Development of High Frequency Circuit Model for Oil-immersed Power Transformers and its Application for Lightning Surge Analysis

被引:32
|
作者
Okabe, Shigemitsu [1 ]
Koto, Masanori [1 ]
Ueta, Genyo [1 ]
Saida, Toshiyuki [2 ]
Yamada, Shin [2 ]
机构
[1] Tokyo Elect Power Co Ltd, Tsurumi Ku, Kanagawa 2308510, Japan
[2] Toshiba Co Ltd, Minato Ku, Tokyo 1058001, Japan
关键词
Oil-immersed transformer; lightning surge; high frequency circuit model; 500 kV substation; Electro-magnetic Transients Program;
D O I
10.1109/TDEI.2011.5739460
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The lightning impulse withstand voltage for an oil-immersed power transformer is determined by the value of the lightning surge overvoltage generated at the transformer terminal. This overvoltage value has been conventionally obtained through lightning surge analysis using the electromagnetic transients program (EMTP), where the transformer is often simulated by a single lumped capacitance. However, since high frequency surge overvoltages ranging from several kHz to several MHz are generated in an actual system, a transformer circuit model capable of simulating the range up to this high frequency must be developed for further accurate analysis. In this paper, a high frequency circuit model for an oil-immersed transformer was developed and its validity was verified through comparison with the measurement results on the model winding actually produced. Consequently, it emerged that a high frequency model with three serially connected LC parallel circuits could adequately simulate the impedance characteristics of the winding up to a high frequency range of several MHz. Following lightning surge analysis for a 500 kV substation using this high frequency model, the peak value of the waveform was evaluated as lower than that simulated by conventional lumped capacitance even though the front rising was steeper. This phenomenon can be explained by the charging process of the capacitance circuit inside the transformer. Furthermore, the waveform analyzed by each model was converted into an equivalent standard lightning impulse waveform and the respective peak values were compared. As a result, the peak value obtained by the lumped capacitance simulation was evaluated as relatively higher under the present analysis conditions.
引用
收藏
页码:541 / 552
页数:12
相关论文
共 45 条
  • [41] A SIMPLE MODEL OF HIGH-POWER THYRISTOR AND ITS APPLICATION IN EML TRANSIENT ANALYSIS
    Zhou, Y.
    Yan, P.
    Sun, Y. H.
    Wang, J.
    Li, M. T.
    2009 IEEE PULSED POWER CONFERENCE, VOLS 1 AND 2, 2009, : 1296 - 1299
  • [42] Development of Iterative Algorithm for High Frequency Transformer Used in Solid State Transformers and its Validation via Finite Element Analysis
    Joseph, Sherin
    John, Shajimon K.
    Pinkymol, K. P.
    Nair, K. R.
    IEEJ JOURNAL OF INDUSTRY APPLICATIONS, 2024, 13 (06) : 683 - 694
  • [43] ANALYSIS OF ELECTROMAGNETIC PROCESSES IN THE "VOLTAGE LIMITER - LOW-FREQUENCY FILTER" CIRCUIT DURING THE INFLUENCE OF HIGH-VOLTAGE SURGE FROM THE POWER SUPPLY NETWORK; [АНАЛІЗ ЕЛЕКТРОМАГНІТНИХ ПРОЦЕСІВ В КОЛІ «ОБМЕЖУВАЧ НАПРУГИ – ФІЛЬТР НИЖНІХ ЧАСТОТ» ЗА ДІЇ ВИСОКОВОЛЬТНОЇ ІМПУЛЬСНОЇ ЗАВАДИ З МЕРЕЖІ ЕЛЕКТРОЖИВЛЕННЯ]
    Pavlovskyi V.O.
    Gurin V.K.
    Yurchenko O.M.
    Technical Electrodynamics, 2023, 2023 (04): : 37 - 42
  • [44] A complete small-signal equivalent circuit model of cooled butterfly-type 2.5 Gbps DFB laser modules and its application to improve high frequency characteristics
    Lee, J
    Nam, S
    Lee, SH
    Jeong, J
    IEEE TRANSACTIONS ON ADVANCED PACKAGING, 2002, 25 (04): : 543 - 548
  • [45] Reduced-Order Dynamic Model of Modular Multilevel Converter in Long Time Scale and Its Application in Power System Low-Frequency Oscillation Analysis
    Zhu, Shu
    Liu, Kaipei
    Qin, Liang
    Ran, Xiaohong
    Li, Yuye
    Huai, Qing
    Liao, Xiaobing
    Zhang, Jian
    IEEE TRANSACTIONS ON POWER DELIVERY, 2019, 34 (06) : 2110 - 2122