A New Two-Port Network Model-Based Pilot Protection for AC Transmission Lines

被引:25
|
作者
Liu, Shiming [1 ]
Zhang, Lu Liang [2 ]
Fu, Chuanshun [1 ]
Jiang, Lin [3 ]
机构
[1] Shandong Univ, Key Lab Power Syst Intelligent Dispatch & Control, Jinan 250061, Shandong, Peoples R China
[2] South China Univ Technol, Sch Elect Power Engn, Guangzhou 510640, Peoples R China
[3] Univ Liverpool, Dept Elect Engn & Elect, Liverpool L69 3BX, Merseyside, England
基金
中国国家自然科学基金;
关键词
Power transmission lines; Transmission line measurements; Transmission line matrix methods; Circuit faults; Current measurement; Voltage measurement; Synchronization; Pilot protection; transmission line; sequence components theory; two-port network; transmission network parameters; CURRENT DIFFERENTIAL PROTECTION; IMPEDANCE; SCHEME; RELAY;
D O I
10.1109/TPWRD.2019.2904310
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Conventional pilot protections used for EHV/UHV ac transmission lines require data synchronization between the two terminals of transmission line, and their performances are affected by the line capacitive charging current and load conditions. To tackle these problems, this paper proposes a new pilot protection scheme based on two-port network model of ac transmission lines. The new protection scheme calculates the two-port network parameters from the online measurements via the sequence components method, and then compares the solved parameters with their setting values to distinguish the internal and external faults. It does not require the data synchronization between two terminals of the transmission line. Moreover, its performance is not affected by the line capacitive charging current and load conditions. The applicability of the proposed scheme for series compensated lines is also analyzed. Effectiveness and accuracy of the proposed protection scheme have been verified by simulation tests.
引用
收藏
页码:473 / 482
页数:10
相关论文
共 50 条
  • [1] MODEL-BASED PHASE RETRIEVAL IN TWO-PORT MICROWAVE NETWORK MEASUREMENTS
    Fang, W.
    McNamara, D. A.
    MICROWAVE AND OPTICAL TECHNOLOGY LETTERS, 2011, 53 (03) : 495 - 499
  • [2] A loaded transmission line as a two-port network
    Tai, CT
    IEEE ANTENNAS AND PROPAGATION MAGAZINE, 2001, 43 (06) : 158 - 162
  • [3] Decentralized Estimation of Two-Port Equivalents for Power Transmission Lines
    Pradhan, Vedanta
    Naidu, O. D.
    Zubic, Sinisa
    Cost, Patrick
    IEEE ACCESS, 2021, 9 : 68223 - 68239
  • [4] Decentralized Estimation of Two-Port Equivalents for Power Transmission Lines
    Pradhan, Vedanta
    Naidu, O.D.
    Zubic, Sinisa
    Cost, Patrick
    IEEE Access, 2021, 9 : 68223 - 68239
  • [5] Transmission characteristics of two-port network terminated in varying load
    Zhu X.
    Zhu Y.-S.
    Dianzi Yu Xinxi Xuebao/Journal of Electronics and Information Technology, 2010, 32 (01): : 231 - 234
  • [6] Two-port quantum model of finite-length transmission lines coupled to lumped circuits
    Forestiere, Carlo
    Miano, Giovanni
    PHYSICAL REVIEW A, 2024, 109 (04)
  • [7] A novel two-port network model for RCPT system
    Zhang Xian
    Yang Qingxin
    Chen Haiyan
    Zhang Xin
    Jin Liang
    Li Yang
    COMPEL-THE INTERNATIONAL JOURNAL FOR COMPUTATION AND MATHEMATICS IN ELECTRICAL AND ELECTRONIC ENGINEERING, 2014, 33 (1-2) : 157 - 166
  • [8] Nonlinear two-port network DC model for FET
    Vikhorev, A. G.
    Matveev, S. Yu.
    Snournitsin, V. R.
    2005 Microwave Electronics: Measurements, Identification, Applications, 2005, : 111 - 116
  • [9] The Indoor Power Line Channel Model Based on Two-port Network Theory
    Li, Huangqiang
    Sun, Yunlian
    Yao, Yao
    ICSP: 2008 9TH INTERNATIONAL CONFERENCE ON SIGNAL PROCESSING, VOLS 1-5, PROCEEDINGS, 2008, : 132 - 135
  • [10] Intelligent two-port numerical algorithm for transmission lines disturbance records analysis
    Zoran Radojević
    Vladimir Terzija