Review of modern diagnostic techniques for assessing insulation condition in aged transformers

被引:490
|
作者
Saha, TK [1 ]
机构
[1] Univ Queensland, Sch Informat Technol & Elect Engn, Brisbane, Qld 4072, Australia
关键词
insulation condition; transformer diagnostics; transformer ageing; dissolved gas analysis; furan analysis; degree of polymerization; oil insulation; cellulose paper; return voltage; polarisation current; depolarisation current; online monitoring; condition based monitoring;
D O I
10.1109/TDEI.2003.1237337
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Cellulosic paper and oil insulation in a transformer degrade at higher operating temperatures. Degradation is accelerated in the presence of oxygen and moisture. Power transformers being expensive items need to be carefully monitored throughout its operation. Well established time-based maintenance and conservative replacement planning is not feasible in a current market driven electricity industry. Condition based maintenance and online monitoring are now gaining importance. Currently there are varieties of chemical and electrical diagnostic techniques available for insulation condition monitoring of power transformers. This paper presents a description of commonly used chemical diagnostics techniques along with their interpretation schemes. A number of new chemical techniques are also described in this paper. In recent times a number of electrical diagnostic techniques have gained exceptional importance to the utility professionals. Among these techniques polarisation/depolarisation current measurement, return voltage measurement and frequency domain dielectric spectroscopy at low frequencies are the most widely used. This paper describes analyses and interpretation of these techniques for transformer insulation condition assessment.
引用
收藏
页码:903 / 917
页数:15
相关论文
共 50 条
  • [41] Review of condition assessment of power transformers in service
    Wang, M
    Vandermaar, AJ
    Srivastava, KD
    [J]. IEEE ELECTRICAL INSULATION MAGAZINE, 2002, 18 (06) : 12 - 25
  • [42] Feasibility of free radical detection for condition assessment of oil/paper insulation of transformers
    Abdolall, K.
    Vandermaar, A. J.
    [J]. CONFERENCE RECORD OF THE 2008 IEEE INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATION, VOLS 1 AND 2, 2008, : 182 - 186
  • [43] Return Voltage Measurements - a Promising Tool for the Diagnosis of the Insulation Condition of Power Transformers
    Patsch, Rainer
    [J]. 2018 IEEE INTERNATIONAL CONFERENCE ON HIGH VOLTAGE ENGINEERING AND APPLICATION (ICHVE), 2018,
  • [44] Experience with diagnostic tools for condition assessment of large power transformers
    Fuhr, J
    Aschwanden, T
    [J]. CONFERENCE RECORD OF THE 2004 IEEE INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATION, 2004, : 508 - 511
  • [45] Thermal stability of cellulose insulation in electrical power transformers - A review
    Jusner, Paul
    Schwaiger, Elisabeth
    Potthast, Antje
    Rosenau, Thomas
    [J]. CARBOHYDRATE POLYMERS, 2021, 252
  • [46] Method for assessing unevenness of cellulose insulation layers aging of power transformers winding
    Poliakov, M. O.
    Vasylevskyi, V. V.
    [J]. ELECTRICAL ENGINEERING & ELECTROMECHANICS, 2022, (05) : 47 - 54
  • [47] Application of dielectric response techniques for the condition assessment of power transformers
    Noirhomme, B
    David, E
    Garbi, H
    Lessard, MC
    Boissonneault, R
    [J]. 2005 Annual Report Conference on Electrical Insulation and Dielectric Phenomena, 2005, : 273 - 276
  • [48] An Overview on Condition Monitoring & Health Assessment Techniques for Distribution Transformers
    Youssef, Mohamed M.
    Ibrahim, Rania A.
    Desouki, Hussein
    Moustafa, Mohamed M. Zakaria
    [J]. 2022 6TH INTERNATIONAL CONFERENCE ON GREEN ENERGY AND APPLICATIONS (ICGEA 2022), 2022, : 187 - 192
  • [49] Diagnostic measurements on instrument transformers: A review and classification of diagnostic measurements
    Predl F.
    Freiburg M.
    Anglhuber M.
    [J]. e & i Elektrotechnik und Informationstechnik, 2018, 135 (6) : 423 - 434
  • [50] Diagnostic of insulation condition of oil impregnated paper insulation systems with return voltage measurements
    Hassan, O
    Borsi, H
    Gockenbach, E
    Aboelzahab, EM
    Gilany, MI
    [J]. 2003 ANNUAL REPORT CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA, 2003, : 153 - 156