Retrofit of R-410A in Air to Water Heat Pumps: Test of Two Low GWP Candidates

被引:0
|
作者
Zoughaib, Assaad [1 ]
Besbes, Karim [2 ]
机构
[1] Mines ParisTech, Ctr Energy Efficiency Syst CES, Paris, France
[2] CES, Paris, France
关键词
D O I
暂无
中图分类号
O414.1 [热力学];
学科分类号
摘要
This paper presents an experimental evaluation of two low GWP refrigerants candidates for the replacement of R-410A in an "air to water" heat pump. The baseline is evaluated following the ANSI/AHRI Standard 551/591. For both low GWP candidates (ARM-70 alpha and DR-5), tests are performed following the same standard for three refrigerant charges. Both heat capacity and coefficient of performance are compared for the baseline and the tests with the low GWP refrigerants. The results show that for the best refrigerant charge, both heat capacity and COP are improved by 5 to 10%. The best refrigerant charge is found for both replacement candidates.
引用
收藏
页数:6
相关论文
共 50 条
  • [1] DROP IN LIFE CYCLE CLIMATE PERFORMANCE OF LOW GWP R-410A ALTERNATIVES FOR HEAT PUMPS
    Li, Gang
    Alabdulkarem, Abdullah
    Hwang, Yunho
    Raderviacher, Reinhard
    [J]. 11TH IIR GUSTAV LORENTZEN CONFERENCE ON NATURAL REFRIGERANTS (2014): NATURAL REFRIGERANTS AND ENVIRONMENTAL PROTECTION, 2014, : 1011 - 1022
  • [2] Numerical Modelling and Seasonal Performance Analysis of Air-toWater Heat Pumps Using Low-GWP Refrigerant R-454B as an Alternative to R-410A
    Dongellini, Matteo
    Naldi, Claudia
    Siam, Raffaele
    Morini, Gian Luca
    [J]. 6TH IIR CONFERENCE ON THERMOPHYSICAL PROPERTIES AND TRANSFER PROCESSES OF REFRIGERANTS (TPTPR2021), 2021, : 153 - 160
  • [3] Two-phase pressure drop of air-water and R-410A in small horizontal tubes
    Chen, IY
    Yang, KS
    Chang, YJ
    Wang, CC
    [J]. INTERNATIONAL JOURNAL OF MULTIPHASE FLOW, 2001, 27 (07) : 1293 - 1299
  • [4] Comparative Performance of Low Global Warming Potential (GWP) Refrigerants as Replacement for R-410A in a Regular 2-Speed Heat Pump for Sustainable Cooling
    Shen, Bo
    Ally, Moonis R.
    [J]. SUSTAINABILITY, 2021, 13 (15)
  • [5] Performance Study of Double Pipe Internal Heat Exchanger in R-410a Air Conditioning System
    Djuanda
    [J]. INTERNATIONAL CONFERENCE ON THERMAL SCIENCE AND TECHNOLOGY (ICTST) 2017, 2018, 1984
  • [6] Seasonal performance assessment of refrigerants with low GWP as substitutes for R410A in heat pump air conditioning devices
    Devecioglu, Atilla Gencer
    [J]. APPLIED THERMAL ENGINEERING, 2017, 125 : 401 - 411
  • [7] HFC32, a low GWP substitute for HFC410A in medium size chillers and heat pumps
    Longo, Giovanni A.
    Mancin, Simone
    Righetti, Giulia
    Zilio, Claudio
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2015, 53 : 62 - 68
  • [8] TWO-PHASE FLOW BOILING HEAT TRANSFER OF R-22 AND R-410A IN HORIZONTAL MICROCHANNELS
    Rifaldi, M.
    Pamitran, A. S.
    Choi, Kwang-Il
    Oh, Jong-Taek
    Hrnjak, Pega
    [J]. ACRA 2009: PROCEEDINGS OF THE 4TH ASIAN CONFERENCE ON REFRIGERATION AND AIR-CONDITIONING, 2009, : 143 - 148
  • [9] R-410A and R-404A real gas thermodynamic relations and their application for predicting exergy efficiency in vapor compression heat pumps
    Stegou-Sagia, A.
    Papadaki, A.
    Loakim, V.
    [J]. FORSCHUNG IM INGENIEURWESEN-ENGINEERING RESEARCH, 2006, 70 (04): : 253 - 261
  • [10] Statistical optimization of Closed Loop Pulsating Heat Pipe parameters with R-410a and nanorefrigerant in air conditioning applications
    Veerasamy, Aruna
    Balakrishnan, Kanimozhi
    Abdul Razack, Sirajunnisa
    [J]. ENERGY SOURCES PART A-RECOVERY UTILIZATION AND ENVIRONMENTAL EFFECTS, 2021,