Four years monitoring of heat pump, solar thermal and PV system in two net-zero energy multi-family buildings

被引:31
|
作者
Dermentzis, Georgios [1 ]
Ochs, Fabian [1 ]
Franzoi, Nicola [1 ]
机构
[1] Univ Innsbruck, Unit Energy Efficient Bldg, Tech Str 13, A-6020 Innsbruck, Austria
来源
JOURNAL OF BUILDING ENGINEERING | 2021年 / 43卷
关键词
Monitoring; Heat pump; NZEB; Residential building; PV; Solar thermal; PERFORMANCE; NZEB; OPTIMIZATION; COST;
D O I
10.1016/j.jobe.2021.103199
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
This work presents four-year monitoring results of two new multi-family houses in Innsbruck aiming to be netzero energy buildings (NZEB). The project combines high-performance buildings designed in Passive House standard, highly-efficient HVAC systems i.e., low-temperature distribution and emission, a double-stage groundwater source heat pump including a desuperheater and mechanical ventilation with heat recovery, and maximum possible renewable sources i.e., roofs fully covered with photovoltaic panels (PV) and solar thermal collectors. The design goal of NZEB was to balance on an annual basis, the electricity consumption of the technical systems and the electricity production of the PVs, and later on the evaluation by means of a monitoring campaign. With a combination of high-performance technologies with respect to the building envelope, HVAC, and renewables, the measured annual onsite produced PV electricity is 6% (4-year average) higher than the one consumed by the heat pump. However, it was not sufficient to cover the consumption of all the technical systems (auxiliary and appliances). Concerning the building envelope, Passive House quality is recommended, concerning the HVAC, complex configuration seems not beneficial in practice and there was no clear indication of the benefit to implementing a desuperheater in this project. Solar thermal collectors produced 20% (4-year average) more heat per unit area than a PV-driven heat pump, however, the combination of both and the corresponding system complexity tends to show more negative aspects, and thus, a decision should be taken with care. Finally, it could be shown that reducing thermal losses and minimization of the auxiliary energies is of major importance to reach NZEB.
引用
收藏
页数:13
相关论文
共 41 条
  • [21] Performance assessment and optimization of a solar cooling system to satisfy renewable energy ratio (RER) requirements in multi-family buildings
    Bilardo, Matteo
    Ferrara, Maria
    Fabrizio, Enrico
    RENEWABLE ENERGY, 2020, 155 (155) : 990 - 1008
  • [22] Cost-optimal energy system design in Zero Energy Buildings with resulting grid impact: A case study of a German multi-family house
    Lindberg, Karen Byskov
    Fischer, David
    Doorman, Gerard
    Korpas, Magnus
    Sartori, Igor
    ENERGY AND BUILDINGS, 2016, 127 : 830 - 845
  • [23] Development of the smart photovoltaic system blind and its impact on net-zero energy solar buildings using technical-economic-political analyses
    Koo, Choongwan
    Hong, Taehoon
    Jeong, Kwangbok
    Ban, Cheolwoo
    Oh, Jeongyoon
    ENERGY, 2017, 124 : 382 - 396
  • [24] Net-zero energy management through multi-criteria optimizations of a hybrid solar-hydrogen energy system for a laboratory in Toronto, Canada
    Abdolmaleki, Leila
    Jahanbin, Aminhossein
    Berardi, Umberto
    ENERGY AND BUILDINGS, 2024, 312
  • [25] Economic analysis of the solar thermal and air source heat pump combined system for energy demand of buildings in China
    Fu, Feifei
    2020 6TH INTERNATIONAL CONFERENCE ON ENERGY MATERIALS AND ENVIRONMENT ENGINEERING, 2020, 508
  • [26] Multi-objective optimisation of a seasonal solar thermal energy storage system combined with an earth-Air heat exchanger for net zero energy building
    Benzaama, M. H.
    Menhoudj, S.
    Lekhal, M. C.
    Mokhtari, A.
    Attia, S.
    SOLAR ENERGY, 2021, 220 : 901 - 913
  • [27] In-depth techno-economic analysis of PV/Thermal plus ground source heat pump systems for multi-family houses in a heating dominated climate
    Sommerfeldt, Nelson
    Madani, Hatef
    SOLAR ENERGY, 2019, 190 : 44 - 62
  • [28] Improving energy flexibility of a net-zero energy house using a solar-assisted air conditioning system with thermal energy storage and demand-side management
    Ren, Haoshan
    Sun, Yongjun
    Albdoor, Ahmed K.
    Tyagi, V. V.
    Pandey, A. K.
    Ma, Zhenjun
    APPLIED ENERGY, 2021, 285
  • [29] Is a fan coil unit (FCU) an efficient cooling system for net-zero energy buildings (NZEBs) in tropical regions? An experimental study on thermal comfort and energy performance of an FCU
    Dezfouli, M. M. S.
    Dehghani-Sanij, A. R.
    Kadir, K.
    Suhairi, R.
    Rostami, Sh.
    Sopian, K.
    RESULTS IN ENGINEERING, 2023, 20
  • [30] A GA-based system sizing method for net-zero energy buildings considering multi-criteria performance requirements under parameter uncertainties
    Yu, Zhun
    Chen, Jiayu
    Sun, Yongjun
    Zhang, Guoqiang
    ENERGY AND BUILDINGS, 2016, 129 : 524 - 534