Comprehensive coupling model of counter-flow wet cooling tower and its thermal performance analysis

被引:18
|
作者
Yu, J. H. [1 ]
Qu, Z. G. [1 ]
Zhang, J. F. [1 ]
Hu, S. J. [2 ]
Guan, J. [3 ]
机构
[1] Xi An Jiao Tong Univ, Sch Energy & Power Engn, Key Lab Thermal Fluid Sci & Engn, MOE, Xian 710049, Peoples R China
[2] Xian TPRI Energy Conservat Technol Co Ltd, Xian 710054, Peoples R China
[3] China Special Equipment Inspect & Res Inst, Beijing 100029, Peoples R China
关键词
Counter-flow wet cooling towers; Coupling model; Heat and mass transfer; Parametric study; DESIGN; MERKEL;
D O I
10.1016/j.energy.2021.121726
中图分类号
O414.1 [热力学];
学科分类号
摘要
Counter-flow wet cooling towers are equipment for removing heat from water to environment. The traditional model for their thermal performance mainly focuses on the heat exchange in packing. The coupling among spray zone, rain zone, and packing are not considered. In this study, a coupling model consisting of mathematical descriptions of the spray zone, rain zone, and packing is proposed. The thermal performance is investigated based on the interaction of three zones. An actual cooling tower test report is used to validate the coupling model. Subsequently, the efficiency and exit water temperature of the cooling tower is analyzed under various conditions. The results indicate that the relative error is 5.68 % when the coupling relation is neglected. The relative error is reduced to 3.25 % when the spray zone and rain zone are coupled with packing. The cooling tower efficiency and exit water temperature increase with increasing air humidity, while the smaller droplets diameter and higher air-to-water mass flow rate ratio cause lower exit water temperature and higher cooling tower efficiency. Besides, the droplets velocity has little influence on these. The results of this study provide theoretical foundations for accurate performance prediction and guide the direction for cooling towers optimization. (c) 2021 Elsevier Ltd. All rights reserved.
引用
收藏
页数:14
相关论文
共 50 条
  • [1] Numerical analysis of a counter-flow wet cooling tower and its plume
    Zargar, A.
    Kodkani, A.
    Peris, A.
    Clare, E.
    Cook, J.
    Karupothula, P.
    Vickers, B.
    Flynn, M.R.
    Secanell, M.
    [J]. International Journal of Thermofluids, 2022, 14
  • [2] THEORETICAL AND EXPERIMENTAL STUDY OF THERMAL PERFORMANCE WITHIN A COUNTER-FLOW WET COOLING TOWER
    Meneceur, N.
    Boulahrouz, S.
    Khounfais, K.
    Boukhari, A.
    [J]. JOURNAL OF ENGINEERING SCIENCE AND TECHNOLOGY, 2018, 13 (11) : 3691 - 3709
  • [3] HEAT TRANSFER AND PSYCHOMETRIC ANALYSIS OF A COUNTER-FLOW WET COOLING TOWER
    Patra, Alok
    Misra, Souren
    Panda, Santosh Kumar
    [J]. Heat Transfer Research, 2023, 54 (12): : 81 - 93
  • [4] HEAT TRANSFER AND PSYCHOMETRIC ANALYSIS OF A COUNTER-FLOW WET COOLING TOWER
    Patra, Alok
    Misra, Souren
    Panda, Santosh Kumar
    [J]. HEAT TRANSFER RESEARCH, 2023, 54 (12) : 81 - 93
  • [5] PERFORMANCE ANALYSIS OF COUNTER FLOW WET COOLING TOWER
    Ramkumar, R.
    Ragupathy, A.
    [J]. INTERNATIONAL JOURNAL OF AIR-CONDITIONING AND REFRIGERATION, 2011, 19 (02) : 141 - 148
  • [6] AN ANALYTICAL MODEL ON THERMAL PERFORMANCE EVALUATION OF COUNTER FLOW WET COOLING TOWER
    Wang, Qian
    Wang, Pei-Hong
    Su, Zhi-Gang
    [J]. THERMAL SCIENCE, 2017, 21 (06): : 2491 - 2501
  • [7] COUPLING MODEL AND SOLVING APPROACH FOR PERFORMANCE EVALUATION OF NATURAL DRAFT COUNTER-FLOW WET COOLING TOWERS
    Wang, Wei
    Zeng, Deliang
    Hu, Yong
    Liu, Jizhen
    Niu, Yuguang
    [J]. THERMAL SCIENCE, 2016, 20 (01): : 291 - 301
  • [8] DYNAMIC MODELING OF MECHANICAL DRAFT COUNTER-FLOW WET COOLING TOWER WITH MODELICA
    Li, Xiao
    Li, Yaoyu
    Seem, John E.
    [J]. PROCEEDINGS OF THE ASME DYNAMIC SYSTEMS AND CONTROL CONFERENCE 2010, VOL 2, 2010, : 687 - 694
  • [9] PERFORMANCE EVALUATION OF COUNTER-FLOW WET COOLING TOWERS USING EXERGETIC ANALYSIS
    Ataei, A.
    Panjeshahi, M. H.
    Gharaie, M.
    [J]. TRANSACTIONS OF THE CANADIAN SOCIETY FOR MECHANICAL ENGINEERING, 2008, 32 (3-4) : 499 - 511
  • [10] Counter-Flow Cooling Tower Test Cell
    Dvorak, Lukas
    Nozicka, Jiri
    [J]. EFM13 - EXPERIMENTAL FLUID MECHANICS 2013, 2014, 67