Analysis of a sort of unusual mal-operation of transformer differential protection due to removal of external fault

被引:17
|
作者
Lin, Xiangning [1 ,2 ]
Weng, Hanli [1 ]
Liu, Pei [1 ]
Wang, Bin [1 ,2 ]
Bo, Zhiqian [1 ,3 ]
机构
[1] Huazhong Univ Sci & Technol, Elect Power Secur & High Efficiency Lab, Wuhan 430074, Peoples R China
[2] Three Gorges Univ, Coll Elect Engn & Informat Technol, Yichang 443002, Hubei, Peoples R China
[3] AREVA T&D Automat & Informat Syst, Stafford ST17 4LX, England
基金
中国国家自然科学基金;
关键词
transformer differential protection; removal of external fault; CT local transient saturation;
D O I
10.1109/TPWRD.2008.919250
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Several cases of mal-operation of transformer differential protection with second-harmonic blocking after clearance of external fault are reported. These mal-operations all occurred at the nonrestraint region of percentage restraint plane. The previous theory cannot be utilized directly to analyze this phenomenon. Therefore, a mathematical model for analyzing the transient course of external fault inception and removal, together with the CT model involving the magnetic hysteresis effect, is proposed in this paper. It is proved that the magnetic linkage of one CT core can be pushed into the region nearby the saturation point by the high fault current with aperiodic component. As soon as the external fault is removed, the magnetic linkage formed by the primary current with low amplitude is not high enough to pull the operating point of the magnetic linkage back to the linear region. This phenomenon is named as CT local transient saturation, which results in the big measuring angle error and relative smooth waveform. In this case, the transformer differential protection using second harmonic blocking inevitably mal-operates. This point of view is verified with the simulation tests.
引用
收藏
页码:1374 / 1379
页数:6
相关论文
共 47 条
  • [1] The association of a transformer differential protection mal-operation
    Shi, Jian-Zeng
    Liu, Jian-Min
    Liu, Chang-Li
    Gao, Yun-Fei
    Dianli Xitong Baohu yu Kongzhi/Power System Protection and Control, 2010, 38 (07): : 132 - 135
  • [2] Analysis and improvement on mal-operation of transformer backup protection
    Yao, Chuang
    Li, Yongli
    Zhang, Weizheng
    Li, Zhongqing
    Du, Dingxiang
    Zhou, Zexin
    Dianwang Jishu/Power System Technology, 2014, 38 (01): : 248 - 254
  • [3] Research on a Mal-operation Case of Differential Protection in UHV Transformer
    Zheng, Tao
    Chen, Peilu
    Lu, Ting
    2013 IEEE PES ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), 2013,
  • [4] Analysis of mal-operation of transformer's differential protection in a 110 kV substation
    Pan, Shu-Yan
    Huang, Biao
    Chen, Yong-Hua
    Li, Yong-Guo
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2005, 29 (19): : 87 - 89
  • [5] A novel explanation to the mal-operation of differential protection during the loaded transformer energization
    Electrical Engineering Department, Huazhong University of Science and Technology, Wuhan 430074, China
    Zhongguo Dianji Gongcheng Xuebao, 2006, 20 (27-32):
  • [6] Analysis on mal-operation of differential protection caused by sympathetic inrush
    State Key Lab. of Power Systems, Department of Electrical Engineering, Tsinghua University, Beijing 100084, China
    不详
    不详
    Dianli Xitong Zidonghue, 2007, 22 (36-40):
  • [7] New algorithm based on the mathematical morphology for avoiding mal-operation of transformer differential protection
    Zheng, Tao
    Liu, Wan-Shun
    Liu, Jian-Fei
    Xiao, Shi-Wu
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2005, 25 (20): : 6 - 11
  • [8] A New Algorithm Based on the Morphological Gradient for Avoiding Mal-operation of Transformer Differential Protection
    Gu, J.
    Zheng, T.
    Huang, S. F.
    IEEE POWER AND ENERGY SOCIETY GENERAL MEETING 2010, 2010,
  • [9] Mal-operation Reason Analysis and Solution for Differential Voltage Protection of Shunt Capacitors
    Lin, Guo-Song
    Li, Zhe
    Journal of Railway Engineering Society, 2018, 35 (11): : 77 - 81
  • [10] Mal-operation analysis on magnetic inrush current of power transformer
    Wang, Li-Da
    Duan, Zhou-Chao
    Dianli Xitong Baohu yu Kongzhi/Power System Protection and Control, 2010, 38 (10): : 138 - 140