Performance investigation of the natural draft wet cooling tower at different wet-bulb temperatures

被引:0
|
作者
Raj, Gaurav [1 ]
Chandra, Prakash [1 ]
Pathak, Piyush Kumar [1 ]
机构
[1] Natl Inst Technol, Dept Mech Engn, Patna, Bihar, India
关键词
Shade; wet-bulb temperature; tripal; aluminium-zinc alloy-coated steel sheet; correlation; regression equation; THERMAL PERFORMANCE; DRY; NANOFLUID; WALL;
D O I
10.1080/01430750.2021.1995487
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
This work experimentally investigated a natural draft wet cooling tower by varying the wet-bulb temperatures by shading. In this work, inlet air conditions were changed by shading of it using tripal and aluminium-zinc alloy-coated steel sheets at different water to air flow rate (L/G) ratios. It is observed that shading of cooling tower with tripal increases the tower characteristics up to 1.43 L/G ratio, whereas it increases up to 1.61 L/G ratio, when it is shaded with a steel sheet. Tripal shades increase the tower characteristics from 0.62% to 4.45% up to an L/G ratio of 1.43. Similarly, the steel sheet shading increases the tower characteristics from 1.46% to 14.48% up to an L/G ratio of 1.61. Finally, regression equations were developed for the coefficient of efficiency and water temperature difference with water flow rate at different wet-bulb temperatures.
引用
收藏
页码:5864 / 5872
页数:9
相关论文
共 50 条