The effect of heat conduction through fins on the performance of finned-tube CO2 supercritical gas coolers

被引:7
|
作者
Zhang, X. [1 ]
Ge, Y. T. [1 ]
机构
[1] London South Bank Univ, Sch Built Environm & Architecture, 103 Borough Rd, London SE1 0AA, England
基金
“创新英国”项目; 英国工程与自然科学研究理事会;
关键词
CO2 finned-tube gas coolers; Split fins and continuous fins; Heat conduction along fins; Computational Fluid Dynamics (CFD); CO2 Transcritical cycles; CARBON-DIOXIDE; PLATE-FIN; EXCHANGER; SIMULATION;
D O I
10.1016/j.ijheatmasstransfer.2021.121908
中图分类号
O414.1 [热力学];
学科分类号
摘要
Air cooled CO2 finned-tube gas coolers are widely used in CO2 trans-critical refrigeration systems due to simplified structural designs. However, the longitudinal heat conduction along fins can lead to inverse heat transfer between adjacent tubes and thus capacity degradation of the heat exchanger. To cope with this adverse effect, the heat exchanger design with split fins between tube rows can be applied although further verification and analysis are expected. Subsequently, as explained in this paper, detailed CFD models have been purposely developed and simulated for the CO2 gas coolers with both continuous and split fins to quantify the effect of the heat conduction through fins. At various operating conditions of both air and refrigerant sides, totally 36 cases were simulated to study the influence of air inlet velocity, air inlet temperature, CO2 pressure and CO2 mass flow rate as well as the heat conduction along fins on the performance of the finned-tube gas coolers with and without split fins. The simulation results show that the approach temperature can be reduced by 0.6-7.5 K for the heat exchanger with split fins and a specific tube circuitry arrangement. Subsequently, the maximum and average heating capacities can be increased up to 22% and 10% respectively when the finned-tube CO2 gas cooler with split fins is applied. Furthermore, the simulation results show that the application of split fins should be designed and implemented appropriately based on different designs of tube circuitry arrangement in the heat exchanger. (c) 2021 Published by Elsevier Ltd.
引用
下载
收藏
页数:13
相关论文
共 50 条
  • [21] A Flexible Top-Down Numerical Modeling of an Air-Cooled Finned-Tube CO2 Trans-Critical Gas Cooler
    Maiorino, Angelo
    Aprea, Ciro
    Del Duca, Manuel Gesu
    ENERGIES, 2021, 14 (22)
  • [22] THE PERFORMANCE OF A COILED FINNED-TUBE HEAT-EXCHANGER SUBMERGED IN A HOT-WATER STORE - THE EFFECT OF THE EXCHANGERS ORIENTATION
    MOTE, R
    PROBERT, SD
    NEVRALA, D
    APPLIED ENERGY, 1991, 38 (01) : 1 - 19
  • [23] Experimental investigations on heat transfer of supercritical CO2 flowing through a helically coiled tube
    Wang, Shuxiang
    Niu, Zhiyuan
    Zhang, Wei
    Xu, Jinliang
    Hedongli Gongcheng/Nuclear Power Engineering, 2014, 35 (01): : 28 - 31
  • [24] CO2 Capture on an Adsorbent-Coated Finned Tube Heat Exchanger: Effect of the Adsorbent Thickness
    Esmaeili, Faezeh
    Hojjat, Mohammad
    Denayer, Joeri F. M.
    Gholami, Mohsen
    INDUSTRIAL & ENGINEERING CHEMISTRY RESEARCH, 2021, 60 (12) : 4677 - 4681
  • [25] Investigation of the Effect of Fin Configuration and Fin Angle on Thermal Performance of Finned-Tube Heat Exchanger. Experimental Study
    Goudarzi, K.
    THERMAL ENGINEERING, 2021, 68 (07) : 556 - 563
  • [26] Numerical investigation on the thermal-hydraulic performance of supercritical CO2 in a modified airfoil fins heat exchanger
    Han, Zengxiao
    Guo, Jiangfeng
    Liao, Haiyan
    Zhang, Zhongmei
    Huai, Xiulan
    JOURNAL OF SUPERCRITICAL FLUIDS, 2022, 187
  • [27] Investigation of the Effect of Fin Configuration and Fin Angle on Thermal Performance of Finned-Tube Heat Exchanger. Experimental Study
    K. Goudarzi
    Thermal Engineering, 2021, 68 : 556 - 563
  • [28] Performance of a tube-in-tube CO2 gas cooler
    Yu, Pei-Yu
    Lin, Kai-Hsiang
    Lin, Wei-Keng
    Wang, Chi-Chuan
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2012, 35 (07): : 2033 - 2038
  • [29] Flow and heat transfer characteristics of supercritical CO2 in vertical tube
    Zhu B.
    Wu X.
    Zhang L.
    Sun E.
    Zhang H.
    Xu J.
    Huagong Xuebao/CIESC Journal, 2019, 70 (04): : 1282 - 1290
  • [30] Simulation and Performance Evaluation of Finned Tube Gas Cooler for Trans-Critical CO2 Refrigeration System
    Gupta, Dileep Kumar
    Dasgupta, M. S.
    MECHANICAL ENGINEERING, MATERIALS AND ENERGY II, 2013, 281 : 324 - 328