Influence of Temperature on Partial Discharge and Flashover Characteristics of Metal Particle on GIS Insulator Surface

被引:0
|
作者
Li X. [1 ]
Xu Y. [2 ]
Ding D. [3 ]
Liu W. [1 ]
机构
[1] Department of Electrical Engineering, Tsinghua University, Haidian District, Beijing
[2] China Electric Power Research Institute, Haidian District, Beijing
[3] Sichuan Energy Internet Research Institute, Tsinghua University, Chengdu
关键词
Flashover; Gas-insulated switchgear (GIS) insulator; Metal particles; Partial discharge; Temperature;
D O I
10.13334/j.0258-8013.pcsee.210451
中图分类号
学科分类号
摘要
The metal particle on the insulator surface is an important cause of GIS insulator failure. In field operation, the insulators work is not only under electric stress, but also under temperature gradient. Therefore, it is of great significance to study the partial discharge (PD) and flashover characteristics of insulator surface defects under electrothermal coupling effect. In this paper, the electrothermal coupling experiment platform was established to study the PD and flashover characteristics of metal particles on the insulator surface under different temperature. The results show that when the maximum temperature of the insulator increases from 25℃ to 75℃, the PD inception voltage (PDIV) of metal particles decreases by about 16%, and the average and maximum apparent charge of PDs increased from 0.55pC and 9.1pC to 1.45pC and 11.5pC respectively, while the discharge repetition rate also increases from less than 200 times/s to nearly 400 times/s. However, the temperature has little effect on the flashover voltage. This paper is helpful to understand the influence of temperature on the PD and flashover characteristics of metal particle defects on insulator surface under electrothermal coupling effect. © 2022 Chin. Soc. for Elec. Eng.
引用
收藏
页码:406 / 414
页数:8
相关论文
共 29 条
  • [1] OKUBO H, BEROUAL A., Recent trend and future perspectives in electrical insulation techniques in relation to sulfur hexafluoride(SF<sub>6</sub>) substitutes for high voltage electric power equipment, IEEE Electrical Insulation Magazine, 27, 2, pp. 34-42, (2011)
  • [2] RIECHERT U, HOLAUS W., Ultra high-voltage gas-insulated switchgear-a technology milestone, European Transactions on Electrical Power, 22, 1, pp. 60-82, (2012)
  • [3] BOLIN P, KOCH H., Introduction and applications of gas insulated substation(GIS), IEEE Power Engineering Society General Meeting, 2005, pp. 920-926, (2005)
  • [4] ZHANG Xin, LI Gaoyang, HUANG Ronghui, Et al., Statistical analysis of defects and maintenance advice for GIS in different operating years above 110 kV, High Voltage Apparatus, 52, 3, pp. 184-188, (2016)
  • [5] XU Yuan, Investigation on mechanism of metallic particle induced flashover of GIS insulators in operation condition, (2020)
  • [6] LI Qingmin, WANG Jian, LI Botao, Et al., Review on metal particle contamination in GIS/GIL, High Voltage Engineering, 42, 3, pp. 849-860, (2016)
  • [7] BUDIMAN F N, KHAN Y, MALIK N H, Et al., Utilization of artificial neural network for the estimation of size and position of metallic particle adhering to spacer in GIS, IEEE Transactions on Dielectrics and Electrical Insulation, 20, 6, pp. 2143-2151, (2013)
  • [8] XU Yuan, LIU Weidong, CHEN Weijiang, Et al., Partial discharge characteristics of metal particles on spacer surface in GIS based on high sensitivity measurement, High Voltage Engineering, 45, 9, pp. 2707-2714, (2019)
  • [9] LI Yansong, LI Shiyan, QIU Zilai, Et al., Study on discharge characteristics of fixed metal particles on GIS insulator surface, Electrical Measurement & Instrumentation, 51, 15, pp. 33-36, (2014)
  • [10] KAMATH B R, SUNDARARAJAN J., Study of metallic particle induced partial discharge activity in 10: 90 SF<sub>6</sub>-N<sub>2</sub> gas mixtures, 2009 IEEE 9th International Conference on the Properties and Applications of Dielectric Materials, pp. 497-500, (2009)