Air quality in rooms conditioned by chilled ceiling and mixed displacement ventilation for energy saving

被引:25
|
作者
Chakroun, W. [1 ]
Ghali, K. [2 ]
Ghaddar, N. [2 ]
机构
[1] Kuwait Univ, Dept Mech Engn, Safat 13060, Kuwait
[2] Amer Univ Beirut, Dept Mech Engn, Beirut 11072020, Lebanon
关键词
Contaminant transport in plumes; Indoor air quality with mixed return air; Chilled ceiling displacement ventilation; SYSTEM; OPERATION; DESIGN; MODEL;
D O I
10.1016/j.enbuild.2011.06.019
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
A transient-contaminant-transport model is developed for assessing IAQ in the breathing zone when introducing return air into rooms conditioned by CC/DV system to save energy. The steady state transport model of [1] is extended to transient conditions while accounting for significant wall plumes associated with external loads. Experiments are performed to validate the extended model predictions of IAQ expressed in the level of CO2 concentration. Experiments are conducted in a chamber with two external walls in Kuwait Climate. Measurements are recorded in time of the air temperature and CO2 concentration at selected locations in the room and compared with values predicted by the model. Experimental results agreed well with model predictions. The maximum errors in predicted CO2 concentrations are less than +/- 25 ppm in presence of external load. 60% fresh air fraction resulted in 37% less energy consumption compared with 100% fresh air CC/DV system. The validated model is applied to a case study in Kuwait to evaluate energy saving over the cooling season for a typical office space while using mixed DV air. Energy savings of up to 20.6% can be realized using mixed supply air while maintaining IAQ compared with energy used for the 100% fresh air. (C) 2011 Elsevier B.V. All rights reserved.
引用
收藏
页码:2684 / 2695
页数:12
相关论文
共 50 条
  • [1] Energy Saving Using Mixed Air in Rooms Conditioned by Chilled Ceiling Displacement Ventilation System
    Chakroun, W.
    Ghali, K.
    Ghaddar, N.
    ASHRAE TRANSACTIONS 2011, VOL 117, PT 2, 2011, 117 : 67 - 75
  • [2] Simplified Model of Contaminant Dispersion in Rooms Conditioned by Chilled-Ceiling Displacement Ventilation System
    Kanaan, M.
    Ghaddar, N.
    Ghali, K.
    HVAC&R RESEARCH, 2010, 16 (06): : 765 - 783
  • [3] New airborne pathogen transport model for upper-room UVGI spaces conditioned by chilled ceiling and mixed displacement ventilation: Enhancing air quality and energy performance
    Kanaan, Mohamad
    Ghaddar, Nesreen
    Ghali, Kamel
    Araj, Georges
    ENERGY CONVERSION AND MANAGEMENT, 2014, 85 : 50 - 61
  • [4] Indoor thermal environment in rooms with combined air conditioning system of displacement ventilation and chilled ceiling panel
    School of Muni. and Eviron. Eng., Xi'an Univ. of Arch. and Tech, Xi'an 710055, China
    Xi'an Jianzhu Keji Daxue Xuebao, 2007, 4 (558-562):
  • [5] Combining chilled ceiling, displacement ventilation and desiccant dehumidification for indoor air quality and thermal comfort
    Hao, XL
    Zhang, GQ
    Chen, YM
    Zou, SH
    INDOOR AIR 2005: PROCEEDINGS OF THE 10TH INTERNATIONAL CONFERENCE ON INDOOR AIR QUALITY AND CLIMATE, VOLS 1-5, 2005, : 1248 - 1253
  • [6] Room air stratification in combined chilled ceiling and displacement ventilation systems
    Schiavon, Stefano
    Bauman, Fred
    Tully, Brad
    Rimmer, Julian
    HVAC&R RESEARCH, 2012, 18 (1-2): : 147 - 159
  • [7] Chilled ceiling and displacement ventilation system for energy savings: A case study
    Ghali, K.
    Ghaddar, N.
    Ayoub, M.
    INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 2007, 31 (08) : 743 - 759
  • [8] An Energy Efficient Air Conditioning System using Displacement Ventilation and Chilled Ceiling for Modern Office Buildings
    Parameshwaran, R.
    Karunakaran, R.
    Muthumariappan, S.
    Bipasha, S.
    INTERNATIONAL JOURNAL OF VENTILATION, 2010, 9 (01) : 25 - 44
  • [9] Evaporative cooler improves transient thermal comfort in chilled ceiling displacement ventilation conditioned space
    Ghaddar, Nesreen
    Ghali, Kamel
    Chakroun, Walid
    ENERGY AND BUILDINGS, 2013, 61 : 51 - 60
  • [10] An experimental study of air flow and temperature distribution in a room with displacement ventilation and a chilled ceiling
    Rees, Simon J.
    Haves, Philip
    BUILDING AND ENVIRONMENT, 2013, 59 : 358 - 368