Assessment of Overvoltage and Insulation Coordination in Mixed HVDC Transmission Lines Exposed to Lightning Strikes

被引:8
|
作者
Asif, Mansoor [1 ]
Lee, Ho-Yun [1 ]
Park, Kyu-Hoon [1 ]
Shakeel, Ayesha [1 ]
Lee, Bang-Wook [1 ]
机构
[1] Hanyang Univ, Dept Elect Engn, Hanyangdaehak Ro 55, Ansan 15588, South Korea
关键词
cable overvoltage; DC transmission; dielectric breakdown; electromagnetic transient simulation; high voltage; insulation coordination; negative lightning strikes; MODELS;
D O I
10.3390/en12214217
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Many geographical constraints and aesthetic concerns necessitate the partial use of cable sections in the High Voltage DC (HVDC) transmission line, resulting in a mixed transmission line. The overhead sections of mixed lines are exposed to lightning strikes. The lightning strikes can not only result in flashover of overhead line (OHL) insulators but can enter the cable and permanently damage its insulation if adequate insulation coordination measures are not taken. In this work, we have analyzed the factors that affect the level of overvoltage inside the cable by simulating a fast front model in PSCAD. It has been determined that surge arresters must be provided at cable terminals when the length of cable sections is less than 16 km to limit the core-ground overvoltage within the lightning impulse protective level (LIPL). The level of sheath-ground overvoltage is independent of the length of cable; however, it can be limited within LIPL by lowering the sheath grounding impedance to 1.2 Omega. Insulation coordination measures do not impact the likelihood of OHL insulators' flashover. The flashover performance of OHL can be improved by lowering the footing impedance of the second tower closest to the cable terminals, which is otherwise most likely to flashover.
引用
收藏
页数:24
相关论文
共 50 条
  • [31] Research on Lightning Interference Protection for HVDC Large-span Transmission Lines
    Hu, Yashan
    Zhang, Qun
    Li, Yan
    Wang, Qingshan
    Wang, Decheng
    Xi, Haibo
    2022 4TH INTERNATIONAL CONFERENCE ON SMART POWER & INTERNET ENERGY SYSTEMS, SPIES, 2022, : 643 - 647
  • [32] Transient Simulation of Lightning Strokes on HVDC Transmission Lines and Fault Pole Selection
    Xing, Luhua
    Weng, Haixia
    Wang, Liang
    Ma, Linlin
    Wu, Cheng
    Wang, Xiaobo
    PROCEEDINGS OF 2017 2ND INTERNATIONAL CONFERENCE ON POWER AND RENEWABLE ENERGY (ICPRE), 2017, : 219 - 224
  • [33] An integrated backflashover model for insulation coordination of overhead transmission lines
    Meliopoulos, APS
    Adams, W
    Casey, R
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 1997, 19 (04) : 229 - 234
  • [34] Transient Overvoltage on HVDC Overhead Transmission Lines With Background DC Space Charges and Impulse Corona
    Xiao, Fengnyu
    Zhang, Bo
    IEEE TRANSACTIONS ON POWER DELIVERY, 2021, 36 (05) : 2921 - 2928
  • [35] A Simplified Approach for Assessment of Exposure of EHV and UHV Lines to Direct Lightning Strikes
    Rizk, Farouk A. M.
    IEEE TRANSACTIONS ON POWER DELIVERY, 2018, 33 (05) : 2420 - 2427
  • [36] Identification of Lightning Strikes on Transmission Lines Based on Time-frequency Joint Analysis
    Chen, Xu
    Zhu, Yongli
    Zhao, Xuesong
    Zhao, Lei
    Guo, Xiaohong
    Gao, Yanfeng
    PROCEEDINGS OF THE 2015 INTERNATIONAL CONFERENCE ON INTELLIGENT SYSTEMS RESEARCH AND MECHATRONICS ENGINEERING, 2015, 121 : 823 - 826
  • [37] Incidence of Lightning Strikes to Power Transmission Lines in the South of Brazil: Current and Future Climate
    P. Naccarato, Kleber
    Paes Dos Santos, Ana Paula
    Lopes De Lima, Francisco Jose
    2022 36TH INTERNATIONAL CONFERENCE ON LIGHTNING PROTECTION (ICLP 2022), 2022, : 311 - 314
  • [38] Modeling Techniques for Lightning Overvoltage Analysis using the Example of Gas Insulated Transmission Lines (GIL)
    Goll, F.
    Witzmann, R.
    Neumann, C.
    Imamovic, D.
    2013 IEEE 1ST INTERNATIONAL CONFERENCE ON CONDITION ASSESSMENT TECHNIQUES IN ELECTRICAL SYSTEMS (CATCON), 2013, : 35 - 41
  • [39] Study of the Lightning Overvoltage Protection Effectiveness of High Voltage Mixed Overhead Cable Power Lines
    Tarko, Rafal
    Gajdzica, Jakub
    Nowak, Wieslaw
    Szpyra, Waldemar
    ENERGIES, 2021, 14 (08)
  • [40] Lightning Impulse Corona Characteristic of 1000-kV UHV Transmission Lines and Its Influences on Lightning Overvoltage Analysis Results
    Yang, Pengcheng
    Chen, Shuiming
    He, Jinliang
    IEEE TRANSACTIONS ON POWER DELIVERY, 2013, 28 (04) : 2518 - 2525