Water saving in thermal power plant by use of membrane filter in cooling tower treatment

被引:3
|
作者
Dhokai, Chetan [1 ]
Palkar, Ritesh Ramesh [2 ]
Jain, Vicky [1 ]
机构
[1] Marwadi Univ, Dept Chem, Rajkot 360003, Gujarat, India
[2] Marwadi Univ, Dept Chem Engn, Rajkot 360003, Gujarat, India
关键词
water conservation; nano filtration; cooling tower; cost saving; power plant; ENERGY; DESALINATION; RO;
D O I
10.3934/environsci.2022020
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
A study was carried to investigate by placing a side stream filter in a cooling tower to observe the water conservation in the system. For any coal based power plant cycles of concentration plays important role for water conservation. The cycles of concentration in cooling tower was increased by installation of membrane system. The drain of the side stream filter was disposed to effluent treatment plant (ETP), while the filtered water will be recycled to the cooling tower inlet. The water parameter was measured by using various flow rates, pressure, and other factors. Significant water savings were demonstrated in the pilot. Maximum make-up water and outflow were both reduced by 14% and 48%, respectively. To save the most water, permeate recovery must be as high as possible. Water savings were minimal due to silica scaling on the membranes. Selected membranes are capable of lower total dissolved system (TDS) rejection than the 88% of total required membranes in the primary study, which might help to save water. The increased energy consumed by membrane treatment was compensated for by lower water outlays. To prevent scaling antiscalent chemical with chemical dosing system was installed along with membrane system.
引用
收藏
页码:282 / 292
页数:11
相关论文
共 50 条
  • [41] Study on the Technology of Raw Water Treatment for Power Plant Cooling System
    Shen, Liang
    Wang, Heli
    Qi, Jingxian
    Lian, Xinying
    Sun, Huichao
    CONFERENCE ON ENVIRONMENTAL POLLUTION AND PUBLIC HEALTH, VOL 1-2, 2010, : 1055 - 1058
  • [42] The influence of condenser cooling water temperature on the thermal efficiency of a nuclear power plant
    Attia, Sami I.
    ANNALS OF NUCLEAR ENERGY, 2015, 80 : 371 - 378
  • [43] The search for optimum condenser cooling water flow rate in a thermal power plant
    Anozie, A. N.
    Odejobi, O. J.
    APPLIED THERMAL ENGINEERING, 2011, 31 (17-18) : 4083 - 4090
  • [44] CONJUGATE MODEL OF THERMAL CYCLE AND COOLING WATER SYSTEM FOR SUPERCRITICAL POWER PLANT
    Wroblewski, Wlodzimierz
    Dykas, Slawomir
    Rulik, Sebastian
    RYNEK ENERGII, 2008, (06): : 54 - 60
  • [45] Structural Engineering Challenges in Structures for Cooling Water System in Thermal Power Plant
    Trivedi, Dipal P.
    Bagga, Raja I.
    Chokshi, Jignesh V.
    CHEMICAL, CIVIL AND MECHANICAL ENGINEERING TRACKS OF 3RD NIRMA UNIVERSITY INTERNATIONAL CONFERENCE ON ENGINEERING (NUICONE2012), 2013, 51 : 141 - 150
  • [46] Use of heat pumps in turbogenerator hydrogen cooling systems at thermal power plant
    Anikina, I. D.
    Sergeyev, V. V.
    Amosov, N. T.
    Luchko, M. G.
    INTERNATIONAL JOURNAL OF HYDROGEN ENERGY, 2017, 42 (01) : 636 - 642
  • [47] Use of Ultrasonics for Saving of Water in Cooling Towers.
    Bartzack, Harald
    Lepenies, Siegfried
    Energietechnik, 1974, 24 (06): : 236 - 238
  • [48] Reducing water consumption of an industrial plant cooling unit using hybrid cooling tower
    Rezaei, Ebrahim
    Shafiei, Sirous
    Abdollahnezhad, Aydin
    ENERGY CONVERSION AND MANAGEMENT, 2010, 51 (02) : 311 - 319
  • [49] STUDY OF PLUME DIFFUSION OF THE COOLING TOWER FOR GEOTHERMAL POWER PLANT.
    Matsumoto, Yoshinobu
    Suzuki, Kouhei
    Andou, Yasunori
    IHI Engineering Review (English Edition), 1982, 15 (02): : 39 - 44
  • [50] Method and Implementation of Energy-saving Control for Industrial Cooling Water Tower Pump
    Zhang, Lizhong
    Jia, Shuhong
    Zhao, Xiaojun
    Sun, Yan
    Shi, Guodong
    RENEWABLE AND SUSTAINABLE ENERGY II, PTS 1-4, 2012, 512-515 : 1163 - +