On selection of supplementary input signals for STATCOM to damp inter-area oscillations in power systems

被引:0
|
作者
Farsangi, MM [1 ]
Song, YH [1 ]
Lee, KY [1 ]
机构
[1] Kerman Univ, Kerman, Iran
关键词
STATCOM; inter-area oscillation; stabilizing signal; input-output controllability analysis; minimum singular value; right half plane zeros; relative gain array;
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
This paper proposes a method to select the supplementary input signal for systems equipped with STATic synchronous COMpensators (STATCOM) to damp inter-area mode(s). Input-output observabiliy-controllability analysis, minimum singular value, right half plane zeros and relative gain array are used to assess the most appropriate supplementary input signal. The open-loop frequency of the system is shown to examine the sensitivity of the selected supplementary input signal to inter-area mode. The method is applied to select the input signal for a small power system equipped with a single STATCOM and for a large power system equipped with two STATCOMs.
引用
下载
收藏
页码:3068 / 3073
页数:6
相关论文
共 50 条
  • [31] Undamped inherent inter-area oscillations in power grids
    G. Hirsch
    Electrical Engineering, 2006, 88 : 259 - 273
  • [32] Low frequency inter-area oscillations. Are they dangerous for interconnected power systems or not?
    Izvestiya Akademii Nauk. Energetika, 2001, (04): : 69 - 82
  • [33] Analysis of the Inter-area Low Frequency Oscillations in Large Scale Power Systems
    Chen Xiangyi
    Li Chunyan
    Wang Yunli
    2011 6TH IEEE CONFERENCE ON INDUSTRIAL ELECTRONICS AND APPLICATIONS (ICIEA), 2011, : 1627 - 1631
  • [34] A Frequency-shaped Controller for Damping Inter-area Oscillations in Power Systems
    Wilches-Bernal, Felipe
    Schoenwald, David A.
    Pierre, Brian J.
    Byrne, Raymond H.
    IFAC PAPERSONLINE, 2020, 53 (02): : 13545 - 13550
  • [35] Impact of Wind Farm Placement on Inter-area Oscillations in Large Power Systems
    Gayme, Dennice F.
    Chakrabortty, Aranya
    2012 AMERICAN CONTROL CONFERENCE (ACC), 2012, : 3038 - 3043
  • [36] Nonlinear Oscillations Caused by Periodic Disturbance between Inter-area Power Systems
    Mao, DeTao
    Zhang, Peng
    Rahman, Hafiz Abdur
    Marti, Jose R.
    2008 IEEE ELECTRICAL POWER AND ENERGY CONFERENCE, 2008, : 89 - +
  • [37] Control strategies to damp inter-area oscillations using a Battery Energy Storage System
    Tsang, MW
    Sutanto, D
    PROCEEDINGS OF EMPD '98 - 1998 INTERNATIONAL CONFERENCE ON ENERGY MANAGEMENT AND POWER DELIVERY, VOLS 1 AND 2 AND SUPPLEMENT, 1998, : 241 - 246
  • [38] An adaptive neuro fuzzy power system stabilizer for damping inter-area oscillations in power systems
    Venugopal, AS
    Radman, G
    Abdelrahman, M
    PROCEEDINGS OF THE THIRTY-SIXTH SOUTHEASTERN SYMPOSIUM ON SYSTEM THEORY, 2004, : 41 - 44
  • [39] Controlling PMSG-based wind generation by a locally available signal to damp power system inter-area oscillations
    Pourfar, Iman
    Shayanfar, Heidar Ali
    Shanechi, Hasan Modir
    Naghshbandy, Ali H.
    INTERNATIONAL TRANSACTIONS ON ELECTRICAL ENERGY SYSTEMS, 2013, 23 (07): : 1156 - 1171
  • [40] Analysis of Inter-area Oscillations-based Switching Attack in Large Power Systems
    Bhatnagar, Nitesh
    Kotian, Shashidhara Mecha
    2022 IEEE 10TH POWER INDIA INTERNATIONAL CONFERENCE, PIICON, 2022,