Effects of ejector geometries on performance of ejector-expansion R410A air conditioner considering cooling seasonal performance factor

被引:41
|
作者
Jeon, Yongseok [1 ]
Jung, Jongho [1 ]
Kim, Dongwoo [1 ]
Kim, Sunjae [1 ]
Kim, Yongchan [1 ]
机构
[1] Korea Univ, Dept Mech Engn, Seoul 136713, South Korea
关键词
Ejector-expansion air conditioner; Two-phase ejector; Optimization; CSPF; REFRIGERATION SYSTEM; 2-PHASE EJECTOR; CYCLE; DEVICE; OPTIMIZATION; MODES; WORK;
D O I
10.1016/j.apenergy.2017.08.059
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The objective of this study was to investigate the effects of ejector geometries on the performance of an ejector expansion air conditioner (EEAC) considering the cooling seasonal performance factor (CSPF). The performance of the EEAC using R410A was measured and analyzed by varying the compressor speed, outdoor-bin temperature, operating pressures, nozzle-throat diameter, and mixing-section diameter. The EEAC in the medium capacity mode exhibited maximum coefficient of performance (COP) improvement, i.e., 7.5%, over the baseline (conventional) cycle. The optimum mixing-section diameter was determined to be 9 mm based on the CSPF. In addition, the optimum mixing-section diameter increased with an increase in the annual average outdoor temperature. The CSPF of the EEAC with the optimized mixing-section diameter improved in the range of 16.0-20.3% over the baseline cycle depending on the climatic conditions.
引用
收藏
页码:761 / 768
页数:8
相关论文
共 50 条
  • [21] Comprehensive performance evaluation on a transcritical CO2 ejector-expansion heat pump system
    Yang, Tianyang
    Yang, Yunchun
    Zou, Huiming
    Tian, Changqing
    Butrymowicz, Dariusz
    [J]. APPLIED THERMAL ENGINEERING, 2024, 254
  • [22] An experimental analysis of the impact of primary nozzle geometries on the ejector performance used in R141b ejector refrigerator
    Thongtip, Tongchana
    Aphornratana, Satha
    [J]. APPLIED THERMAL ENGINEERING, 2017, 110 : 89 - 101
  • [23] Performance analysis of low GWP refrigerants mixture as a substitute for R410A in residential air conditioner in tropical region
    Ng, WenBin
    Kamar, Haslinda Mohamed
    Kamsah, Nazri
    Wang, Fu-Jen
    [J]. INTERNATIONAL CONFERENCE ON SUSTAINABLE ENERGY AND GREEN TECHNOLOGY 2018, 2019, 268
  • [24] Ejector in R410A vapor compression systems with experimental quantification of two major mechanisms of performance improvement: Work recovery and liquid feeding
    Pottker, Gustavo
    Hrnjak, Pega
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2015, 50 : 184 - 192
  • [25] Experimental Investigation of an Air-Conditioner Performance and Chemical Compositions of Differently Sourced R410A and R22 Refrigerants
    Alabdulkarem, Abdullah
    Almutairi, Zeyad
    [J]. INTERNATIONAL JOURNAL OF THERMOPHYSICS, 2022, 43 (09)
  • [26] Experimental Investigation of an Air-Conditioner Performance and Chemical Compositions of Differently Sourced R410A and R22 Refrigerants
    Abdullah Alabdulkarem
    Zeyad Almutairi
    [J]. International Journal of Thermophysics, 2022, 43
  • [27] Development and performance of a heat driven R141b ejector air conditioner: Application in hot climate country
    Thongtip, Tongchana
    Aphornratana, Satha
    [J]. ENERGY, 2018, 160 : 556 - 572
  • [28] Charge-Air Cooling of High Performance Engines in an Ejector Refrigeration Cycle
    Beran, Tobias
    Gaertner, Jan
    Koch, Thomas
    [J]. INTERNATIONALER MOTORENKONGRESS 2021, 2021,
  • [29] Effect of Suction Nozzle Pressure Drop on the Performance of an Ejector-Expansion Transcritical CO2 Refrigeration Cycle
    Zhang, Zhenying
    Tian, Lili
    [J]. ENTROPY, 2014, 16 (08) : 4309 - 4321
  • [30] Performance analysis of dual ejector-expansion air source heat pump cycle with three-stage evaporation for cold region application
    Lu, Yu
    Yu, Mengqi
    Yu, Jianlin
    [J]. APPLIED THERMAL ENGINEERING, 2023, 226