Power-Based Concept for Current Injection by Inverter-Interfaced Distributed Generations during Transmission-Network Faults

被引:1
|
作者
Polajzer, Bostjan [1 ]
Grcar, Bojan [1 ]
Cernelic, Jernej [2 ]
Ritonja, Jozef [1 ]
机构
[1] Univ Maribor, Fac Elect Engn & Comp Sci, SI-2000 Maribor, Slovenia
[2] MAHLE Elect Drives Slovenija Doo, SI-5290 Sempeter Pri Gorici, Slovenia
来源
APPLIED SCIENCES-BASEL | 2021年 / 11卷 / 21期
关键词
distributed generation; fault current injection; voltage support; distance protection; VOLTAGE SUPPORT CONTROL; CONTROL STRATEGY; PROTECTION COORDINATION; DISTRIBUTION-SYSTEMS; OVERCURRENT RELAYS; CURRENT LIMITATION; SHORT-CIRCUIT; PV INVERTERS; RIDE;
D O I
10.3390/app112110437
中图分类号
O6 [化学];
学科分类号
0703 ;
摘要
This paper analyzes the influence of inverter-interfaced distributed generations' (IIDGs) response during transmission network faults. The simplest and safest solution is to switch IIDGs off during network faults without impacting the network voltages. A more elaborate and efficient concept, required by national grid codes, is based on controlling the IIDGs' currents, involving positive- and negative-sequence voltage measured at the connection point. In this way the magnitude and phase of the injected currents can be adjusted, although the generated power will depend on the actual line voltages at the connection point. Therefore, an improved concept is proposed to adjust IIDGs' fault current injection through the required active and reactive power, employing the same voltage characteristics. The proposed, i.e., power-based concept, is more definite than the current-based one, since the required power will always be generated. The discussed concepts for the fault current injection by IIDGs were tested in different 110-kV networks with loop and radial topologies, and for different short-circuit capabilities of the aggregated network supply. Based on extensive numerical calculations, the power-based concept during transmission networks faults generates more reactive power compared to the current-based concept. However, the voltage support by IIDGs during transmission networks faults, regardless of the concept being used, is influenced mainly by the short-circuit capability of the aggregated network supply. As regards distance protection operation, it is influenced additionally by the network topology, i.e., in radial network topology, the remote relay's operation can be delayed due to a largely seen impedance.
引用
收藏
页数:15
相关论文
共 25 条
  • [21] Zero-sequence current injection based power flow control strategy for grid inverter interfaced renewable energy systems
    Aygen, M. Selim
    Inci, Mustafa
    ENERGY SOURCES PART A-RECOVERY UTILIZATION AND ENVIRONMENTAL EFFECTS, 2022, 44 (03) : 7782 - 7803
  • [22] Continuation Power Flow for Distribution Network Considering Current Limiting Status of Inverter Based Distributed Generation
    Yang, Shan
    Tong, Xiangqian
    2016 CHINA INTERNATIONAL CONFERENCE ON ELECTRICITY DISTRIBUTION (CICED), 2016,
  • [23] Supporting effect of power injection from distributed generations on voltage at grid-connected point during symmetrical short-circuit faults in power system
    Jiang, Ling
    Liu, Bangyin
    Duan, Shanxu
    Dianwang Jishu/Power System Technology, 2014, 38 (03): : 669 - 674
  • [24] Peak Current Limitation for Grid Side Inverter by Limited Active Power in PMSG-Based Wind Turbines During Different Grid Faults
    Nasiri, Mojtaba
    Mohammadi, Reza
    IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, 2017, 8 (01) : 3 - 12
  • [25] PI-based controller for low-power distributed inverters to maximise reactive current injection while avoiding over voltage during voltage sags
    Miret, Jaume
    Garnica, Miguel A.
    Castilla, Miguel
    Garcia de Vicuna, Jose Luis
    Camacho, Antonio
    IET POWER ELECTRONICS, 2019, 12 (01) : 83 - 91