Experimental study on refrigerant maldistribution in a fin-and-tube evaporator for a direct expansion air-conditioning system

被引:6
|
作者
Tang, Haida [1 ]
Zhang, Tao [2 ]
Liu, Xiao-Hua [2 ]
机构
[1] Shenzhen Univ, Benyuan Design Res Ctr, Sch Architecture & Urban Planning, Shenzhen 518060, Peoples R China
[2] Tsinghua Univ, Dept Bldg Sci, Beijing 100084, Peoples R China
基金
中国国家自然科学基金;
关键词
Evaporator; Flow distribution; Suction header; Choked flow; Laboratory experiment; FUZZY-LOGIC CONTROLLER; CHINA ENERGY-CONSUMPTION; VARIABLE-SPEED; FLOW MALDISTRIBUTION; HEAT-EXCHANGERS; BUILDING SECTOR; HYBRID METHOD; HEADER; PERFORMANCE; MODEL;
D O I
10.1016/j.enbuild.2019.109638
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
In this paper, the design concept of the face split evaporator with a retrofitted suction header and choked flow in the capillary tubes was adopted to improve a direct expansion air-conditioning system with a designed air flow rate of 20,000 m(3)/h. The novel design of the direct expansion air-conditioning system was experimentally tested and validated. Face split evaporator reduced the refrigerant pressure drop in the suction header and the choked flow design limited the maximum flow rate across each branch circuit, which both contributed to the uniform refrigerant flow distribution of the improved system. Consequently, the cooling capacity and COP of the improved system was 10.5% and 13.4% higher than the original system. With the refrigerant mass flow rate of the improved system varying from 1.33 kg/s to 2.05 kg/s, the measured cooling capacity ranged 240-350 kW and the ratio of the system COP to the ideal COP of the reversed Carnot cycle with the same evaporating and condensing temperatures maintained at 0.72-0.74. The experimental results demonstrated that the improved system performed a relatively uniform refrigerant flow distribution among the branch circuit of the evaporator regardless of the refrigerant mass flow rate. This study is beneficial to the optimization design of the multi-circuit evaporator for a direct expansion air-conditioning system with a large air flow rate in engineering applications. (C) 2019 Elsevier B.V. All rights reserved.
引用
收藏
页数:10
相关论文
共 50 条
  • [1] Compensation of flow maldistribution in fin-and-tube evaporators for residential air-conditioning
    Kaern, Martin Ryhl
    Brix, Wiebke
    Elmegaard, Brian
    Larsen, Lars Finn Sloth
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2011, 34 (05): : 1230 - 1237
  • [2] Performance of residential air-conditioning systems with flow maldistribution in fin-and-tube evaporators
    Kaern, Martin Ryhl
    Brix, Wiebke
    Elmegaard, Brian
    Larsen, Lars Finn Sloth
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2011, 34 (03): : 696 - 706
  • [3] Sleeping evaporator and refrigerant maldistribution: An experimental investigation in an automotive multi-evaporator air-conditioning and battery cooling system
    Gillet, Thomas
    Andres, Emmanuelle
    El-Bakkali, Amin
    Lemort, Vincent
    Rulliere, Romuald
    Haberschill, Philippe
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2018, 90 : 119 - 131
  • [4] Refrigerant maldistribution in an evaporator of automotive air conditioning system: investigation and a design improvement by numerical simulations
    Stevanovic, V.
    Cucuz, S.
    Seeds, N.
    [J]. VEHICLE THERMAL MANAGEMENT SYSTEMS CONFERENCE PROCEEDINGS (VTMS 11), 2013, : 103 - 112
  • [5] Experimental study of a fin-and-tube heat exchanger working as evaporator in subatmospheric conditions
    Palomba, Valeria
    Frazzica, Andrea
    [J]. APPLIED THERMAL ENGINEERING, 2020, 175
  • [6] Transient Modeling of Refrigerant-to-Air Fin-and-Tube Heat Exchangers
    Ndiaye, Demba
    Bernier, Michel
    [J]. HVAC&R RESEARCH, 2010, 16 (03): : 355 - 381
  • [7] A numerical investigation of the refrigerant maldistribution from a header towards parallel channels in an evaporator of automotive air conditioning system
    Stevanovic, Vladimir
    Cucuz, Stojan
    Carl-Meissner, Waldemar
    Maslovaric, Blazenka
    Prica, Sanja
    [J]. INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2012, 55 (13-14) : 3335 - 3343
  • [8] THE TRIBOLOGY OF AN AUTOMOTIVE AIR-CONDITIONING SYSTEM WITH AN ALTERNATIVE REFRIGERANT
    NATSUME, Y
    ARAHIRA, K
    [J]. JOURNAL OF JAPANESE SOCIETY OF TRIBOLOGISTS, 1995, 40 (09) : 718 - 723
  • [9] Boiling Heat Transfer Coefficient of R22 and an HFC/HC Refrigerant Mixture in a Fin-and-Tube Evaporator of a Window Air Conditioner
    Raj, M.
    Lal, D.
    [J]. HEAT TRANSFER-ASIAN RESEARCH, 2010, 39 (06): : 410 - 439
  • [10] A heat exchanger model for air-to-refrigerant fin-and-tube heat exchanger with arbitrary fin sheet
    Singh, Varun
    Aute, Vikrant
    Radermacher, Reinhard
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2009, 32 (07): : 1724 - 1735