An experimental study on the operating performance of a novel reverse-cycle hot gas defrosting method for air source heat pumps

被引:104
|
作者
Hu Wenju [2 ]
Jiang Yiqiang [2 ]
Qu Minglu [1 ]
Ni Long [2 ]
Yao Yang [2 ]
Deng Shiming [1 ]
机构
[1] Hong Kong Polytech Univ, Dept Bldg Serv Engn, Kowloon, Hong Kong, Peoples R China
[2] Harbin Inst Technol, Inst Heat Pump & Air Conditioning Technol, Harbin 150090, Peoples R China
关键词
Air source heat pumps; Defrosting; Thermal energy storage (TES); Phase change material (PCM); Reverse-cycle hot gas;
D O I
10.1016/j.applthermaleng.2010.09.024
中图分类号
O414.1 [热力学];
学科分类号
摘要
This paper reports on an experimental study on the operating performance for a novel reverse-cycle hot gas defrosting method for air source heat pumps (ASHPs). Firstly, a description of both an experimental prototype ASHP unit where the novel reverse-cycle hot gas defrosting method may be realized, and its operating modes are presented. This is followed by reporting an experimental set up for testing the defrosting performance of the prototype ASHP unit using the novel thermal energy storage (TES) based reverse-cycle hot gas defrosting method. Finally, experimental results are presented and discussed. The experimental results suggested that the use of the novel reverse-cycle hot gas defrosting method for the experimental ASHP unit was able to help shorten the defrosting time by similar to 3 min or 38%, and minimize the risk of shutting down the ASHP unit due to low suction pressure through increasing the compressor's suction pressure by about 200 kPa, when compared to the use of the traditional standard reverse-cycle hot gas defrosting method. In addition, when the TES based reverse-cycle hot gas defrosting method was used, the mean indoor coil surface temperature during defrosting was about 25 K higher than that when the traditional standard reverse-cycle hot gas defrosting method was used. These results suggested that as compared to the use of the traditional standard reverse-cycle hot gas defrosting method, the use of the novel TES based defrosting method would enable a quicker space heating resumption, impacting less on indoor thermal environment due to defrosting. Hence, the novel TES based defrosting method was proven to be effective in reducing the current problems in ASHPs using standard reverse-cycle hot gas defrosting method, such as a longer defrosting time and a poor system reliability. (C) 2010 Elsevier Ltd. All rights reserved.
引用
收藏
页码:363 / 369
页数:7
相关论文
共 50 条
  • [1] AN EXPERIMENTAL STUDY ON THE DEFROSTING PERFORMANCE OF A PCM-BASED REVERSE-CYCLE DEFROSTING METHOD FOR AIR SOURCE HEAT PUMPS
    Qu, Minglu
    Deng, Shiming
    Jiang, Yiqiang
    INTERNATIONAL JOURNAL OF AIR-CONDITIONING AND REFRIGERATION, 2010, 18 (04) : 327 - 337
  • [2] Operating performance of novel reverse-cycle defrosting method based on thermal energy storage for air source heat pump
    董建锴
    姜益强
    姚杨
    张雪丹
    Journal of Central South University of Technology, 2011, 18 (06) : 2163 - 2169
  • [3] Operating performance of novel reverse-cycle defrosting method based on thermal energy storage for air source heat pump
    Dong Jian-kai
    Jiang Yi-qiang
    Yao Yang
    Zhang Xue-dan
    JOURNAL OF CENTRAL SOUTH UNIVERSITY OF TECHNOLOGY, 2011, 18 (06): : 2163 - 2169
  • [4] Operating performance of novel reverse-cycle defrosting method based on thermal energy storage for air source heat pump
    Jian-kai Dong
    Yi-qiang Jiang
    Yang Yao
    Xue-dan Zhang
    Journal of Central South University of Technology, 2011, 18 : 2163 - 2169
  • [5] Improved indoor thermal comfort during defrost with a novel reverse-cycle defrosting method for air source heat pumps
    Qu Minglu
    Xia Liang
    Deng, Shiming
    Jiang Yiqiang
    BUILDING AND ENVIRONMENT, 2010, 45 (11) : 2354 - 2361
  • [6] An experimental investigation on reverse-cycle defrosting performance for an air source heat pump using an electronic expansion valve
    Qu, Minglu
    Xia, Liang
    Deng, Shiming
    Jiang, Yiqiang
    APPLIED ENERGY, 2012, 97 : 327 - 333
  • [7] Comparison of dynamic characteristics between the hot-gas bypass defrosting method and reverse-cycle defrosting method on an air-to-water heat pump
    Huang, Dong
    Yuan, Xiuling
    Hsi-An Chiao Tung Ta Hsueh/Journal of Xi'an Jiaotong University, 2006, 40 (05): : 539 - 543
  • [8] Comparison between hot-gas bypass defrosting and reverse-cycle defrosting methods on an air-to-water heat pump
    Huang, Dong
    Li, Quanxu
    Yuan, Xiuling
    APPLIED ENERGY, 2009, 86 (09) : 1697 - 1703
  • [9] Development and validation of a dynamic modeling framework for air-source heat pumps under cycling of frosting and reverse-cycle defrosting
    Ma, Jiacheng
    Kim, Donghun
    Braun, James E.
    Horton, W. Travis
    ENERGY, 2023, 272
  • [10] Experimental analysis of heat coupling during TES based reverse cycle defrosting method for cascade air source heat pumps
    Qu Minglu
    Zhang Rao
    Chen Jianbo
    Cheng Yuanda
    Zhao Xudong
    Zhang Tongyao
    Li Zhao