Experimental Investigation of the Condensation Heat Transfer Coefficient of R134a inside Horizontal Smooth and Micro-Fin Tubes

被引:4
|
作者
Li, Qingpu [1 ]
Tao, Leren [1 ]
Li, Lei [1 ]
Hu, Yongpan [1 ]
Wu, Shengli [1 ]
机构
[1] Univ Shanghai Sci & Technol, Inst Refrigerat & Cryogen, Shanghai 200093, Peoples R China
关键词
condensation; heat transfer coefficient; correlation; dimensionless parameter; turbulence effect; PRESSURE-DROP; 2-PHASE FLOW; TRANSFER MODEL; REFRIGERANTS; HERRINGBONE; PATTERN; EVAPORATION; PREDICTION; EXCHANGER; REGIMES;
D O I
10.3390/en10091280
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The condensation heat transfer coefficient of R134a was experimentally studied inside two smooth and four micro-fin tubes. The working conditions and structural parameters of the test tubes were selected as the influencing factors, and the experiment was conducted under mass velocities of 400-1100 kg.m 2.s(-1), condensation temperatures of 35-45 degrees C and water-testing Reynolds numbers of 8000-22,000, with an inlet superheat of 1-2 degrees C and outlet subcooling of 1-2 degrees C at the test section for the refrigerant. Experimental results indicate that the heat transfer coefficient increases with increasing mass velocity and decreasing condensation temperature and water-testing Reynolds number. The heat transfer coefficient of the micro-fin tube with a helix angle of 28 degrees is the highest and that of smooth tube is the lowest for test tubes with the same inner diameter. Tube diameter has a small influence on the heat transfer coefficient for the smooth tubes while the heat transfer coefficient increases with decreasing tube diameter for the micro-fin tubes. The heat transfer coefficient inside the test tube was compared with some well-known existing correlations, and results show that correlations by Cavallini et al., Thome et al., Shah and Akers et al. can estimate the experimental data with mean absolute deviation of less than 30%, and correlations of Dobson and Chato et al. and Jung et al. cannot be used to capture the heat transfer coefficient with mean absolute deviations of 140.18% and 146.23%, respectively. While the Miyara et al. correlation overestimates the heat transfer coefficient, correlations of Cavallini et al., Koyama et al. and Oliver et al. all underestimate the experimental data for the micro-fin tube. Their deviations are from 25 to 55% for micro-fin tubes 3 and 4, while their deviations keep to within 30% for micro-fin tubes 5 and 6. Finally, to improve the correlation prediction accuracy, a dimensionless parameter was introduced to the correlations of Dobson and Chato et al. and Jung et al., and correlations of Cavallini et al., Koyama et al. and Oliver et al. were modified by enhancing the turbulence effect. The prediction accuracy of all modified correlations can be controlled to within 30%.
引用
收藏
页数:18
相关论文
共 50 条
  • [21] Evaluation of existing condensation heat transfer models in horizontal micro-fin tubes
    Chamra, LM
    Tan, MO
    Kung, CC
    [J]. EXPERIMENTAL THERMAL AND FLUID SCIENCE, 2004, 28 (06) : 617 - 628
  • [22] Evaporation heat transfer enhancement of R-134a flowing inside smooth and micro-fin tubes using the electrohydrodynamic technique
    Posew, Kittiporn
    Laohalertdecha, Suriyan
    Wongwises, Somchai
    [J]. ENERGY CONVERSION AND MANAGEMENT, 2009, 50 (07) : 1851 - 1861
  • [23] Heat transfer performance during condensation inside spiralled micro-fin tubes
    Bukasa, JPM
    Liebenberg, L
    Meyer, JP
    [J]. JOURNAL OF HEAT TRANSFER-TRANSACTIONS OF THE ASME, 2004, 126 (03): : 321 - 328
  • [24] Two phase heat transfer and flow regimes of R-134a and R-410A during condensation in horizontal micro-fin tubes
    Kukreja, Rajeev
    Jain, Sanjeev
    Aggarwal, Radhey Sham
    [J]. INTERNATIONAL JOURNAL OF HEAT AND TECHNOLOGY, 2018, 36 (04) : 1463 - 1469
  • [25] Condensation heat transfer and pressure drop of R134a inside microfin tubes: effect of fin height and fin angle
    Al-Dadah, R. K.
    Naser, A. D.
    [J]. PROCEEDINGS OF THE INSTITUTION OF MECHANICAL ENGINEERS PART C-JOURNAL OF MECHANICAL ENGINEERING SCIENCE, 2007, 221 (01) : 43 - 54
  • [26] Condensation heat transfer on single horizontal smooth and finned tubes and tube bundles for R134a and propane
    Gebauer, Thomas
    Al-Badri, Alaa R.
    Gotterbarm, Achim
    El Hajal, Jean
    Leipertz, Alfred
    Froeba, Andreas Paul
    [J]. INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2013, 56 (1-2) : 516 - 524
  • [27] Flow condensation heat transfer of propane refrigerant inside a horizontal micro-fin tube
    Quang Vu Pham
    Jong-Taek Oh
    [J]. International Journal of Air-Conditioning and Refrigeration, 30
  • [28] Flow condensation heat transfer of propane refrigerant inside a horizontal micro-fin tube
    Quang Vu Pham
    Oh, Jong-Taek
    [J]. INTERNATIONAL JOURNAL OF AIR-CONDITIONING AND REFRIGERATION, 2022, 30 (01)
  • [29] Experimental investigation on characteristics of R290 boiling heat transfer in horizontal micro-fin tubes with small diameter
    Wang, Lele
    Dai, Yuande
    Tian, Siyao
    Lin, Qinhan
    [J]. Huagong Xuebao/CIESC Journal, 2020, 71 (03): : 1026 - 1034
  • [30] Condensation heat transfer characteristics of R134A on smooth orfinned horizontal tube
    Fatouh, M.