Air quality in rooms conditioned by chilled ceiling and mixed displacement ventilation for energy saving

被引:25
|
作者
Chakroun, W. [1 ]
Ghali, K. [2 ]
Ghaddar, N. [2 ]
机构
[1] Kuwait Univ, Dept Mech Engn, Safat 13060, Kuwait
[2] Amer Univ Beirut, Dept Mech Engn, Beirut 11072020, Lebanon
关键词
Contaminant transport in plumes; Indoor air quality with mixed return air; Chilled ceiling displacement ventilation; SYSTEM; OPERATION; DESIGN; MODEL;
D O I
10.1016/j.enbuild.2011.06.019
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
A transient-contaminant-transport model is developed for assessing IAQ in the breathing zone when introducing return air into rooms conditioned by CC/DV system to save energy. The steady state transport model of [1] is extended to transient conditions while accounting for significant wall plumes associated with external loads. Experiments are performed to validate the extended model predictions of IAQ expressed in the level of CO2 concentration. Experiments are conducted in a chamber with two external walls in Kuwait Climate. Measurements are recorded in time of the air temperature and CO2 concentration at selected locations in the room and compared with values predicted by the model. Experimental results agreed well with model predictions. The maximum errors in predicted CO2 concentrations are less than +/- 25 ppm in presence of external load. 60% fresh air fraction resulted in 37% less energy consumption compared with 100% fresh air CC/DV system. The validated model is applied to a case study in Kuwait to evaluate energy saving over the cooling season for a typical office space while using mixed DV air. Energy savings of up to 20.6% can be realized using mixed supply air while maintaining IAQ compared with energy used for the 100% fresh air. (C) 2011 Elsevier B.V. All rights reserved.
引用
收藏
页码:2684 / 2695
页数:12
相关论文
共 50 条
  • [21] Optimized selection and operation of the combined chilled ceiling system and displacement ventilation
    Ghaddar, N.
    Ghali, K.
    Saadeh, R.
    INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 2010, 34 (15) : 1328 - 1340
  • [22] A nodal model for displacement ventilation and chilled ceiling systems in office spaces
    Rees, SJ
    Haves, P
    BUILDING AND ENVIRONMENT, 2001, 36 (06) : 753 - 762
  • [23] Indoor air quality in rooms with cooled ceilings. Mixing ventilation or rather displacement ventilation?
    Behne, M
    ENERGY AND BUILDINGS, 1999, 30 (02) : 155 - 166
  • [24] Chilled ceiling and displacement ventilation system: Laboratory study with high cooling load
    Schiavon, Stefano
    Bauman, Fred S.
    Tully, Brad
    Rimmer, Julian
    SCIENCE AND TECHNOLOGY FOR THE BUILT ENVIRONMENT, 2015, 21 (07) : 944 - 956
  • [25] Impact of chilled ceiling on indoor air distribution in a room with mixing ventilation
    Wu, Xiaozhou
    Gao, Jie
    Lv, Pin
    Wang, Haichao
    Wang, Shugang
    Wang, Fenghao
    SCIENCE AND TECHNOLOGY FOR THE BUILT ENVIRONMENT, 2020, 26 (03) : 366 - 376
  • [26] Simplified model for thermal comfort, IAQ and energy savings in rooms conditioned by displacement ventilation aided with transient personalized ventilation
    Al Assaad, Douaa
    Habchi, Carine
    Ghali, Kamel
    Ghaddar, Nesreen
    ENERGY CONVERSION AND MANAGEMENT, 2018, 162 : 203 - 217
  • [27] A novel operating strategy to avoid dew condensation for displacement ventilation and chilled ceiling system
    Guo, Shaopeng
    Tian, Yuchen
    Fan, Donghao
    Wu, Wenfei
    Zhao, Jun
    Jin, Guang
    Wang, Xiaotong
    APPLIED THERMAL ENGINEERING, 2020, 176
  • [28] Model-based optimal supervisory control of chilled ceiling displacement ventilation system
    Keblawi, A.
    Ghaddar, N.
    Ghali, K.
    ENERGY AND BUILDINGS, 2011, 43 (06) : 1359 - 1370
  • [29] Numerical investigation of transient buoyant flow in a room with a displacement ventilation and chilled ceiling system
    Rees, SJ
    McGuirk, JJ
    Haves, P
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2001, 44 (16) : 3067 - 3080
  • [30] Experimental and computational investigation into suppressing natural convection in chilled ceiling/displacement ventilation environments
    Taki, A. H.
    Jalil, L.
    Loveday, D. L.