Experimental investigation of a loop heat pipe with a flat evaporator and cupric oxide nanofluids as working fluid

被引:11
|
作者
Zhao, Tianyuan [1 ]
Ma, Zhengyuan [1 ]
Zhang, Zikang [1 ]
Deng, Weizhong [1 ]
Long, Rui [1 ]
Liu, Wei [1 ]
Ma, Lei [2 ]
Liu, Zhichun [1 ]
机构
[1] Huazhong Univ Sci & Technol, Sch Energy & Power Engn, Wuhan 430074, Peoples R China
[2] Shenzhen Technol Univ, Coll New Mat & New Energies, Shenzhen 518118, Peoples R China
基金
中国国家自然科学基金;
关键词
Loop heat pipe; Flat evaporator; Nanofluids; Heat transfer enhancement; THERMAL PERFORMANCE; WATER NANOFLUID; WICK; FLOW;
D O I
10.1016/j.egyr.2021.10.114
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Loop heat pipe (LHP) is widely used in high-power electronic cooling as a passive cooling device. In this paper, the LHP system was designed with a flat evaporator and a capillary biporous wick with cupric oxide nanofluids as working fluid in LHP. The capillary biporous wick was sintered by nickel powder and the nanofluids were prepared by a two-step method. The startup tests, variable heat load tests, and performance degradation tests of LHP were conducted respectively and the thermal resistance was further analyzed. The results showed that, compared with distilled water, the maximum heat load increased from 290 W to 310 W and the minimum startup heat load decreased from 40 W to 20 W with nanofluids as working fluid. Both the temperature of the evaporator wall and the thermal resistance were reduced in startup tests. At the heat load of 50 W, the performance improvement was the most noticeable, where the temperature of the evaporator wall was reduced by 12.7 degrees C, the thermal resistance of the evaporator was reduced by 26.9%, and the thermal resistance of the LHP system was reduced by 17.6%. With a variable heat load ranging from 50 W to 290 W, the response speed of LHP became faster and the temperature fluctuation was smaller. The LHP with nanofluids as working fluid still operated normally and the change of thermal resistance with the varies of heat load had the same tendency as the previous experiment in performance degradation tests of 2 months. (C) 2021 The Authors. Published by Elsevier Ltd.
引用
收藏
页码:7693 / 7703
页数:11
相关论文
共 50 条
  • [21] Experimental study of the loop heat pipe with a flat disk-shaped evaporator
    Wang, Dongdong
    Liu, Zhichun
    Shen, Jun
    Jiang, Chi
    Chen, Binbin
    Yang, Jinguo
    Tu, Zhengkai
    Liu, Wei
    EXPERIMENTAL THERMAL AND FLUID SCIENCE, 2014, 57 : 157 - 164
  • [22] Experimental study on the operating characteristics of a flat bifacial evaporator loop heat pipe
    Joung, Wukchul
    Yu, Taeu
    Lee, Jinho
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2010, 53 (1-3) : 276 - 285
  • [23] Experimental study on operating parameters of miniature loop heat pipe with flat evaporator
    Wang, Shuangfeng
    Huo, Jiepeng
    Zhang, Xianfeng
    Lin, Zirong
    APPLIED THERMAL ENGINEERING, 2012, 40 : 318 - 325
  • [24] Transient responses of the flat evaporator loop heat pipe
    Joung, Wukchul
    Gam, Keesool
    Park, Kwangmin
    Ma, Sungpil
    Lee, Jinho
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2013, 57 (01) : 131 - 141
  • [25] Research and development of loop heat pipe with flat evaporator
    Xiong K.
    Wu W.
    Wang S.
    Huagong Jinzhan/Chemical Industry and Engineering Progress, 2021, 40 (10): : 5388 - 5402
  • [26] Experimental study on a liquid nitrogen temperature region loop heat pipe with flat evaporator
    Zhang C.
    Xie R.
    Zhang T.
    Lu D.
    Wu Y.
    Hong F.
    Beijing Hangkong Hangtian Daxue Xuebao/Journal of Beijing University of Aeronautics and Astronautics, 2019, 45 (06): : 1211 - 1217
  • [27] Theoretical and Experimental Studies on an Ammonia-Based Loop Heat Pipe With a Flat Evaporator
    Adoni, Abhijit A.
    Ambirajan, Amrit
    Jasvanth, V. S.
    Kumar, D.
    Dutta, Pradip
    IEEE TRANSACTIONS ON COMPONENTS AND PACKAGING TECHNOLOGIES, 2010, 33 (02): : 478 - 487
  • [28] Experimental studies on a high performance compact loop heat pipe with a square flat evaporator
    Li, Ji
    Wang, Daming
    Peterson, G. P.
    APPLIED THERMAL ENGINEERING, 2010, 30 (6-7) : 741 - 752
  • [29] Experimental study on a novel loop heat pipe with both flat evaporator and boiling pool
    Lu, Xiao
    Wei, Jin-Jia
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2014, 79 : 54 - 63
  • [30] Experimental Investigation of Designer Working Fluids in a Flat Heat Pipe
    Supowit, Jacob
    Yamada, Kouhei
    Catton, Ivan
    2015 31ST ANNUAL SEMICONDUCTOR THERMAL MEASUREMENT, MODELING & MANAGEMENT SYMPOSIUM (SEMI-THERM), 2015, : 68 - 74