Experimental validation of the numerical model of air, heat and moisture flow in an indoor swimming pool

被引:32
|
作者
Ciuman, Piotr [1 ]
Lipska, Barbara [1 ]
机构
[1] Silesian Tech Univ, Dept Heating Ventilat & Dust Removal Technol, Konarskiego 20, PL-44100 Gliwice, Poland
关键词
Indoor swimming pool; Ventilation; Air flow variables; Measurement; CFD prediction; Experimental validation; EVAPORATION; PREDICTION; SIMULATION; OPENFOAM;
D O I
10.1016/j.buildenv.2018.09.009
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Indoor swimming pools are facilities in which a ventilation system has a vital impact on the proper operation of the building, as well as the users' comfort, operating costs and the safety of the structure. The major problem in ensuring appropriate thermal-moisture conditions is the removal of moisture that is mainly gained from the surface of the water in the pool's basin. The aim of this paper was to experimentally identify the physical phenomena occurring in the actual indoor swimming pool and to evaluate whether the numerical model of the facility, developed with the use of Ansys CFX 14.5 software, correctly mapped these phenomena and how it should be improved in this field. Results of the experimental research of the air variables, carried out in various periods of the year, were used to identify the changes in the thermal-moisture conditions and to prepare boundary conditions for the numerical calculations, as well as to validate these simulations experimentally. The numerical model was improved with the use of the authors' own method of modelling moisture emission from the surface of the water. It was based on the implementation of literature formulas for calculating the value of this parameter in the software. The validation encompassed the indoor airflow pattern and the distribution of the air flow variables above the surface of the water and around the pool's basin. The improved numerical model was able to reproduce the actual conditions in the indoor swimming pool with good concurrence of the experimental and predicted values.
引用
收藏
页码:1 / 13
页数:13
相关论文
共 50 条
  • [21] Experimental validation of coupled heat, air and moisture transfer modeling in multilayer building components
    Ferroukhi, M. Y.
    Abahri, K.
    Belarbi, R.
    Limam, K.
    Nouviaire, A.
    HEAT AND MASS TRANSFER, 2016, 52 (10) : 2257 - 2269
  • [22] Experimental validation of coupled heat, air and moisture transfer modeling in multilayer building components
    M. Y. Ferroukhi
    K. Abahri
    R. Belarbi
    K. Limam
    A. Nouviaire
    Heat and Mass Transfer, 2016, 52 : 2257 - 2269
  • [23] Effects of Ventilation and Air Cleaning on Indoor Air Quality of a Swimming Pool - Mass Balance Analysis Approach
    Lee, Chang-Seo
    Lakdawala, Ness
    Haghighat, Fariborz
    SEVENTH INTERNATIONAL COLD CLIMATE HVAC CONFERENCE, 2012, : 152 - 160
  • [24] Comprehensive assessment of the indoor air quality in a chlorinated Olympic-size swimming pool
    Felgueiras, Fatima
    Mourao, Zenaida
    Morais, Catarina
    Santos, Hugo
    Gabriel, Marta Fonseca
    Fernandes, Eduardo de Oliveira
    ENVIRONMENT INTERNATIONAL, 2020, 136
  • [25] Temperature control of a PCM integrated open-air swimming pool in cold season: a numerical and experimental study
    Li, Y.
    Huang, G.
    4TH ASIA CONFERENCE OF INTERNATIONAL BUILDING PERFORMANCE SIMULATION ASSOCIATION, 2019, 238
  • [26] Direct numerical simulation of indoor air flow
    Sun, Zai
    Huang, Zhen
    Wang, Jia-Song
    Shanghai Jiaotong Daxue Xuebao/Journal of Shanghai Jiaotong University, 2007, 41 (05): : 677 - 680
  • [27] AN EXPERIMENTAL STUDY TO DETERMINE THE PERFORMANCE AND POTENTIAL SAVING OF SWIMMING POOL AIR SOURCE HEAT PUMP WATER HEATER
    Tangwe, Stephen
    Simon, Michael
    Meyer, Edson
    PROCEEDINGS OF THE TWENTY FOURTH CONFERENCE ON THE DOMESTIC USE OF ENERGY, 2016,
  • [28] PRIMARY AMEBIC MENINGO-ENCEPHALITIS IN AN INDOOR HEAT-EXCHANGE SWIMMING POOL
    CURSONS, RTM
    BROWN, TJ
    KEYS, EA
    GORDON, EH
    LENG, RH
    HAVILL, JH
    HYNE, BEB
    NEW ZEALAND MEDICAL JOURNAL, 1979, 90 (646) : 330 - 331
  • [29] An Experimental Validation of a Turbulence Model for Air Flow in a Mining Chamber
    Branny, M.
    Karch, M.
    Wodziak, W.
    Jaszczur, M.
    Nowak, R.
    Szmyd, J. S.
    XXI FLUID MECHANICS CONFERENCE, 2014, 530
  • [30] Optimization of heat pump system in indoor swimming pool using particle swarm algorithm
    Lee, Wen-Shing
    Kung, Chung-Kuan
    APPLIED THERMAL ENGINEERING, 2008, 28 (13) : 1647 - 1653