : 349 - 370
  • [34] Preliminary Design of a Compressor Oil Reliability Test Loop Using a Low GWP Refrigerant as an Alternative to R410A in VRF Systems
    Cho, Junhyun
    Lee, Gilbong
    Choi, Bongsu
    Oh, Bong Seong
    Na, Sun-Ik
    Wang, Eunseok
    Ra, Ho-Sang
    Baik, Young-Jin
    Hur, Gyunchul
    Cho, Jongjae
    Lee, Beomjoon
    Shin, Hyungki
    [J]. TRANSACTIONS OF THE KOREAN SOCIETY OF MECHANICAL ENGINEERS B, 2022, 46 (11) : 627 - 632
  • [35] Lubrication of R290 Rotary Compressor Used in Low-Temperature Air-Water Heat Pumps
    Shi, Hongyan
    Lei, Bowen
    Wu, Jianhua
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION, 2022, 144 : 163 - 174
  • [36] COMPARATIVE EXPERIMENTAL RESEARCHES OF AIR-TO-WATER HEAT PUMP WITH R32 AND R410A FOR HOUSEHOLD
    Huang, Y.
    Yin, Q.
    Yu, J.
    Wang, J.
    [J]. 23RD IIR INTERNATIONAL CONGRESS OF REFRIGERATION, 2011, 23 : 796 - +
  • [37] A NON-FLAMMABLE LOW GWP REFRIGERANT FOR CENTRIFUGAL CHILLERS AND HIGH TEMPERATURE HEAT PUMPS: R-1336mzz(Z)
    Juhasz, Jason
    Kontomaris, Konstantinos
    [J]. 1ST IIR INTERNATIONAL CONFERENCE ON THE APPLICATION OF HFO REFRIGERANTS, 2018, : 231 - 237
  • [38] Energy and Exergy Analysis of Low-Global Warming Potential Refrigerants as Replacement for R410A in Two-Speed Heat Pumps for Cold Climates
    Shen, Bo
    Ally, Moonis R.
    [J]. ENERGIES, 2020, 13 (21)
  • [39] Energetic and Exergetic Analysis of Low Global Warming Potential Refrigerants as Substitutes for R410A in Ground Source Heat Pumps
    Bobbo, Sergio
    Fedele, Laura
    Curcio, Marco
    Bet, Anna
    De Carli, Michele
    Emmi, Giuseppe
    Poletto, Fabio
    Tarabotti, Andrea
    Mendrinos, Dimitris
    Mezzasalma, Giulia
    Bernardi, Adriana
    [J]. ENERGIES, 2019, 12 (18)
  • [40] Drop-in analysis of R450A and R513A as low-GWP alternatives to R134a in a water-to-water heat pump
    Molinaroli, Luca
    Lucchini, Andrea
    Colombo, Luigi Pietro Maria
    [J]. International Journal of Refrigeration, 2022, 135 : 139 - 147