Influence of household air-conditioning use modes on the energy performance of residential district cooling systems

被引:63
|
作者
Zhou, Xin [1 ]
Yan, Da [2 ]
Feng, Xiaohang [2 ]
Deng, Guangwei [3 ]
Jian, Yiwen [4 ]
Jiang, Yi [2 ]
机构
[1] Southeast Univ, Sch Architecture, Nanjing 210096, Jiangsu, Peoples R China
[2] Tsinghua Univ, Sch Architecture, Beijing 100084, Peoples R China
[3] Shanghai Res Inst, Bldg Sci Grp, Shanghai 610041, Peoples R China
[4] Beijing Univ Technol, Beijing 100084, Peoples R China
关键词
AC usage model; load distribution; residential district cooling system; uncertainty analysis; energy performance; THERMAL COMFORT; OCCUPANT BEHAVIOR; SIMULATION; EFFICIENCY; CONSUMPTION; BUILDINGS; DEST; OPTIMIZATION; VERIFICATION; METHODOLOGY;
D O I
10.1007/s12273-016-0280-9
中图分类号
O414.1 [热力学];
学科分类号
摘要
During technical evaluations of cooling systems in residential buildings, it is necessary to consider the influence of the household air-conditioning (AC) use modes. In other words, how the occupants control the AC, for instance, when it is turned on, what the temperature setting is, and how long it is used. Field measurements and spot interviews indicate that AC usage by residents should be environmental, event and random related. A reduced-order AC conditional probability (CP) model was developed in this study to describe AC usage. The AC CP model was integrated with a building energy modeling program (BEMP) to reflect the interaction of the AC operation and the indoor environment. With consideration of stochastic AC use modes, the uncertainty of user compositions was studied. Additionally, simulation results revealed that AC use modes and user compositions can cause up to a 4.5-fold difference in the system efficiency of district cooling systems. The Lorenz curve and Gini coefficient were applied in this study to describe the load distribution in a quantitative manner. Through a comparison with the constant schedule definition model, the study also identified inclusion of the stochastic feature of AC use modes and their compositions in simulations as being important to the technical evaluation of district cooling systems.
引用
收藏
页码:429 / 441
页数:13
相关论文
共 50 条
  • [31] Use of desiccant dehumidification to improve energy utilization in air-conditioning systems in Beirut
    Ghaddar, N
    Ghali, K
    Najm, A
    [J]. INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 2003, 27 (15) : 1317 - 1338
  • [32] A Simplified Air-conditioning Systems Model with Energy Management
    Dejvises, Jackravut
    Tanthanuch, Nutthaphong
    [J]. 2016 INTERNATIONAL ELECTRICAL ENGINEERING CONGRESS, IEECON2016, 2016, : 361 - 364
  • [33] AIR-CONDITIONING AND PARTICLE FILTRATION SYSTEMS FOR ENERGY SAVING
    TAKENAMI, T
    OHMI, T
    FUKUDA, S
    [J]. SOLID STATE TECHNOLOGY, 1989, 32 (04) : 161 - 168
  • [34] Decoupling the complexities of air-conditioning cooling energy use in express hotels by data mining approaches
    Chen, Shuqin
    Li, Xinyue
    Ma, Yuhang
    Wang, Zhichao
    [J]. INDOOR AND BUILT ENVIRONMENT, 2024, 33 (03) : 435 - 450
  • [35] Rational use of energy in the air-conditioning of computer centers
    Rationeller Energieeinsatz bei der Klimatisierung von Rechenzentren
    [J]. 1600, (42):
  • [36] Reducing energy consumption of air-conditioning systems in moderate climates by applying indirect evaporative cooling
    Cichon, Aleksandra
    Pacak, Anna
    Pandelidis, Demis
    Anisimov, Sergey
    [J]. 10TH CONFERENCE ON INTERDISCIPLINARY PROBLEMS IN ENVIRONMENTAL PROTECTION AND ENGINEERING EKO-DOK 2018, 2018, 44
  • [37] Energy Efficient Demand Control for Air-Conditioning Systems
    Tomita, Yasushi
    Kuwabara, Kenichi
    Kobayashi, Nobuhisa
    Murata, Junichi
    Goda, Tadahiro
    [J]. 2013 IEEE POWER AND ENERGY SOCIETY GENERAL MEETING (PES), 2013,
  • [38] Zoned heating, ventilation, and air-conditioning residential systems: A systematic review
    Rodriguez, Jose
    Fumo, Nelson
    [J]. JOURNAL OF BUILDING ENGINEERING, 2021, 43
  • [39] ENERGY CONSERVATION IN HEATING AND AIR-CONDITIONING PUMPING SYSTEMS
    RISHEL, JB
    [J]. ASHRAE JOURNAL-AMERICAN SOCIETY OF HEATING REFRIGERATING AND AIR-CONDITIONING ENGINEERS, 1974, 16 (06): : 37 - 40
  • [40] Performance evaluation of prototype microchannel evaporators for the residential air-conditioning application
    Cho, Honggi
    Cho, Keumnam
    [J]. HT2005: PROCEEDINGS OF THE ASME SUMMER HEAT TRANSFER CONFERENCE 2005, VOL 4, 2005, : 413 - 418