The behavior of arcing faults in low voltage switchboards

被引:0
|
作者
Land, HB [1 ]
机构
[1] Johns Hopkins Univ, Appl Phys Lab, Laurel, MD 20723 USA
关键词
arc; are fault; arc physics; electric breakdown; fires; power system protection; power distribution faults; switchgear; switchgear fires; voltage breakdown;
D O I
暂无
中图分类号
U6 [水路运输]; P75 [海洋工程];
学科分类号
0814 ; 081505 ; 0824 ; 082401 ;
摘要
An arc fault is the discharge of electricity through the air between two conductors creating large quantities of heat and light. It is widely accepted that there are many variables which affect the behavior of an arc in real switchboards and thus understanding the phenomena is difficult. This paper is based upon the results of several years of arc testing with circuits from 155 VDC to three phase 450 VAC and at power levels from tens of kilowatts to several megawatts. The goal of the testing was to understand the general behavior of arcing faults in low voltage switchboards well enough to predict the motion of arcs and to design electronic monitoring systems which are capable of protecting switchboards against arcs. This paper will focus on the arc behavior while our other papers will discuss its implications upon forensic investigations and upon the arc fault protective systems.
引用
收藏
页码:133 / 140
页数:8