Adjustable performance analysis of combined cooling heating and power system integrated with ground source heat pump

被引:48
|
作者
Wang, Jiangjiang [1 ]
Chen, Yuzhu [1 ]
Dou, Chao [1 ]
Gao, Yuefen [1 ]
Zhao, Zheng [2 ]
机构
[1] North China Elect Power Univ, Sch Energy Power & Mech Engn, Baoding 071003, Hebei, Peoples R China
[2] North China Elect Power Univ, Sch Control & Comp Engn, Baoding 071003, Hebei, Peoples R China
基金
中国国家自然科学基金;
关键词
Combined cooling heating and power system; Ground source heat pump; Primary energy ratio; Exergy efficiency; Adjustable area; EXERGY ANALYSIS; CCHP SYSTEM; ADSORPTION CHILLER; ECONOMIC-ANALYSIS; OPTIMAL-DESIGN; ENERGY; BIOMASS; OPTIMIZATION;
D O I
10.1016/j.energy.2018.08.143
中图分类号
O414.1 [热力学];
学科分类号
摘要
The difference in the electricity to cooling/heating ratio between a building and combined cooling, heating, and power (CCHP) system has a significant influence on the system configuration and performance. This paper designs a CCHP system coupled with a ground source heat pump (GSHP) to coordinate the match between system supplies and building demands. The energy flows in the cooling and heating work conditions are analyzed, and the thermodynamic models of components constructed. By means of a case study, the performances of the coupling CCHP system, under design and off-design working conditions, are evaluated and analyzed using energetic indicators, including the primary energy ratio and exergy efficiency, respectively. The adjustable areas expressed by electricity and cooling/heating, as well as the adjustable performance distributions, are obtained and discussed in order to guide operation regulation of the CCHP system integrated with the GSHP. Comparisons between the CCHP system with and without GSHP indicate that the coupling CCHP system in the specific case study can save averagely 40.6% and 39.5% of the primary energy in cooling and heating work conditions, respectively. (C) 2018 Elsevier Ltd. All rights reserved.
引用
收藏
页码:475 / 489
页数:15
相关论文
共 50 条
  • [41] Optimization and performance comparison of combined cooling, heating and power/ground source heat pump/photovoltaic/solar thermal system under different load ratio for two operation strategies
    Zeng, Rong
    Zhang, Xiaofeng
    Deng, Yan
    Li, Hongqiang
    Zhang, Guoqiang
    ENERGY CONVERSION AND MANAGEMENT, 2020, 208
  • [42] Thermodynamic analysis of a ground-source heat pump system for district heating
    Hepbasli, A
    INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 2005, 29 (07) : 671 - 687
  • [43] Performance analysis for solar photovoltaic/thermal-ground source heat pump hybrid heating system
    Liu X.
    Tian D.
    Lei Y.
    Hao X.
    Li D.
    Taiyangneng Xuebao/Acta Energiae Solaris Sinica, 2022, 43 (09): : 88 - 97
  • [44] Experimental performance analysis of a solar assisted ground-source heat pump greenhouse heating system
    Ozgener, O
    Hepbasli, A
    ENERGY AND BUILDINGS, 2005, 37 (01) : 101 - 110
  • [45] Combined system of solar heating and cooling using heat pump
    Zakhidov R.A.
    Anarbaev A.I.
    Zakhidov, R.A., 1600, Allerton Press Incorporation (50): : 178 - 183
  • [46] Performance evaluation of ground source heat pump system for greenhouse heating in northern China
    Chai, Lilong
    Ma, Chengwei
    Ni, Ji-Qin
    BIOSYSTEMS ENGINEERING, 2012, 111 (01) : 107 - 117
  • [47] Experimental investigation of the cooling performance of a ground source heat pump system in Denizli, Turkey
    Karabacak, Rasim
    Acar, Sengul Guven
    Kumsar, Halil
    Gokgoz, Ali
    Kaya, Mustafa
    Tulek, Yahya
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2011, 34 (02): : 454 - 465
  • [48] Energy conservation and emissions reduction analysis of cooling water of power plant source heat in pump heating system
    Li Yang
    Liang Xiujuan
    2012 WORLD AUTOMATION CONGRESS (WAC), 2012,
  • [49] Modeling and optimization of hybrid ground source heat pump with district heating and cooling
    Puttige, Anjan Rao
    Andersson, Staffan
    oestin, Ronny
    Olofsson, Thomas
    ENERGY AND BUILDINGS, 2022, 264
  • [50] Testing and Analysis of Thermal Performance of Ground Source Heat Pump System
    Qu Shilin
    Xu, Ge
    Liu Yimin
    Yu Qian
    2011 2ND INTERNATIONAL CONFERENCE ON CHALLENGES IN ENVIRONMENTAL SCIENCE AND COMPUTER ENGINEERING (CESCE 2011), VOL 11, PT B, 2011, 11 : 566 - 572