Effects of Thermally Induced Bubbles on the Discharge Characteristics of Oil-Impregnated Pressboard

被引:3
|
作者
Zhang, Rui [1 ]
Zhang, Qiaogen [1 ]
Guo, Chong [1 ]
Zhang, Zhetao [1 ]
Wu, Zhicheng [1 ]
Wen, Tao [2 ]
机构
[1] Xi An Jiao Tong Univ, State Key Lab Elect Insulat & PowerEquipment, Xian 710049, Peoples R China
[2] Hefei Univ Technol, Sch Elect & Automat Engn, Hefei 230009, Peoples R China
关键词
Partial discharges; Moisture; Insulation; Heating systems; Temperature; Discharges (electric); Temperature measurement; Deterioration mechanisms; microcavities; oil-impregnated pressboard (OIPB); partial discharge (PD); thermally induced bubbles; PAPER; MECHANISM; CELLULOSE; BREAKDOWN;
D O I
10.1109/TDEI.2022.3165737
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Under temperature and moisture combined, bubbles will be formed in oil-impregnated paper/pressboard (OIP/OIPB). Although many studies have been done to understand the thermo-induced bubble phenomenon in OIPB, the formation mechanism is not, let alone its effect on discharge characteristics and insulation performance of OIPB. In this article, the phenomena and mechanisms of thermally induced bubbles, their effects and mechanisms on the partial discharge (PD), and breakdown characteristics of OIPB are investigated. The results show that the bubble inception temperature (BIT) decreases significantly with the increase of the moisture of OIPB. There is a growth process of bubbles from small to large, and the heating temperature and moisture content of OIPB affect the gas component inside the bubble. Thermal bubbles significantly reduce the PD inception voltage (PDIV) and breakdown voltage (BV), and the PD evolution and dissolved gas components in the oil show significant differences in the presence/absence of bubbles. Interestingly, PDIV and BV start to decrease in a temperature interval before BIT, and we infer that many microbubbles and gaseous channels exist inside OIPB before observable bubbles are formed on the surface. Considering the fibrous porous structure of OIPB and combining it with the bubble nucleation theory, we propose a new model for interpreting bubble formation and insulation degradation. The model suggests that bubbles (vapors) form first in microcavities and holes inside the OIPB and then spill over to the surface to form observable bubbles. The microcavities and pores in the OIPB are filled with gas (vapor) as the main cause of PD inception and insulation degradation. This study contributes to understanding the mechanisms of bubble formation in oil-paper insulation as well as provides a reference for risk assessment during overload operation and diagnosis of bubble-induced related faults of transformers.
引用
收藏
页码:1191 / 1199
页数:9
相关论文
共 50 条
  • [41] Influence of Board Density on the Conductivity of Oil-impregnated Pressboard for HVDC Insulation Systems
    Schober, F.
    Kuechler, A.
    Exner, W.
    Krause, Ch.
    Berger, F.
    2015 IEEE ELECTRICAL INSULATION CONFERENCE (EIC), 2015, : 61 - 64
  • [42] Space charge dynamics in oil-impregnated pressboard under AC electric field
    Hao, Miao
    Hao, Jiao
    Fu, Jin
    Wang, Qian
    Tang, Chao
    Chen, George
    2015 IEEE CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA (CEIDP), 2015, : 118 - 121
  • [43] Ultrasonic propagation characteristics of partial discharge in oil-impregnated paper traction transformer
    Mu, Guowei
    Dai, Quanmin
    Chai, Shuying
    Yang, Peng
    AIP ADVANCES, 2024, 14 (03)
  • [44] Effect of Superimposed Impulses on AC Partial Discharge Characteristics of Oil-Impregnated Paper
    Nikjoo, Roya
    Taylor, Nathaniel
    Edin, Hans
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2016, 23 (06) : 3602 - 3611
  • [45] Space Charge Behaviour in Thick Oil-Impregnated Pressboard under HVDC Stresses
    Hao, Miao
    Zhou, Yuan
    Chen, George
    Wilson, Gordon
    Jarman, Paul
    PROCEEDINGS OF THE 2013 IEEE INTERNATIONAL CONFERENCE ON SOLID DIELECTRICS (ICSD 2013), VOLS 1 AND 2, 2013, : 397 - 400
  • [46] Effect of Voltage Reversal on Space Charge in Oil and Oil-impregnated Pressboard under Temperature Gradient
    Huang, Bo
    Hao, Miao
    Xu, Zhiqiang
    Chen, George
    Tang, Chao
    2018 12TH INTERNATIONAL CONFERENCE ON THE PROPERTIES AND APPLICATIONS OF DIELECTRIC MATERIALS (ICPADM 2018), 2018, : 98 - 101
  • [47] Phenomenon analysis and state classification of surface discharge on oil-impregnated pressboard under AC-DC combined voltage
    Li, Xudong
    Huang, Zhengyong
    Li, Jian
    Jiang, Tianyan
    Mehmood, Muhammad Ali
    Hou, Shubin
    AIP ADVANCES, 2018, 8 (10)
  • [48] Investigation of partial discharge properties in oil-impregnated insulation
    Ariastina, W. G.
    Khawaja, R. H.
    Blackburn, T. R.
    ICPASM 2005: PROCEEDINGS OF THE 8TH INTERNATIONAL CONFERENCE ON PROPERTIES AND APPLICATIONS OF DIELECTRIC MATERIALS, VOLS 1 AND 2, 2006, : 714 - +
  • [49] Characteristics of oil-impregnated polymer and its applications
    Takajyo, T
    JOURNAL OF JAPANESE SOCIETY OF TRIBOLOGISTS, 2000, 45 (01) : 31 - 35
  • [50] Partial Discharge-induced Degradation Characteristics of Oil-impregnated Insulating Material Used in Oil-immersed Power Transformers
    Okabe, Shigemitsu
    Ueta, Genyo
    Wada, Haruhisa
    Okubo, Hitoshi
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2010, 17 (04) : 1225 - 1233