Effects of hot SF6 on post-arc circuit breaker design

被引:25
|
作者
Uchii, T [1 ]
Nishiwaki, S
Boggs, S
机构
[1] TM T&D Corp, Kawasaki, Kanagawa 2100862, Japan
[2] Univ Toronto, Dept Elect & Comp Engn, Toronto, ON, Canada
[3] Univ Connecticut, Dept Elect Engn, Elect Insulat Res Ctr, Storrs, CT 06269 USA
[4] Univ Connecticut, Dept Phys, Elect Insulat Res Ctr, Storrs, CT 06269 USA
关键词
Arc; gas circuit breaker; SF6; transient recovery voltage;
D O I
10.1109/TPWRD.2003.820210
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
SF6 is blown through the arc during interruption of an SF6 puffer circuit breaker. This hot gas flows down an exhaust tube into the chamber of a dead tank circuit breaker where it can lower the dielectric withstand between the exhaust tube and the tank of the circuit breaker, leading to dielectric breakdown during the transient recovery voltage after clearing. This paper presents experimental evidence that any such breakdown is controlled by,the hot gas near the exhaust tube, with cold gas in the remainder of gap having little effect on the breakdown voltage. This experimental conclusion is supported by a detailed theory for conditions under which breakdown can occur.
引用
收藏
页码:124 / 130
页数:7
相关论文
共 50 条
  • [1] Effects of hot SF6 on post-arc circuit breaker design
    Uchii, T
    Nishiwaki, S
    Boggs, S
    [J]. 2003 IEEE POWER ENGINEERING SOCIETY GENERAL MEETING, VOLS 1-4, CONFERENCE PROCEEDINGS, 2003, : 1934 - 1934
  • [2] The arcing and post-arc breakdown characteristics of SF6 generator circuit breaker based on magnetohydrodynamic model
    Yin, Jianning
    Zhao, Yongyong
    Zeng, Xiaobao
    Duan, Jiandong
    [J]. Physics of Fluids, 2024, 36 (11)
  • [3] SF6 post-arc recovery characteristics
    Spiliopoulos, I
    [J]. EUROPEAN TRANSACTIONS ON ELECTRICAL POWER, 2004, 14 (03): : 185 - 199
  • [4] Instability of DC arc in SF6 circuit breaker
    Ito, H
    Hamano, S
    Ibuki, K
    Yoshinaga, K
    Hasegawa, T
    Yamaji, K
    Irokawa, H
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 1997, 12 (04) : 1508 - 1513
  • [5] Characteristics Analysis of Arc Temperature in SF6 Circuit Breaker
    Lu Yangze
    Guan Yonggang
    Zhong Jianying
    Guo Yujing
    [J]. 2018 CHINA INTERNATIONAL CONFERENCE ON ELECTRICITY DISTRIBUTION (CICED), 2018, : 1705 - 1708
  • [6] THERMAL-ANALYSIS OF AN SF6 CIRCUIT BREAKER ARC
    SWANSON, BW
    ROIDT, RM
    [J]. IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1972, PA91 (02): : 381 - &
  • [7] BOUNDARY LAYER ANALYSIS OF AN SF6 CIRCUIT BREAKER ARC
    SWANSON, BW
    ROIDT, RM
    [J]. IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1971, PA90 (03): : 1086 - &
  • [8] Modified arc models in a SF6 power circuit breaker
    Sawicki, Antoni
    [J]. PRZEGLAD ELEKTROTECHNICZNY, 2018, 94 (04): : 91 - 94
  • [9] A ROTATING-ARC SF6 CIRCUIT-BREAKER
    PARRY, J
    [J]. ELECTRONICS AND POWER, 1981, 27 (10): : 725 - 727
  • [10] SF6 CIRCUIT-BREAKER DESIGN AND PERFORMANCE
    STEWART, JS
    [J]. ELECTRONICS AND POWER, 1979, 25 (02): : 121 - 126