Enhancement of Thermo-Flow Performances by Windbreakers for Two-Tower Indirect Dry Cooling System

被引:8
|
作者
Yan, Jingbo [1 ]
Wang, Weijia [1 ]
Chen, Lei [1 ]
Yang, Lijun [1 ]
Du, Xiaoze [1 ]
机构
[1] North China Elect Power Univ, Sch Energy Power & Mech Engn, Beijing 102206, Peoples R China
关键词
indirect dry cooling system; twin towers; windbreakers; wind directions; flow and heat transfer performances; WIND; TOWER; EFFICIENCY;
D O I
10.1007/s11630-020-1294-2
中图分类号
O414.1 [热力学];
学科分类号
摘要
The winds will greatly weaken the cooling performance of indirect dry cooling system with twin towers. The exterior windbreakers are recommended to restrain the wind adverse effects in this paper. The macro heat exchanger model was adopted to simulate the heat exchange between circulating water and ambient air. The performances of natural draft dry cooling system (NDDCS) with and without exterior windbreakers were numerically studied. The pressure, velocity and temperature distribution of cooling air in wind angles of 0 degrees, 45 degrees and 90 degrees was obtained and presented. The results show that in all wind directions, the performances for lateral sector of towers with windbreakers are significantly improved, but the low-pressure zone appears unexpectedly for the rear sectors, which reduces the air flow rate. The cooling performances of the twin towers with or without windbreakers decrease at first but then recover with the wind velocity increasing. Besides, the optimal flow and heat transfer performances appear in the wind angle of 0 degrees. The cooling performances can be significantly improved in all three wind directions due to windbreaker configuration.
引用
收藏
页码:676 / 686
页数:11
相关论文
共 31 条
  • [21] A performance enhancement of a natural draft dry cooling tower in crosswind via inlet flow field reconstruction
    Wang, Weiliang
    Lyu, Junfu
    Zhang, Hai
    Liu, Qing
    Yue, Guangxi
    Ni, Weidou
    ENERGY AND BUILDINGS, 2018, 164 : 121 - 130
  • [22] Spray cooling system design and optimization for cooling performance enhancement of natural draft dry cooling tower in concentrated solar power plants
    Sun, Yubiao
    Guan, Zhigiang
    Gurgenci, Hal
    Wang, Jianyong
    Dong, Peixin
    Hooman, Kamel
    ENERGY, 2019, 168 : 273 - 284
  • [23] Numerical study identifies the interaction between two adjacent dry cooling towers on fluid flow and heat transfer performances of the radiators at different points of each tower
    Ma, Huan
    Cai, Liang
    Si, Fengqi
    INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2023, 191
  • [24] Numerical study on the effects of layout compactness of the annular-aligned moist media on thermo-hydraulic performance of an indirect dry cooling tower
    Ma, Huan
    Cai, Liang
    Si, Fengqi
    APPLIED THERMAL ENGINEERING, 2022, 213
  • [25] FLOW AND HEAT TRANSFER CHARACTERISTICS OF SOLAR-ENHANCED INDIRECT DRY COOLING TOWER AND ITS MECHANISMS INFLUENCIED BY ENVIRONMENTAL CROSSWIND
    Zhang L.
    Ma H.
    Si F.
    Taiyangneng Xuebao/Acta Energiae Solaris Sinica, 2023, 44 (10): : 198 - 208
  • [26] Study on Gas-Solid Two-Phase Flow Characteristics of One-Furnace with Two-Tower Semi-Dry Desulfurization in Circulating Fluidized Bed Boiler
    Wang, Xueshen
    Gan, Zheng
    Xin, Shengwei
    Yang, Chunzhen
    ENERGIES, 2023, 16 (04)
  • [27] Tower Configuration Impacts on the Thermal and Flow Performance of Steel-Truss Natural Draft Dry Cooling System
    Guo, Huiqian
    Yang, Yue
    Cheng, Tongrui
    Zhou, Hanyu
    Wang, Weijia
    Du, Xiaoze
    ENERGIES, 2021, 14 (07)
  • [28] Cooling water mass flow optimization for indirect dry cooling system of thermal power unit under variable output load
    Wu, Tao
    Wei, Huimin
    Ge, Zhihua
    Yang, Lijun
    Du, Xiaoze
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2019, 133 : 1 - 10
  • [29] Flow and heat transfer characteristics of indirect dry cooling system with horizontal heat exchanger A-frames at ambient winds
    Wu, X. P.
    Yang, L. J.
    Du, X. Z.
    Yang, Y. P.
    INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2014, 79 : 161 - 175
  • [30] Enhancement in thermodynamic cycle condensation of a coal-fired power plant by integrating a PCM heat storage tank into the indirect dry cooling system
    Wang, Baigong
    Ma, Huan
    Si, Fengqi
    MECHANICAL ENGINEERING JOURNAL, 2024, 11 (02):