Characteristics of the Partial Discharge in the Development of Conductive Particle-Initiated Flashover of a GIS Insulator

被引:12
|
作者
Zhao, Junping [1 ,2 ]
An, Zhengjie [1 ,2 ]
Lv, Bin [1 ,2 ]
Wu, Zhicheng [1 ,2 ]
Zhang, Qiaogen [1 ,2 ]
机构
[1] State Key Lab Elect Insulat & Power Equipment, Xian 710049, Peoples R China
[2] Xi An Jiao Tong Univ, Sch Elect Engn, High Voltage Div, Xian 710049, Peoples R China
关键词
partial discharge; insulation defect; photomultiplier tube; PRPD pattern; flashover; SURFACE-CHARGE ACCUMULATION; GAS;
D O I
10.3390/en13102481
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Conductive particles are one of the most important defects which can greatly degrade the performance of gas-insulated metal-enclosed switchgear (GIS). Many efforts have been made to clarify the influence on the withstand voltage, understand the flashover mechanism, and build a comprehensive model to describe the particle-initiated flashover. In this study, a partial discharge (PD) signal detected through a photomultiplier (PMT) and recorded by a high-speed data acquisition (DAQ) system was used to analyze the discharge development of a conductive particle-contaminated GIS insulator under constant high AC voltage. An additional PMT was used as a reference to eliminate the dark count of the PMT and the data collection method of a DAQ system was optimized to capture the pulse waveform of each PD to obtain detailed physical information. Spectra of the PD pulse amplitude over pulse width, PD counts within various amplitude ranges over time and phase resolved partial discharge (PRPD) patterns of the PDs in different stages are obtained through the captured PD waveforms. Characteristics of the PDs from the application of the high AC voltage up to the flashover of the insulator were then analyzed, and it was found that the features of the PDs in the near-flashover stage were significantly different to the previous stages.
引用
收藏
页数:11
相关论文
共 50 条
  • [1] TIME-DEPENDENCE OF AC FLASHOVER CHARACTERISTICS FOR PARTICLE-INITIATED BREAKDOWN IN GIS
    LEIJON, MAS
    VLASTOS, AE
    IEEE TRANSACTIONS ON POWER DELIVERY, 1989, 4 (01) : 317 - 325
  • [2] Influence of Temperature on Partial Discharge and Flashover Characteristics of Metal Particle on GIS Insulator Surface
    Li X.
    Xu Y.
    Ding D.
    Liu W.
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2022, 42 (01): : 406 - 414
  • [3] Theoretical study of metallic particle motion and particle-initiated breakdown in GIS
    Matsumoto, Satoshi
    Aoyagi, Hirokuni
    Okubo, Hitoshi
    Kobayashi, Nobumitsu
    Yanabu, Satoru
    Electrical Engineering in Japan (English translation of Denki Gakkai Ronbunshi), 1989, 109 (01): : 22 - 30
  • [4] DC Partial Discharge and Flashover Characteristics and Charging Activity on Solid Insulator in Air
    Takabayashi, K.
    Furuyashiki, T.
    Sakai, T.
    Okubo, H.
    2016 IEEE CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA (IEEE CEIDP), 2016, : 352 - 355
  • [5] Influence of Conducting Particle on DC Flashover Characteristics and Tracking Property of GIS/GIL Insulator
    Li, Xiaolong
    Cao, Chen
    Lin, Xin
    IEEE ACCESS, 2022, 10 : 17212 - 17220
  • [6] Phase Resolved Partial Discharge Pattern of Free Conductive Particle Defects in GIS
    Wu Z.
    Zhang Q.
    Song J.
    Du Q.
    Li X.
    Li Z.
    Gaodianya Jishu/High Voltage Engineering, 2019, 45 (06): : 1995 - 2002
  • [7] Partial flashover characteristics of UHV DC insulator assemblies
    Takenaka, Akira
    Yasui, Mitsuru
    Electrical Engineering in Japan (English translation of Denki Gakkai Ronbunshi), 1988, 108 (04): : 32 - 41
  • [8] Partial Discharge Characteristics of GIS
    Wang Zhihui
    Gou Lin
    Wang Xinming
    APPLIED SCIENCE, MATERIALS SCIENCE AND INFORMATION TECHNOLOGIES IN INDUSTRY, 2014, 513-517 : 3532 - 3535
  • [9] Partial Discharge Initiated by Free Moving Metallic Particles on GIS Insulator Surface: Severity Diagnosis and Assessment
    Qi, Bo
    Li, Chengrong
    Xing, Zhaoliang
    Wei, Zhen
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2014, 21 (02) : 766 - 774
  • [10] Partial Discharge Measurement of GIS With Damped AC (DAC) Voltage: Case Study for the Particle on Insulator
    Zhao, Shujing
    Wang, Wei
    Qi, Zhiqiang
    Chen, Lianming
    Li, Chengrong
    Huang, Xingquan
    IEEE TRANSACTIONS ON POWER DELIVERY, 2023, 38 (03) : 1665 - 1673