Comprehensive Assessment of Lightning Protection Schemes for 10 kV Overhead Distribution Lines

被引:20
|
作者
Cao, Jinxin [1 ]
Du, Yaping [1 ]
Ding, Yuxuan [1 ]
Qi, Ruihan [2 ]
Li, Binghao [1 ]
Chen, Mingli [1 ]
Li, Zhe [3 ]
机构
[1] Hong Kong Polytech Univ, Dept Bldg Serv Engn, Hung Hom, Hong Kong, Peoples R China
[2] China Southern Power Grid, State Key Lab HVDC Transmiss Technol, Guangzhou 510000, Peoples R China
[3] China Southern Power Grid, Shenzhen Power Supply Bur, Shenzhen 10000, Peoples R China
关键词
Lightning; Wires; Surges; Arresters; Lightning protection; Monte Carlo methods; Flashover; overhead line; Monte Carlo simulation; medium voltage; economic analysis; POWER DISTRIBUTION LINES; INDUCED VOLTAGES; INDUCED OVERVOLTAGES; SHIELD WIRES; PERFORMANCE; ARRESTERS; SYSTEMS;
D O I
10.1109/TPWRD.2021.3110248
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents an assessment of lightning protection schemes for overhead lines from two aspects: protection performance and economic cost. Considering the random nature of lightning, the Monte-Carlo method with a heuristic technique is applied in the assessment. The one-dimensional finite-difference time-domain method is adopted to evaluate lightning overvoltages on insulators and lightning currents in surge arresters for failure assessment. The failure rate of an overhead line is addressed under both direct lightning and indirect lightning. A reduced set of design parameters are identified. It is found that the line insulation itself with a critical flashover overvoltage of less than 200 kV is not sufficient for lightning protection, especially against direct strokes. With other protection options, however, increasing the insulation level can greatly improve the protection performance. Installing surge arresters on every pole results in the best protection performance, but could be extremely expensive due to the replacement of failed surge arresters. The shielding wire provides moderate protection performance with a relatively low cost. The combination of the shielding wire and surge arresters provides much better performance under a wide range of soil conductivity with a moderate cost. It is worth mentioning that adopting high insulation strength for overhead lines in the new-line design could lead to significant cost savings for lightning protection. Guidelines for selecting design parameter values and protection schemes are provided, as well as a procedure for performance-cost evaluation.
引用
收藏
页码:2326 / 2336
页数:11
相关论文
共 50 条
  • [21] Lightning protection of overhead distribution lines installed on high resistivity soil
    Paulino, Jose Osvaldo S.
    Barbosa, Celio F.
    Lopes, Ivan J. S.
    Boaventura, Wallace C.
    Cardoso, Eduardo N.
    Guimaraes, Maurissone F.
    ELECTRIC POWER SYSTEMS RESEARCH, 2022, 209
  • [22] Observation on improved 20 kV's overhead distribution lines against lightning
    Zoro, R.
    Mefiardhi, R.
    Aritonang, R. R.
    Suhana, H.
    ICPASM 2005: PROCEEDINGS OF THE 8TH INTERNATIONAL CONFERENCE ON PROPERTIES AND APPLICATIONS OF DIELECTRIC MATERIALS, VOLS 1 AND 2, 2006, : 979 - +
  • [23] The Lightning Protection Performance of the Composite Material Cross-Arm in 10 kV Distribution Lines
    Cai, Wei
    Deng, Heming
    Zhang, Rui
    Zhang, Zichao
    Zeng, Qiang
    2014 INTERNATIONAL CONFERENCE ON LIGHTNING PROTECTION (ICLP), 2014, : 242 - 245
  • [24] A Comprehensive Analysis on the Influence of the Adopted Cumulative Peak Current Distribution in the Assessment of Overhead Lines Lightning Performance
    Conceicao, Daiane
    Alipio, Rafael
    Lopes, Ivan J. S.
    Chisholm, William
    ENERGIES, 2023, 16 (15)
  • [25] Observation of induced voltage on 10 kV overhead distribution lines with and without shield wire by rocket triggered lightning
    Cai, Li
    Xu, Changfeng
    Cao, Jinxin
    Zhou, Mi
    Chu, Wangxiang
    Wang, Jianguo
    Fan, Yadong
    ELECTRIC POWER SYSTEMS RESEARCH, 2023, 224
  • [26] Design Consideration of the Shielding Wire in 10 kV Overhead Distribution Lines Against Lightning-Induced Overvoltage
    Cao, Jinxin
    Ding, Yuxuan
    Du, Yaping
    Chen, Mingli
    Qi, Ruihan
    IEEE TRANSACTIONS ON POWER DELIVERY, 2021, 36 (05) : 3005 - 3013
  • [27] Effect of Earth Conductivity and Length of Line on Lightning Induced Voltage of 10kV Overhead Distribution Lines
    Yu J.
    Fan Y.
    Wang J.
    Cai L.
    Zhou M.
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2020, 40 (02): : 672 - 683
  • [28] Assessment of the Lightning Performance of overhead distribution lines based on Lightning Location Systems data
    Nicora, Martino
    Mestriner, Daniele
    Brignone, Massimo
    Bernardi, Marina
    Procopio, Renato
    Fiori, Elisabetta
    Delfino, Federico
    Piantini, Alexandre
    Rachidi, Farhad
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2022, 142
  • [29] Application possibilities of special lightning protection systems of overhead distribution and transmission lines
    Banjanin, Mladen S.
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2018, 100 : 482 - 488
  • [30] Designing Method of Insulation Strength and Lightning Protection for Overhead Power Distribution Lines
    Yokoyama, Shigeru
    Sato, Tomoyuki
    2018 34TH INTERNATIONAL CONFERENCE ON LIGHTNING PROTECTION (ICLP 2018), 2018,