Harmonic Stability Assessment for Multiparalleled, Grid-Connected Inverters

被引:112
|
作者
Yoon, Changwoo [1 ]
Bai, Haofeng [1 ]
Beres, Remus Narcis [1 ]
Wang, Xiongfei [1 ]
Bak, Claus Leth [1 ]
Blaabjerg, Frede [1 ]
机构
[1] Aalborg Univ, Dept Energy Technol, DK-9220 Aalborg, Denmark
基金
欧洲研究理事会;
关键词
Impedance based stability criterion; harmonic stability; distribution generation; inverter output impedance; grid impedance; passivity;
D O I
10.1109/TSTE.2016.2551737
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
This paper investigates the harmonic interactions of current controllers in multiparalleled grid-connected inverters. Potential harmonic instability phenomenon, which features oscillations above the fundamental frequency, is evaluated by the impedance-based stability criterion. The possible reasons of the destabilized inverter with different types of grid impedances are explained by the passivity-based analysis and impedance-based stability criterion. Thereafter, case studies are provided, which shows how the nonpassive grid connected inverters interact with the varying grid impedance due to load changes or by the new connections of other grid-connected inverters. Time domain simulations in the PSCAD/EMTDC environment and experimental results show the corresponding harmonic interaction problems may exist in nowadays power system and the impedance-based stability analysis can be an effective tool to assess those problems.
引用
收藏
页码:1388 / 1397
页数:10
相关论文
共 50 条
  • [21] Stability of grid-connected PV inverters with large grid impedance variation
    Liserre, M
    Teodorescu, R
    Blaabjerg, F
    PESC 04: 2004 IEEE 35TH ANNUAL POWER ELECTRONICS SPECIALISTS CONFERENCE, VOLS 1-6, CONFERENCE PROCEEDINGS, 2004, : 4773 - 4779
  • [22] Comparative Stability Analysis of Several Single-Phase Grid-Connected Inverters with Harmonic Compensation
    Troxler, John O.
    Cox, Robert W.
    2018 9TH IEEE INTERNATIONAL SYMPOSIUM ON POWER ELECTRONICS FOR DISTRIBUTED GENERATION SYSTEMS (PEDG), 2018,
  • [23] LCL Filter Design Method Based on Stability Region and Harmonic Interaction for Grid-connected Inverters in Weak Grid
    Liu F.
    Zhang Z.
    Ma M.
    Wang M.
    Deng J.
    Zhang J.
    Zhan M.
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2019, 39 (14): : 4231 - 4241
  • [24] Multirate Resonant Controllers for Grid-Connected Inverters With Harmonic Compensation Function
    Xie, Chuan
    Zhao, Xin
    Li, Kai
    Zou, Jianxiao
    Guerrero, Josep M.
    IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2019, 66 (11) : 8981 - 8991
  • [25] Optimization Configuration of Grid-Connected Inverters to Suppress Harmonic Amplification in a Microgrid
    Sun, Xing
    Lei, Wanjun
    Dai, Yuqi
    Yin, Yilin
    Liu, Qian
    ENERGIES, 2022, 15 (14)
  • [26] Impedance-Based Stability Criterion for Grid-Connected Inverters
    Sun, Jian
    IEEE TRANSACTIONS ON POWER ELECTRONICS, 2011, 26 (11) : 3075 - 3078
  • [27] Modeling and analysis of harmonic interaction between multiple grid-connected inverters and the utility grid
    Wang, F. (f.wang@shu.edu.cn), 2013, Chinese Society for Electrical Engineering (33):
  • [28] Improved DPC Strategy of Grid-connected Inverters under Unbalanced and Harmonic Grid Conditions
    Shen, Yongbo
    Nian, Heng
    2013 INTERNATIONAL CONFERENCE ON ELECTRICAL MACHINES AND SYSTEMS (ICEMS), 2013, : 1566 - 1570
  • [29] An improved LCL Filter Design Method Based on Stability Region and Harmonic Interaction for Grid-Connected Inverters in Weak Grid
    Zhang, Zhe
    Liu, Fang
    Deng, Jinxin
    Xie, Zhen
    Wang, Meng
    2018 IEEE INTERNATIONAL POWER ELECTRONICS AND APPLICATION CONFERENCE AND EXPOSITION (PEAC), 2018, : 1689 - 1693
  • [30] Stability Analysis of Grid-Connected Inverters with an LCL Filter Considering Grid Impedance
    Li, Xiao-Qiang
    Wu, Xiao-Jie
    Geng, Yi-Wen
    Zhang, Qi
    JOURNAL OF POWER ELECTRONICS, 2013, 13 (05) : 896 - 908