A virtual supply airflow rate meter for rooftop air-conditioning units

被引:46
|
作者
Yu, Daihong [1 ]
Li, Haorong [1 ]
Yang, Mo [1 ]
机构
[1] Univ Nebraska Lincoln, Dept Architectural Engn, Omaha, NE 68182 USA
关键词
Virtual sensing technology; Virtual calibration methodology; Rooftop air-conditioning units; Airflow rate; Fault detection and diagnosis; FAULT-DETECTION; SENSORS; TEMPERATURE;
D O I
10.1016/j.buildenv.2010.12.017
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
A proper amount of supply airflow is critical in all kinds of air-based HVAC systems to maintain desired control effectiveness, energy efficiency and indoor air quality (IAQ). Although knowledge of supply airflow rate (SCFM) is certainly very important, measuring and monitoring SCFM in rooftop air-conditioning units (RTUs) by using the conventional SCFM metering devices are very costly and more than often problematic. This paper proposes a low-cost but accurate virtual SCFM meter to solve the dilemma for RTUs. The SCFM values are indirectly derived from a first-principle model in combination with accurate measurements of low-cost virtual or virtually calibrated temperature sensors. Modeling, uncertainty analysis and experimental evaluation through a wide range of laboratory testing for both cooling- and heating-based approaches are performed respectively in the development. The study reveals that the heating-based method surpasses the other in terms of its simplicity, accuracy (uncertainty is +/- 6.9% vs +/- 13.8%) and reliability and is chosen to be the virtual SCFM meter in RTUs. This cost-effective application is promising with a number of merits, such as easy to implement, economical for use, and generic in RTUs with the same constructed gas furnaces. For applications, it could be applied as a permanently installed monitoring tool to indicate the SCFM and/or to automatically detect and diagnose improper quantity of SCFM for RTUs. (C) 2010 Elsevier Ltd. All rights reserved.
引用
收藏
页码:1292 / 1302
页数:11
相关论文
共 50 条
  • [1] Virtual calibration of a supply air temperature sensor in rooftop air conditioning units
    Yu, Daihong
    Li, Haorong
    Yu, Yuebin
    Xiong, Jun
    HVAC&R RESEARCH, 2011, 17 (01): : 31 - 50
  • [2] An improved virtual calibration of a supply air temperature sensor in rooftop air conditioning units
    Yu, Daihong
    Li, Haorong
    Ni, Long
    Yu, Yanshun
    HVAC&R RESEARCH, 2011, 17 (05): : 798 - 812
  • [3] AIR-CONDITIONING UNITS
    DUNN, A
    BRITISH DENTAL JOURNAL, 1977, 142 (05) : 146 - 146
  • [4] Advanced AC drives key to innovative rooftop hybrid air-conditioning units
    HPAC Heating, Piping, AirConditioning Engineering, 2006, 78 (01): : 68 - 69
  • [5] A Virtual Supply Airflow Rate Sensor Based on Original Equipment Manufacturer Data for Rooftop Air Conditioners
    Hu, Yifeng
    Zhang, Yun
    Liu, Xiaoyu
    Li, Haorong
    Wang, Yubo
    JOURNAL OF ARCHITECTURAL ENGINEERING, 2024, 30 (01)
  • [6] AIR-CONDITIONING AND CONCEPT OF SUPPLY
    PIELKE, R
    KALTE UND KLIMATECHNIK, 1978, 31 (10): : 432 - 432
  • [7] Measurement of Airflow of Air-Conditioning in a Car with PIV
    Yang, J. H.
    Kato, S.
    Nagano, H.
    JOURNAL OF VISUALIZATION, 2009, 12 (02) : 119 - 130
  • [8] Measurement of airflow of air-conditioning in a car with PIV
    J. H. Yang
    S. Kato
    H. Nagano
    Journal of Visualization, 2009, 12 : 119 - 130
  • [9] ROOFTOP AIR-CONDITIONING VS ICE AND WATER STORAGE
    TAMBLYN, RT
    HEATING-PIPING-AIR CONDITIONING, 1985, 57 (03): : 117 - 120
  • [10] PERFORMANCE EVALUATION OF AIR-CONDITIONING UNITS
    ALBASSAM, E
    MAHESHWARI, GP
    RENEWABLE ENERGY, 1994, 4 (07) : 873 - 878