Optimization of ground heat exchanger parameters of ground source heat pump system for space heating applications

被引:51
|
作者
Sivasakthivel, T. [1 ]
Murugesan, K. [1 ]
Sahoo, P. K. [1 ]
机构
[1] Indian Inst Technol, Dept Mech & Ind Engn, Roorkee, Uttar Pradesh, India
关键词
Ground heat exchanger length; Thermal resistance; COP (coefficient of performance); Taguchi optimization; Ground source heat pump; Utility concept; MULTIRESPONSE OPTIMIZATION; NEURAL-NETWORKS; U-TUBE; PERFORMANCE; DESIGN; HYBRID; ENERGY; METHODOLOGY; COMBINATION; PARALLEL;
D O I
10.1016/j.energy.2014.10.045
中图分类号
O414.1 [热力学];
学科分类号
摘要
In this paper Taguchi and utility methods have been employed to optimize eight important parameters (i.e. radius of U tube, borehole radius, heating load, grout conductivity, entering water temperature, distance between U tubes, U tube thermal conductivity and mass flow rate) of GHX (ground heat exchanger) used for space heating applications. Length of GHX, COP (coefficient of performance) and thermal resistance of GHX are considered as the objective functions. In Taguchi method lower the better concept is applied to obtain optimum values for the length of the GHX and its thermal resistance and for COP higher the better concept is used. In utility concept higher the better method has been employed. Based on the results obtained using Taguchi optimization, the optimum parameters and levels for GHX length, COP and GHX thermal resistances are found to be, A2B1C1D1E3F3G1I3, A2B2C1D3E3F3G1I2 and A1B2C1D2E1F1G3I1 respectively. Results obtained using the above optimized set of parameters show 15.17% reduction in the length of GHX, 2.5% increase in COP and 17.1% reduction in thermal resistance of GHX. The implementation of utility concept to obtain a single set of optimum parameters and levels resulted in 3.2% increase in GHX length, about 1.2% decrease in COP and 13.23% decrease in thermal resistance. (C) 2014 Elsevier Ltd. All rights reserved.
引用
收藏
页码:573 / 586
页数:14
相关论文
共 50 条
  • [21] Performance study of heat pipe heat exchanger for ground source heat pump
    Hsieh, Jui Ching
    Lin, David T.W.
    Shin, Long Der
    [J]. 1600, Chinese Mechanical Engineering Society (35): : 165 - 170
  • [22] A novel shallow bore ground heat exchanger for ground source heat pump applications-Model development and validation
    Warner, Joseph
    Liu, Xiaobing
    Shi, Liang
    Qu, Ming
    Zhang, Mingkan
    [J]. APPLIED THERMAL ENGINEERING, 2020, 164
  • [23] Performance optimization of a hybrid ground source heat pump with the parallel configuration of a ground heat exchanger and a supplemental heat rejecter in the cooling mode
    Park, Honghee
    Lee, Joo Seoung
    Kim, Wonuk
    Kim, Yongchan
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2012, 35 (06): : 1537 - 1546
  • [24] Municipal space heating using a ground source absorption heat pump driven by an urban heating system
    Zhang, Qunli
    Zhang, Xinchao
    Sun, Donghan
    Wang, Gang
    [J]. GEOTHERMICS, 2019, 78 : 224 - 232
  • [25] Heating system of biogas digester by ground-source heat pump
    Shi H.
    Wang T.
    Zhu H.
    Li Y.
    Rong L.
    Pei X.
    [J]. Nongye Gongcheng Xuebao/Transactions of the Chinese Society of Agricultural Engineering, 2010, 26 (02): : 268 - 273
  • [26] Evaluation of stainless steel pipe performance as a ground heat exchanger in ground-source heat-pump system
    Yoon, Seok
    Lee, Seung-Rae
    Kim, Min-Jun
    Kim, Woo-Jin
    Kim, Geon-Young
    Kim, Kyungsu
    [J]. ENERGY, 2016, 113 : 328 - 337
  • [27] Heating and cooling performance of a minitype ground source heat pump system
    Zhai, X. Q.
    Cheng, X. W.
    Wang, R. Z.
    [J]. APPLIED THERMAL ENGINEERING, 2017, 111 : 1366 - 1370
  • [28] District Feasibility Assessment for Wastewater Heat Exchanger Integrated Ground Source Heat Pump System
    Dacquay, Connor
    Lohrenz, Ed
    Hood, John
    [J]. ASHRAE TRANSACTIONS 2023, VOL 129, PT 1, 2023, 129 : 112 - 119
  • [29] Experimental and numerical investigation on a new type of heat exchanger in ground source heat pump system
    Liu, Xichen
    Xiao, Yimin
    Inthavong, Kiao
    Tu, Jiyuan
    [J]. ENERGY EFFICIENCY, 2015, 8 (05) : 845 - 857
  • [30] Experimental and numerical investigation on a new type of heat exchanger in ground source heat pump system
    Xichen Liu
    Yimin Xiao
    Kiao Inthavong
    Jiyuan Tu
    [J]. Energy Efficiency, 2015, 8 : 845 - 857