Evaporative Cooling Options for Building Air-Conditioning: A Comprehensive Study for Climatic Conditions of Multan (Pakistan)

被引:14
|
作者
Noor, Shazia [1 ,2 ]
Ashraf, Hadeed [1 ]
Sultan, Muhammad [1 ]
Khan, Zahid Mahmood [1 ]
机构
[1] Bahauddin Zakariya Univ, Dept Agr Engn, Multan 60800, Pakistan
[2] Bahauddin Zakariya Univ, Dept Mech Engn, Multan 60800, Pakistan
关键词
Evaporative cooling systems; vapor compression air-conditioning; building air-conditioning; human thermal comfort; predicted mean vote (PMV); Pakistan; LIQUID DESICCANT; THERMAL COMFORT; MAISOTSENKO CYCLE; HEAT-EXCHANGER; ENERGY SAVINGS; SYSTEM; PERFORMANCE; COOLER; SIMULATION; WATER;
D O I
10.3390/en13123061
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
This study provides comprehensive details of evaporative cooling options for building air-conditioning (AC) in Multan (Pakistan). Standalone evaporative cooling and standalone vapor compression AC (VCAC) systems are commonly used in Pakistan. Therefore, seven AC system configurations comprising of direct evaporative cooling (DEC), indirect evaporative cooling (IEC), VCAC, and their possible combinations, are explored for the climatic conditions of Multan. The study aims to explore the optimum AC system configuration for the building AC from the viewpoints of cooling capacity, system performance, energy consumption, and CO(2)emissions. A simulation model was designed in DesignBuilder and simulated using EnergyPlus in order to optimize the applicability of the proposed systems. The standalone VCAC and hybrid IEC-VCAC & IEC-DEC-VCAC system configurations could achieve the desired human thermal comfort. The standalone DEC resulted in a maximum COP of 4.5, whereas, it was 2.1 in case of the hybrid IEC-DEC-VCAC system. The hybrid IEC-DEC-VCAC system achieved maximum temperature gradient (21 degrees C) and relatively less CO(2)emissions as compared to standalone VCAC. In addition, it provided maximum cooling capacity (184 kW for work input of 100 kW), which is 85% higher than the standalone DEC system. Furthermore, it achieved neutral to slightly cool human thermal comfort i.e., 0 to -1 predicted mean vote and 30% of predicted percentage dissatisfied. Thus, the study concludes the hybrid IEC-DEC-VCAC as an optimum configuration for building AC in Multan.
引用
收藏
页数:21
相关论文
共 50 条
  • [21] Energy consumption analysis and CFD simulation of the combined evaporative cooling and cooling ceiling air-conditioning system
    Huang, X.
    Li, Y. M.
    Wu, J. M.
    [J]. CRYOGENICS AND REFRIGERATION, PROCEEDINGS, 2008, : 596 - 599
  • [22] Energy performance of air-conditioning systems using an indirect evaporative, cooling combined with a cooling/reheating treatment
    Cianfrini, Claudio
    Corcione, Massimo
    Habib, Emanuele
    Quintino, Alessandro
    [J]. ENERGY AND BUILDINGS, 2014, 69 : 490 - 497
  • [23] Design on The Air-conditioning System's Automation of Evaporative Cooling Assisting to Mechanical Refrigeration
    Huang Xiang
    Lu Yong-mei
    Qiang Tian-wei
    Xiong Li
    [J]. 2010 INTERNATIONAL COLLOQUIUM ON COMPUTING, COMMUNICATION, CONTROL, AND MANAGEMENT (CCCM2010), VOL III, 2010, : 276 - 279
  • [24] An investigation on energy savings of a split air-conditioning using different commercial cooling pad thicknesses and climatic conditions
    Harby, K.
    Al-Amri, Fahad
    [J]. ENERGY, 2019, 182 : 321 - 336
  • [25] Experimental Study of Cooling Performance of Gravity Air-conditioning
    Li, Cuimin
    Zhao, Jianing
    Fang, Xiumu
    [J]. 6TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATING AND AIR CONDITIONING, VOLS I-III, PROCEEDINGS, 2009, : 504 - 510
  • [26] Simulation study on the operating characteristics of the heat pipe for combined evaporative cooling of computer room air-conditioning system
    Han, Zongwei
    Zhang, Yanqing
    Meng, Xin
    Liu, Qiankun
    Li, Weiliang
    Han, Yu
    Zhang, Yanhong
    [J]. ENERGY, 2016, 98 : 15 - 25
  • [27] Numerical study and optimization of the combined indirect evaporative air cooler for air-conditioning systems
    Anisimov, Sergey
    Pandelidis, Demis
    Danielewicz, Jan
    [J]. ENERGY, 2015, 80 : 452 - 464
  • [28] Study on Desiccant Air-Conditioning System for Livestock Application in Pakistan
    Niaz, Hassan
    Sultan, Muhammad
    Miyazaki, Takahiko
    Khan, Zahid M.
    [J]. 2018 2ND INTERNATIONAL CONFERENCE ON ENERGY CONSERVATION AND EFFICIENCY (ICECE), 2018, : 19 - 22
  • [29] SOLAR ASSISTED EVAPORATIVE COOLING BASED PASSIVE AIR-CONDITIONING SYSTEM FOR AGRICULTURAL AND LIVESTOCK APPLICATIONS
    Sultan, Muhammad
    Miyazaki, Takahiko
    Mahmood, Muhammad H.
    Khan, Zahid M.
    [J]. JOURNAL OF ENGINEERING SCIENCE AND TECHNOLOGY, 2018, 13 (03) : 693 - 703
  • [30] Reducing energy consumption of air-conditioning systems in moderate climates by applying indirect evaporative cooling
    Cichon, Aleksandra
    Pacak, Anna
    Pandelidis, Demis
    Anisimov, Sergey
    [J]. 10TH CONFERENCE ON INTERDISCIPLINARY PROBLEMS IN ENVIRONMENTAL PROTECTION AND ENGINEERING EKO-DOK 2018, 2018, 44