Waveform Difference Based Adaptive Restart Strategy for LCC-MMC Hybrid DC System

被引:0
|
作者
Liang, Chenguang [1 ]
Zhang, Dahai [1 ]
Li, Meng [1 ]
Nie, Ming [1 ]
Mirsaeidi, Sohrab [1 ]
Xu, Yin [1 ]
He, Jinghan [1 ]
机构
[1] Beijing Jiaotong Univ, Sch Elect Engn, Beijing 100044, Peoples R China
基金
中国国家自然科学基金;
关键词
Circuit faults; Firing; HVDC transmission; Valves; Fault diagnosis; Rectifiers; Inverters; Hybrid HVDC system; travelling wave; fault property; overhead line; Pearson correlation coefficient; LINE FAULT LOCATION; RECLOSING SCHEME;
D O I
10.1109/TPWRD.2022.3148179
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Hybrid high voltage direct current systems utilized for bulk-power transmission have recently attracted more attention. The overhead lines (OHLs) are mainly used for the implementation of such systems due to their outstanding economic advantages. However, OHLs are vulnerable to temporary faults, jeopardizing the safe and reliable operation of the network. The resiliency to the line faults is of considerable significance to the power transmission. This paper proposes a fault property identification strategy based on the Pearson correlation coefficient for the LCC-MMC hybrid HVDC system which can differentiate temporary and permanent faults. To achieve this, a voltage signal is injected into the faulty line by decreasing the firing angles of the LCC-based rectifier. Based on the established OHLs model and the injected signal, an estimated backward travelling wave can be accurately calculated. The fault property is identified by comparing the wave difference of the real backward travelling wave and the estimated backward travelling wave. The proposed strategy has a high accuracy since all influencing factors including the fault resistance, fault distance, and line parameters have been taken into account. Finally, to verify the efficacy of the proposed algorithm, several simulations have been performed using PSCAD/EMTDC. The simulation results show that the proposed algorithm can effectively distinguish the fault property.
引用
收藏
页码:4237 / 4247
页数:11
相关论文
共 50 条
  • [21] Research on a Fault Location Method for a Pole-to-Pole Short-Circuit Fault in an LCC-MMC Hybrid DC Transmission System
    Xing, Chao
    Li, Shengnan
    Xi, Xinze
    [J]. IEEE ACCESS, 2020, 8 : 165683 - 165692
  • [22] Fault response comparison of LCC-MMC hybrid topologies and conventional HVDC topology
    Lou, Boliang
    Zhou, Hua
    Xu, Zheng
    Wang, Shijia
    Xu, Yuzhe
    [J]. JOURNAL OF ENGINEERING-JOE, 2019, (16): : 2068 - 2073
  • [23] A Three-Terminal Hybrid HVDC System Based on LCC and Hybrid MMC with DC Fault Clearance Capability
    Han, Wei
    Yang, Ruizhang
    Xiang, Wang
    Liu, Chao
    Ma, Weidong
    Wen, Jinyu
    [J]. 2019 10TH INTERNATIONAL CONFERENCE ON POWER ELECTRONICS AND ECCE ASIA (ICPE 2019 - ECCE ASIA), 2019,
  • [24] Optimization and Configuration of Control Parameters to Enhance Small-signal Stability of Hybrid LCC-MMC HVDC System
    Chunyi Guo
    Peng Cui
    Chengyong Zhao
    [J]. Journal of Modern Power Systems and Clean Energy, 2022, (01) : 213 - 221
  • [25] Optimization and Configuration of Control Parameters to Enhance Small-signal Stability of Hybrid LCC-MMC HVDC System
    Guo, Chunyi
    Cui, Peng
    Zhao, Chengyong
    [J]. JOURNAL OF MODERN POWER SYSTEMS AND CLEAN ENERGY, 2022, 10 (01) : 213 - 221
  • [26] Application of MMC with Embedded Energy Storage for Overvoltage Suppression and Fault Ride-through Improvement in Series LCC-MMC Hybrid HVDC System
    Li, Xiaodong
    Xu, Zheng
    Zhang, Zheren
    [J]. JOURNAL OF MODERN POWER SYSTEMS AND CLEAN ENERGY, 2023, 11 (03) : 1001 - 1013
  • [27] Application of MMC with Embedded Energy Storage for Overvoltage Suppression and Fault Ride-through Improvement in Series LCC-MMC Hybrid HVDC System
    Xiaodong Li
    Zheng Xu
    Zheren Zhang
    [J]. Journal of Modern Power Systems and Clean Energy, 2023, 11 (03) : 1001 - 1013
  • [28] Fault ride-through control for the sending-end AC system based on reactive power auxiliary in LCC-MMC hybrid HVDC system
    Hao, Liangliang
    Liu, Chang
    Zhan, Qingqing
    Chen, Zhengguang
    Wang, Xingguo
    [J]. ENERGY REPORTS, 2021, 7 : 118 - 133
  • [29] A Novel Protection Scheme for LCC-MMC Hybrid Multi-terminal HVDC Transmission Lines
    Zhou, Yi
    Cao, Junzheng
    Zhao, Jing
    Li, Yang
    Zhang, Chenhao
    Song, Guobing
    [J]. 2022 4TH INTERNATIONAL CONFERENCE ON SMART POWER & INTERNET ENERGY SYSTEMS, SPIES, 2022, : 638 - 642
  • [30] Traveling Wave Propagation Characteristic-Based LCC-MMC Hybrid HVDC Transmission Line Fault Location Method
    Wang, Jian
    Zhang, Yanxia
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2022, 37 (01) : 208 - 218