Comparative analysis of optimal operation strategies for district heating and cooling system based on design and actual load

被引:24
|
作者
Deng, Na [1 ]
He, Guansong [1 ]
Gao, Yuan [1 ]
Yang, Bin [2 ]
Zhao, Jun [1 ]
He, Shunming [3 ]
Tian, Xue [1 ,3 ]
机构
[1] Tianjin Univ, MOE, Sch Environm Sci & Engn, Key Lab Efficient Utilizat Low & Medium Grade Ene, Tianjin 300350, Peoples R China
[2] Umea Univ, Dept Appl Phys & Elect, SE-90187 Umea, Sweden
[3] Tianjin Ecocity Construct & Investment Co Ltd, Tianjin 300467, Peoples R China
关键词
District heating and cooling; Design load; Actual load; Optimal operation strategy; THERMAL-ENERGY STORAGE; CCHP SYSTEMS; OPTIMIZATION; DEMAND; UNCERTAINTY; TECHNOLOGY; SIMULATION; IMPACTS; COST; PUMP;
D O I
10.1016/j.apenergy.2017.07.104
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Computational load significantly influences energy and cost savings when developing an operation strategy for a district heating and cooling system. In this study, a model was identified to study the effects of the difference between design load and actual load on an optimal operation strategy. The established model is strongly dependent on the economy principle, and the proposed optimal strategy could achieve a dynamic balance between the users' load and the system energy supply. This model was validated at 30% load rate, which demonstrated an obvious cost saving of 63.6% under the actual load and 42.2% under the design load. Based on the current strategy, the optimal strategy at different load rates was analyzed with respect to two characteristics of each subsystem: energy outputs and operation costs. Furthermore, in the optimal strategy, changes in total operation costs and cost savings rates under different load rates are also discussed. The results showed that, when the load rate was changed from 30 to 75%, the savings rates based on the design load were 42.2, 17.9, 2.5, and 12.6%, and the savings rates based on the actual load were 63.6, 49.8, 34.3, and 25.7%, respectively. Based on the actual load, the energy savings advantage of the optimal operation strategy could be maximized, in particular, during the initial stage of project construction. Furthermore, the commercial software MATLAB was used for programming and calculations. The simulation results indicated that the application of the combined cooling, heating, and power system could significantly improve the cost-effectiveness.
引用
收藏
页码:577 / 588
页数:12
相关论文
共 50 条
  • [31] Optimization method of district heating and cooling plant operation based on genetic algorithm
    Sakamoto, Yoshiyuki
    Nagaiwa, Akihiro
    Kobayasi, Syuichiro
    Shinozaki, Tsutomu
    ASHRAE Transactions, 105 (PA : 104 - 115
  • [32] Optimal operation of a multi-generation district energy hub based on electrical, heating, and cooling demands and hydrogen production
    Ebrahimi-Moghadam, Amir
    Farzaneh-Gord, Mahmood
    APPLIED ENERGY, 2022, 309
  • [33] Diameter optimization of district heating and cooling piping network based on hourly load
    Zeng, Jing
    Han, Jie
    Zhang, Guoqiang
    APPLIED THERMAL ENGINEERING, 2016, 107 : 750 - 757
  • [34] OPTIMAL INTERVALS OF GEOTHERMAL PIPE-LINE OF DISTRICT HEATING SYSTEM OPERATION
    Durickovic, Veljko V.
    ARCHIVES FOR TECHNICAL SCIENCES, 2010, (02): : 10 - 15
  • [35] Optimal Operation Strategy of Large-scale CHP in District Heating System
    Song, Hyoung-Yong
    Lee, Da-Han
    Roh, Jae Hyung
    Park, Jong-Bae
    Park, Yong-Gi
    JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY, 2024, 19 (05) : 2843 - 2858
  • [36] Comparison between design and actual energy performance of a HVAC-ground coupled heat pump system in cooling and heating operation
    Magraner, T.
    Montero, A.
    Quilis, S.
    Urchueguia, J. F.
    ENERGY AND BUILDINGS, 2010, 42 (09) : 1394 - 1401
  • [37] Heating, cooling, and electrical load forecasting for a large-scale district energy system
    Powell, Kody M.
    Sriprasad, Akshay
    Cole, Wesley J.
    Edgar, Thomas F.
    ENERGY, 2014, 74 : 877 - 885
  • [38] Design of a combined heating, cooling and power system: Sizing, operation strategy selection and parametric analysis
    Kavvadias, K. C.
    Tosios, A. P.
    Maroulis, Z. B.
    ENERGY CONVERSION AND MANAGEMENT, 2010, 51 (04) : 833 - 845
  • [39] Optimal design of a 5th generation district heating and cooling network based on seawater heat pumps
    Calise, Francesco
    Cappiello, Francesco Liberato
    Cimmino, Luca
    d'Accadia, Massimo Dentice
    Vicidomini, Maria
    ENERGY CONVERSION AND MANAGEMENT, 2022, 267
  • [40] Optimal Operation of Residential Cooling Heating and Power System Integrated with DR Programs
    Fang, Xinxin
    He, Xing
    2017 14TH INTERNATIONAL WORKSHOP ON COMPLEX SYSTEMS AND NETWORKS (IWCSN), 2017, : 39 - 44