Experimental study on frosting suppression for a finned-tube evaporator using ultrasonic vibration

被引:56
|
作者
Wang, Dingyuan [1 ]
Tao, Tangfei [1 ]
Xu, Guanghua [1 ]
Luo, Ailing [1 ]
Kang, Shaoying [1 ]
机构
[1] Xi An Jiao Tong Univ, Sch Mech Engn, Xian 710049, Shaanxi, Peoples R China
关键词
Evaporator; Frost suppression; Defrost; Ultrasonic vibration;
D O I
10.1016/j.expthermflusci.2011.03.002
中图分类号
O414.1 [热力学];
学科分类号
摘要
An experimental study was conducted to investigate the possibility and the effect of frost release from a finned-tube evaporator by using ultrasonic vibrations in natural convection. A compressor was adopted as cold source, and a finned-tube evaporator was placed horizontal on the frames inside a chamber. The aluminum fins surface was covered with hydrophilic coatings whose contact angle of the water drop of the surface is 37.7 degrees, and the fins had wing-cases to enlarge the heat-exchange area. The thickness of a fin was approximately 0.1 mm, and the gap distance between any two fins of the evaporator was about 1.55 mm in average. An ultrasonic transducer with resonance 28.2 kHz and rating power 60 W was adopted as a vibrator to excite the evaporator. A microscopic image system was used to observe and record the whole frosting process with/without ultrasonic vibrations, a method of frost thickness measurement on the double sides of a fin was present and realized through digital image processing technology. From microscopic view, the deposited frost nearly block the fins gaps when the compressor worked for 32 min without ultrasonic vibration, while almost 2/3 of the gaps between two neighbor fins were unblocked when the compressor worked for 92 min with ultrasonic vibration, which shows that the frost deposited on the fins surfaces could be suppressed with high frequency ultrasonic vibrations. From macroscopic view, the frost growing on the fins are being vibrated to fall off and accumulated under the evaporator to form frost piles. Although the fins above the braze tubes were deposited with frost, the fins between any two neighboring tubes were unblocked. Experiments show that the basic ice layer on the fins cannot be removed with ultrasonic vibrations, but frost crystals and frost branches on the ice layer can be fractured and removed effectively, the frost growing on the evaporator can be suppressed by using ultrasonic vibrations. The main mechanism of ultrasonic frost suppression maybe mainly attributed to the high frequency ultrasonic mechanical vibrations that can break up frost crystals and frost layers, then frost will fall off with the gravity, not to ultrasonic cavitation effect or heat effect. (C) 2011 Elsevier Inc. All rights reserved.
引用
收藏
页码:1 / 11
页数:11
相关论文
共 50 条
  • [31] EXPERIMENTAL AND NUMERICAL STUDY OF THE CHARACTERISTICS OF FINNED-TUBE OIL RADIATORS OF POWER ENGINEERING DEVICES
    Skrypnik, A. N.
    Ermakov, A. M.
    Kalimullin, R. T.
    Mironov, A. A.
    Popov, I. A.
    Chorny, A. D.
    Zhukova, Yu, V
    Marshalova, G. S.
    HEAT TRANSFER RESEARCH, 2020, 51 (14) : 1261 - 1271
  • [32] Experimental Investigation of Phase Change inside a Finned-Tube Heat Exchanger
    Rahimi, M.
    Ranjbar, A. A.
    Ganji, D. D.
    Sedighi, K.
    Hosseini, M. J.
    JOURNAL OF ENGINEERING, 2014, 2014
  • [33] Transient modeling of an adsorber using finned-tube heat exchanger
    Riffel, Douglas B.
    Wittstadt, Ursula
    Schmidt, Ferdinand P.
    Nunez, Tomas
    Belo, Francisco A.
    Leite, Antonio P. F.
    Ziegler, Felix
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2010, 53 (7-8) : 1473 - 1482
  • [34] An experimental study on the effects of frosting conditions on frost distribution and growth on finned tube heat exchangers
    Zhang, Long
    Jiang, Yiqiang
    Dong, Jiankai
    Yao, Yang
    Deng, Shiming
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2019, 128 : 748 - 761
  • [35] PERFORMANCE OF FINNED-TUBE HEAT-EXCHANGERS UNDER FROSTING CONDITIONS .1. SIMULATION-MODEL
    KONDEPUDI, SN
    ONEAL, DL
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 1993, 16 (03): : 175 - 180
  • [36] Finned-tube condenser design optimization using thermoeconomic isolation
    Stewart, Susan W.
    Shelton, Samuel V.
    APPLIED THERMAL ENGINEERING, 2010, 30 (14-15) : 2096 - 2102
  • [37] A comparison study on fin surfaces in finned-tube heat exchangers
    Sheu, Tony W. H.
    Tsai, S.F.
    International Journal of Numerical Methods for Heat and Fluid Flow, 1999, 9 (01): : 92 - 106
  • [38] Experimental study of the natural convection characteristics of finned-tube sodium-to-air heat exchanger
    Lee, Jewhan
    Min, Jaehong
    Yoon, Jung
    Kim, Hyungmo
    JOURNAL OF MECHANICAL SCIENCE AND TECHNOLOGY, 2024, 38 (04) : 2055 - 2062
  • [39] Experimental study on the effect of frost parameters on domestic refrigerator finned tube evaporator coils
    Ozkan, Derya Burcu
    Ozil, Eralp
    APPLIED THERMAL ENGINEERING, 2006, 26 (17-18) : 2490 - 2493
  • [40] A comparison study on fin surfaces in finned-tube heat exchangers
    Sheu, TWH
    Tsai, SF
    INTERNATIONAL JOURNAL OF NUMERICAL METHODS FOR HEAT & FLUID FLOW, 1999, 9 (01) : 92 - 106