An energy exchange efficiency prediction approach based on multivariate polynomial regression for membrane-based air-to-air energy recovery ventilator core

被引:27
|
作者
Qiu, Shunian [1 ]
Li, Shan [1 ]
Wang, Fei [1 ]
Wen, Yang [2 ]
Li, Zhenhai [1 ]
Li, Zhengwei [1 ]
Guo, Jianfeng [3 ]
机构
[1] Tongji Univ, Sch Mech Engn, Shanghai 200092, Peoples R China
[2] East China Architect Design Inst, Shanghai 200002, Peoples R China
[3] Transtech New Mat Technol Co Ltd, Zhongshan 528437, Guangdong, Peoples R China
关键词
Membrane-based air-to-air energy recovery ventilator; Energy exchange efficiency; Multivariate polynomial regression; HEAT-EXCHANGER; THERMAL PERFORMANCE; CFD SIMULATION; SYSTEM; SAVINGS;
D O I
10.1016/j.buildenv.2018.12.052
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Air-to-air energy recovery ventilators (AERVs) are widely applied in building heating, ventilation, and air conditioning (HVAC) systems to reduce energy consumption by reducing heating and cooling loads caused by ventilation. Its energy exchange efficiency data are typically acquired experimentally and are time consuming to be applied to engineering fields when the number of working scenarios to be tested is large. Instead of manual labor and time, detailed numerical calculation methods require the characteristic information of the membrane material, which is difficult for manufacturers to provide. Hence, an energy exchange efficiency prediction approach based on a multivariate polynomial regression model is proposed herein to predict the energy exchange efficiency of the membrane-based AERV (MERV) core. In the proposed approach, a simplified numerical efficiency calculation model of a cross-flow air-to-air enthalpy exchanger is trained with a small sample of experimentally measured efficiency data. Subsequently, the trained model is adopted to predict the energy exchange efficiency of the MERV core made of the same membrane, under other flowrates and structures. As verified by the experimental data, the proposed approach can predict the energy exchange efficiency with absolute deviation limits within +/- 8.0%. Compared to detailed numerical calculation methods, the proposed approach requires less membrane characteristic information and calculations; thus, the proposed approach is practical for engineering applications to simulate the equipment performance over different conditions and help sizing the equipment with less requirements.
引用
收藏
页码:490 / 500
页数:11
相关论文
共 50 条
  • [21] Development of CFD model for membrane-based energy recovery ventilators
    Jafarizave, Mohammad
    Khaleghi, Ali
    Rezakazemi, Mashallah
    CHEMICAL ENGINEERING RESEARCH & DESIGN, 2019, 145 : 226 - 234
  • [22] A manufacturing process design for producing a membrane-based energy recovery ventilator with high aspect ratio support ribs
    Paul, Brian K.
    Kawula, Steven
    Song, Chuankai
    JOURNAL OF MANUFACTURING SYSTEMS, 2019, 52 : 242 - 252
  • [23] Air Pollution Quality Prediction Model Based on Clustering and Multivariate Regression
    Liu, Chong
    Wang, Xuguang
    Wang, Qingchuan
    EKOLOJI, 2019, 28 (107): : 2975 - 2988
  • [24] Innovative modeling and simulation of membrane-based dehumidification and energy recovery equipment
    Gao, Zhiming
    Rendall, Joe
    Nawaz, Kashif
    Abuheiba, Ahmad
    Abdelaziz, Omar
    CASE STUDIES IN THERMAL ENGINEERING, 2023, 43
  • [25] Recovering latent and sensible energy from building exhaust with membrane-based energy recovery ventilation
    Lekshminarayanan, Gayatri
    Croal, Michelle
    Maisonneuve, Jonathan
    SCIENCE AND TECHNOLOGY FOR THE BUILT ENVIRONMENT, 2020, 26 (07) : 1000 - 1012
  • [26] Independent air dehumidification with membrane-based total heat recovery: Modeling and experimental validation
    Liang, C. H.
    Zhang, L. Z.
    Pei, L. X.
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2010, 33 (02): : 398 - 408
  • [27] Efficiency and Core Loss Map Estimation with Machine Learning Based Multivariate Polynomial Regression Model
    Misir, Oguz
    Akar, Mehmet
    MATHEMATICS, 2022, 10 (19)
  • [28] A novel thermal energy storage based reversed-cycle defrosting technology for Air-to-air heat pumps
    Hu, W. J.
    Jiang, Y. Q.
    Han, Z. T.
    Yao, Y.
    Ma, Z. L.
    CRYOGENICS AND REFRIGERATION, PROCEEDINGS, 2008, : 755 - 759
  • [29] Regression prediction of the energy consumption of air source heat pump drying based on machine learning
    Yang S.
    Chen W.
    Yang M.
    Zhang Y.
    Li S.
    Pu Y.
    Yang L.
    Song W.
    Nongye Gongcheng Xuebao/Transactions of the Chinese Society of Agricultural Engineering, 2024, 40 (02): : 41 - 51
  • [30] Analysis of thermal performance and energy savings of membrane based heat recovery ventilator
    Zhang, YP
    Jiang, Y
    Zhang, LZ
    Deng, YC
    Jin, ZF
    ENERGY, 2000, 25 (06) : 515 - 527