Thirty-Six Years of Service Experience with a National Population of Gas-Insulated Substations

被引:66
|
作者
Istad, Maren [1 ,2 ]
Runde, Magne [1 ,2 ]
机构
[1] Norwegian Univ Sci & Technol, Dept Elect Power Engn, N-7034 Trondheim, Norway
[2] SINTEF Energy Res, NO-7465 Trondheim, Norway
关键词
Aging; end of life; failure analysis; gas-insulated substations (GIS); reliability; sulfur hexafluoride; switchgear;
D O I
10.1109/TPWRD.2010.2050705
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper shows the result of a failure survey including the entire population of gas-insulated substations in the Norwegian power transmission system. The survey comprises the complete service experience up to now-nearly 12 000 circuit-breaker years. Information about 180 failures has been recorded during 36 years: 77 internal flashovers/arcing faults have occurred, four of which burned through the encapsulation and another six caused the pressure-relief devices to operate. No severe injuries have been recorded. The overall failure rates and their causes are comparable to the findings of other reliability surveys, although the occurrence of severe arcing faults appears to be clearly higher than noticed elsewhere. The 300-kV and 420-kV gas-insulated substations put into service around 1980 have a significant and negative influence on the overall failure rate, whereas a large number of 145-kV substations installed since the early 1990s have proven very reliable. Even though a large portion of the population is above or approaching the designed service life of 30 years, no significant aging problems could be revealed with a basis in the failure statistics.
引用
收藏
页码:2448 / 2454
页数:7
相关论文
共 50 条
  • [1] EXPERIENCE WITH GAS-INSULATED SUBSTATIONS IN THE USA
    ERIKSSON, A
    PETTERSSON, KG
    KRENICKY, A
    BAKER, R
    OCHOA, JR
    LEIBOLD, A
    BOLIN, PC
    BOGGS, SA
    IEEE TRANSACTIONS ON POWER DELIVERY, 1995, 10 (01) : 210 - 218
  • [2] GAS-INSULATED AND HYBRID SUBSTATIONS
    Ruiz Flores, Luis Ivan
    Hernandez Munoz, Nestor A.
    Salazar Castro, Israel
    Martinez Torres, Valentin
    IEEE INDUSTRY APPLICATIONS MAGAZINE, 2014, 20 (05) : 64 - 70
  • [3] THIRTY-SIX YEARS OF "NATIONAL EMERGENCY" STRIKES
    Warren, Edgar L.
    INDUSTRIAL & LABOR RELATIONS REVIEW, 1951, 5 (01): : 3 - 19
  • [4] THIRTY-SIX YEARS OF JUDICIAL SERVICE OF RARE VARIETY
    Kunc, Justice Francois
    AUSTRALIAN LAW JOURNAL, 2024, 98 (04):
  • [5] Overvoltage protection of gas-insulated substations
    Simms, J.R.
    GEC Review, 1988, 4 (02): : 100 - 108
  • [6] DIAGNOSTIC METHODS FOR GAS-INSULATED SUBSTATIONS
    TAKAHASHI, Y
    IEEE TRANSACTIONS ON ELECTRICAL INSULATION, 1986, 21 (06): : 1037 - 1043
  • [7] GAS-INSULATED SUBSTATIONS FAULT SURVEY
    CHU, FY
    TAHILIANI, V
    IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1980, 99 (06): : 2351 - 2356
  • [8] Condition assessment of contacts in gas-insulated substations
    Runde, M
    Lillevik, O
    Larsen, V
    Skyberg, B
    Mjelve, A
    Tonstad, A
    IEEE TRANSACTIONS ON POWER DELIVERY, 2004, 19 (02) : 609 - 617
  • [9] Addendum I to bibliography of gas-insulated substations
    Anon
    IEEE Transactions on Power Delivery, 1992, v (0n) : 1003 - 1020
  • [10] Polycythemia vera in Chinese patients: Thirty-six years of experience
    Chim, CS
    Kwong, YL
    Chan, PT
    Liang, R
    AMERICAN JOURNAL OF HEMATOLOGY, 1997, 56 (01) : 59 - 62